SPEC 22230

CSA ACWU 90

600V Rating, 8000 Series ACM Aluminum Conductors, CSA Approved For Hazardous Locations, CSA -40°C Low Temperature Rating, CSA Sunlight Resistant, XLPE 90°C Insulation

...

Construction:

  1. Conductor:8000 Series ACM Aluminum Conductors
  2. Insulation:Low Temperature Cross-linked Polyethylene Insulation (XLPE)
  3. Grounding Conductors:Bare Aluminum Bonding Wire in Multi-conductor Cables
  4. Inner Jacket:Oil Impregnated Kraft Paper Binder
  5. Armor:Aluminum Interlocked Armour (AIA)
  6. Overall Jacket:Black PVC (optional colours available)

Applications and Features:

Southwire’s ACWU 90 cables are primarily intended for exposed and concealed wiring in dry or wet locations and where exposed to the weather. For use in ventilated, non-ventilated, ladder type cable trays and in all hazardous locations; direct earth burial; service entrance above or below ground.

Specifications:

  • CSA C22.2, No. 51 Armored Cables
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 0-M91 General Requirements
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA AG14 - Acid Gas Compliance
  • CSA AWM IB 105°C 600V. FT4-ST1
  • CSA Certified File Listing LL90458, CLASS 581801 - Armoured Cable
  • Sample Print Legend:

    {SQMTR} SOUTHWIRE {CSA} LL90458 X/C XX AWG AL ACM ACWU90 XLPE -40°C AG14 FT4 SUN. RES. 600V {YYYY}
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessDiameter Over ArmorApprox. ODAluminum WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilinchinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    6 AWG
    5641826370.169450.8991.0192223760.6740.8120.05155055black
    5663366470.169450.9591.0792574340.6740.8120.0515.34044black
    4 AWG
    5641834370.212450.9941.1142914670.4240.510.0485.56575black
    5663404470.212451.0711.2313445930.4240.510.0486.15260black
    2 AWG
    5641842360.268451.1071.2673816310.2670.3210.0456.390100black
    5663432460.268451.2041.3644607470.2670.3210.0456.87280black
    5642051380.298551.2231.3834657540.2110.2540.0466.9100115black
    5663461480.298551.3271.4875628970.2110.2540.0467.48092black
    5642061/03100.336551.2951.4555398470.1680.2010.0447.2120135black
    5663571/04100.336551.4081.57766110310.1680.2010.0447.896108black
    5642072/03120.376551.3811.5486349760.1330.160.0437.7135150black
    5663612/04120.376551.5131.70378112300.1330.160.0438.5108120black
    5642083/03160.422551.4831.6575011220.1050.1260.0428.2155175black
    5663653/04160.422551.6121.80294614190.1050.1260.0429124140black
    5642094/03190.474551.5891.77990713500.0840.10.0418.8180205black
    5663684/04190.474551.7381.928113416540.0840.10.0419.6144164black
    5642102503220.52651.731.92106515720.0710.0860.0419.6205230black
    5659092504220.52651.9052.095139019880.0710.0860.04112.5164184black
    5642123003350.569651.8482.038128318320.0590.0710.04112.2230260black
    5657413503350.615651.9472.137144720250.050.0620.0412.8250280black
    5661293504350.615652.1362.326181825010.050.0620.0413.9200224black
    5642145003350.735652.2062.396194426120.0350.0440.03914.3310350black
    5663715004350.735652.4262.646246333300.0350.0440.03915.8248280black
    5642156003580.812802.422.64227331380.0290.0370.03915.8340385black
    5642167503580.908802.6422.862276737230.0240.0310.03817.1385435black
    5660327504580.908802.9143.134353346740.0240.0310.03818.8308348black
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.004

    Updated On: Oct. 2, 2025, 1:11 a.m. UTC