SPEC 25051

CSA TECK 90 1000V PVC POWER CABLE

1000V Multi Conductor, 8AWG -1000 Kcmil Copper, FT4 - Flame Retardancy Rating, XLPE Insulation, Aluminum Interlocked Armour, Sunlight Resistant, -40°C - 90°C, Rated HL, AG14

...

Construction:

  1. Conductor:Class B stranded copper, compressed or compact, in accordance with ASTM B3 and B8.
  2. Insulation:Cross-Linked Polyethylene (XLPE), Colour Code: 2/C black, white; 3/C red, black, blue; 4/C red, black, blue, white; For cables larger than No. 2 AWG or more than 4/C, the insulation is black and numbered
  3. Grounding Conductors:Uninsulated Class B stranded grounding conductor
  4. Inner Jacket:Black Polyvinyl Chloride (PVC)
  5. Armor:Aluminum Interlocked Armour (AIA). Galvanized Steel Interlocked Armour Optional (GSIA)
  6. Overall Jacket:Black PVC (optional colours available)

Applications and Features:

For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, or hazardous locations. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants. Rated for 1000 lbs./FT maximum sidewall pressure.
  • -40°C - CSA Cold Bend and Impact Temperature
  • -25°C - Min. Installation Temperature
  • 90°C - Max. Continuous Operating Temperature

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 131 Type TECK 90 Cable
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA AG14 - Acid Gas Compliance
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQMTR} SOUTHWIRE {CSA} LL90458 X/C XX AWG CU TECK 90 XLPE -40°C FT4 AG14 SUN RES 90°C 1000V HL USA
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.inchinchmilNo. x AWGAWGmilinchinchmilinchlb/1000ftlb/1000ft
    568605^870.1420.237451x1010650.610.809450.899135397
    671448870.1420.234451x1010650.6040.809450.899135397
    561963870.1420.234451x1010650.6410.846450.936187473
    561964870.1420.237451x1010650.710.906551.016238575
    573821^670.1780.304601x88650.7440.949451.039215540
    671452670.1780.304601x88650.7440.949451.039215540
    561965670.1780.304601x88650.7931.108451.198297717
    561966670.1780.304601x88850.9121.226451.316379895
    582005470.2250.351601x88850.8781.186551.296312800
    561967470.2250.351601x88850.9341.251451.341442961
    561968470.2250.351601x88851.0251.34451.435721153
    671456270.2830.409601x66850.9941.299551.4094961047
    571184^270.2830.409601x66850.9941.299551.4094961047
    561972270.2830.409601x66851.0591.363451.4537031283
    561973270.2830.409601x66851.1661.465451.5559101563
    5619741190.3220.489801x66851.2321.549551.6598651606
    5619751190.3220.489801x66851.3591.673551.78311261977
    5619761/0190.3620.528801x66851.3161.633551.74310701863
    5619781/0190.3620.528801x66851.4541.767551.87713992310
    5619482/0190.4050.572801x66851.4121.728551.83813272187
    5619492/0190.4050.572801x66851.561.885551.99517422789
    5864003/0190.4560.622801x44851.421.738651.8711772045
    5619503/0190.4560.622801x44851.521.814551.92417002623
    5619523/0190.4560.622801x441151.7411.989552.09922233344
    5619534/0190.5120.666801x44851.6151.943652.07521103207
    5619544/0190.5120.666801x441151.8482.175652.30727704150
    561955250370.5580.731901x441151.8152.146552.25624693762
    561956250370.5580.731901x441152.0052.332652.46432494775
    561957300370.6110.8901x441151.9642.295652.42729374389
    561958300370.6110.8901x441152.1722.499652.63138725529
    561959350370.6610.83901x331152.0292.36652.49234394940
    561960350370.6610.83901x331152.2452.571652.70345306244
    561961500370.7890.955901x331152.2992.63652.76248426546
    561962500370.7890.955901x331152.5472.873653.00564018344
    592314600610.8661.029901x221152.4592.79802.95658207713
    568478750610.9681.157901x221452.7953.116803.28472239513
    568479750610.9681.157901x221453.0963.424803.592956212223
    6411551000611.1171.306901x111453.1173.451803.619961612221
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ Colour Code: 2/C black, Red
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    86.32640.6530.810.05255
    86.32640.6530.810.05255
    86.63960.6530.810.05255
    87.15280.6530.810.05244
    67.34190.4110.510.05175
    67.34190.4110.510.05175
    68.46290.4110.510.05175
    69.28390.4110.510.05160
    49.16670.2580.320.04895
    49.410010.2580.320.04895
    41013350.2580.320.04876
    29.910610.1620.2010.045130
    29.910610.1620.2010.045130
    210.215920.1620.2010.045130
    210.921230.1620.2010.045104
    111.620080.1280.1590.046145
    112.526780.1280.1590.046116
    1/012.225340.1020.1270.044170
    1/013.133790.1020.1270.044136
    2/012.931940.0820.1020.043195
    2/01442590.0820.1020.043156
    3/013.126840.0640.0790.042225
    3/013.540270.0640.0790.042225
    3/014.753690.0640.0790.042180
    4/014.550780.0510.0630.041260
    4/016.167710.0510.0630.041208
    25015.860000.0430.0530.041290
    25017.280000.0430.0530.041232
    3001772000.0360.0450.041320
    30018.496000.0360.0450.041256
    35017.484000.0310.0390.04350
    35018.9112000.0310.0390.04280
    50019.3120000.0210.0270.039430
    50021160000.0210.0270.039344
    60020.7144000.0180.0240.039475
    75023180000.0140.0190.038535
    75025.1240000.0140.0190.038428
    100025.3240000.0110.0160.037615
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.mmmmmmNo. x AWGAWGmmmmmmmmmmkg/kmkg/km
    568605^873.616.021.141x10101.6515.4920.551.1422.83201591
    671448873.615.941.141x10101.6515.3420.551.1422.83201591
    561963873.615.941.141x10101.6516.2821.491.1423.77278704
    561964873.616.021.141x10101.6518.0323.011.4025.81354856
    573821^674.527.721.521x881.6518.9024.101.1426.39320804
    671452674.527.721.521x881.6518.9024.101.1426.39320804
    561965674.527.721.521x881.6520.1428.141.1430.434421067
    561966674.527.721.521x882.1623.1631.141.1433.435641332
    582005475.728.921.521x882.1622.3030.121.4032.924641191
    561967475.728.921.521x882.1623.7231.781.1434.066581430
    561968475.728.921.521x882.1626.0334.041.1436.328511716
    671456277.1910.391.521x662.1625.2532.991.4035.797381558
    571184^277.1910.391.521x662.1625.2532.991.4035.797381558
    561972277.1910.391.521x662.1626.9034.621.1436.9110461909
    561973277.1910.391.521x662.1629.6237.211.1439.5013542326
    5619741198.1812.422.031x662.1631.2939.341.4042.1412872390
    5619751198.1812.422.031x662.1634.5242.491.4045.2916762942
    5619761/0199.1913.412.031x662.1633.4341.481.4044.2715922772
    5619781/0199.1913.412.031x662.1636.9344.881.4047.6820823438
    5619482/01910.2914.532.031x662.1635.8643.891.4046.6919753255
    5619492/01910.2914.532.031x662.1639.6247.881.4050.6725924150
    5864003/01911.5815.802.031x442.1636.0744.151.6547.5017523043
    5619503/01911.5815.802.031x442.1638.6146.081.4048.8725303903
    5619523/01911.5815.802.031x442.9244.2250.521.4053.3133084976
    5619534/01913.0016.922.031x442.1641.0249.351.6552.7131404773
    5619544/01913.0016.922.031x442.9246.9455.241.6558.6041226176
    5619552503714.1718.572.291x442.9246.1054.511.4057.3036745598
    5619562503714.1718.572.291x442.9250.9359.231.6562.5948357106
    5619573003715.5220.322.291x442.9249.8958.291.6561.6543716532
    5619583003715.5220.322.291x442.9255.1763.471.6566.8357628228
    5619593503716.7921.082.291x332.9251.5459.941.6563.3051187352
    5619603503716.7921.082.291x332.9257.0265.301.6568.6667419292
    5619615003720.0424.262.291x332.9258.3966.801.6570.1572069742
    5619625003720.0424.262.291x332.9264.6972.971.6576.33952612417
    5923146006122.0026.142.291x222.9262.4670.872.0375.08866111478
    5684787506124.5929.392.291x223.6870.9979.152.0383.411074914157
    5684797506124.5929.392.291x223.6878.6486.972.0391.241423018190
    64115510006128.3733.172.291x113.6879.1787.662.0391.921431018187
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ Colour Code: 2/C black, Red
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmΩ/kmAmp
    8160.0211752.14242.660.170655
    8160.0211752.14242.660.170655
    8167.6417622.14242.660.170655
    8180.3423502.14242.660.170644
    6185.4218651.34841.670.167375
    6185.4218651.34841.670.167375
    6213.3627991.34841.670.167375
    6233.6837341.34841.670.167360
    4231.1429680.84651.050.157595
    4238.7644540.84651.050.157595
    4254.0059410.84651.050.157576
    2251.4647210.53150.660.1476130
    2251.4647210.53150.660.1476130
    2259.0870840.53150.660.1476130
    2276.8694470.53150.660.1476104
    1294.6489360.41990.520.1509145
    1317.50119170.41990.520.1509116
    1/0309.88112760.33460.420.1444170
    1/0332.74150370.33460.420.1444136
    2/0327.66142130.26900.330.1411195
    2/0355.60189530.26900.330.1411156
    3/0332.74119440.21000.260.1378225
    3/0342.90179200.21000.260.1378225
    3/0373.38238920.21000.260.1378180
    4/0368.30225970.16730.210.1345260
    4/0408.94301310.16730.210.1345208
    250401.32267000.14110.170.1345290
    250436.88356000.14110.170.1345232
    300431.80320400.11810.150.1345320
    300467.36427200.11810.150.1345256
    350441.96373800.10170.130.1312350
    350480.06498400.10170.130.1312280
    500490.22534000.06890.090.1280430
    500533.40712000.06890.090.1280344
    600525.78640800.05910.080.1280475
    750584.20801000.04590.060.1247535
    750637.541068000.04590.060.1247428
    1000642.621068000.03610.050.1214615
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.