SPEC 22068

SIMpull® RWU90 Aluminum 1000 Volt

Single 8000 Series Aluminum Conductor, 1000V Alumaflex Strand, No. 6 AWG to 1000 Kcmil, 90°C MAX -40°C MIN, Sunlight Resistant. SIMpull® technology on sizes #8 and larger. Cable can be installed in conduit without the aid of lubrication.

...

Construction:

  1. Conductor:Class B compact stranded bare aluminum per ASTM B800 and ASTM B801 or Single Input Wire (SIW) Compact AL per ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Southwire SIMpull® aluminum RWU90 is for open wiring used in raceways (except cabletroughs and ventilated flexible cableways) in dry or wet locations. For open wiring exposed to the weather. Minimum recommended installation temperature minus 40°C (with suitable handling procedures). Maximum conductor temperature 90°C. SIMpull® technology on sizes #8 and larger. Cable can be installed in conduit without the aid of lubrication.

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • Sample Print Legend:

    {SQMTR} SOUTHWIRE{R} LL90458 {CSA} XXX AWG (XX.X{mm2}) COMPACT AL. --- {ALUMAFLEX}{R} AA8176 RWU90 XLPE 1000 VOLTS -40{D}C SR
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    5689426770BK0.339551.3001570.6740.8120.05155
    5689434770BK0.383761.5002500.4240.5100.04875
    5689442670BK0.4381061.7003980.2670.3210.045100
    56894511895BK0.4991301.9005020.2110.2540.046115
    5687941/01895BK0.5261522.1006330.1680.2010.044135
    6624821/01895BK0.5361622.1006330.1680.2010.044135
    6631332/01295BK0.5761942.3007980.1330.1600.043150
    5708752/01295BK0.5761872.3007980.1330.1600.043150
    6631343/01595BK0.6232342.50010060.1050.1260.042175
    5707723/01695BK0.6232262.40010060.1050.1260.042175
    6631354/01995BK0.6752832.70012690.0840.1000.041205
    5687934/01995BK0.6752752.70012690.0840.1000.041205
    56879225022110BK0.743252.90015000.0710.0860.041230
    66313625022110BK0.7523423.00015000.0710.0860.041230
    66553135035110BK0.8484533.40021000.0500.0620.040280
    56879135035110BK0.8484413.30021000.0500.0620.040280
    66542840035110BK0.8915083.60024000.0440.0540.040305
    56878950034110BK0.976013.80030000.0350.0440.039350
    66542950034110BK0.9706163.90030000.0350.0440.039350
    59337360037108BK1.0777475.30036000.0290.0370.039385
    13870375061125BK1.1729075.90045000.0240.0310.038435
    56878875061125BK1.1728875.80045000.0240.0310.038435
    604121100058125BK1.32411536.60060000.0180.0250.037500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    568942671.78BK8.618233.026992.212.660.167355
    568943471.78BK9.7311338.1011131.391.670.157575
    568944261.78BK11.1315843.1817710.881.050.1476100
    5689451182.41BK12.6719348.2622340.690.830.1509115
    5687941/0182.41BK13.3622653.3428170.550.660.1444135
    6624821/0182.41BK13.6124153.3428170.550.660.1444135
    6631332/0122.41BK14.6328958.4235510.440.520.1411150
    5708752/0122.41BK14.6327858.4235510.440.520.1411150
    6631343/0152.41BK15.8234863.5044770.340.410.1378175
    5707723/0162.41BK15.8233660.9644770.340.410.1378175
    6631354/0192.41BK17.1542168.5856470.280.330.1345205
    5687934/0192.41BK17.1540968.5856470.280.330.1345205
    568792250222.79BK18.8048473.6666750.230.280.1345230
    663136250222.79BK19.1050976.2066750.230.280.1345230
    665531350352.79BK21.5467486.3693450.160.200.1312280
    568791350352.79BK21.5465683.8293450.160.200.1312280
    665428400352.79BK22.6375691.44106800.140.180.1312305
    568789500342.79BK24.6489496.52133500.110.140.1280350
    665429500342.79BK24.6491799.06133500.110.140.1280350
    593373600372.74BK27.361112134.62160200.100.120.1280385
    138703750613.18BK29.771350149.86200250.080.100.1247435
    568788750613.18BK29.771320147.32200250.080.100.1247435
    6041211000583.18BK33.631716167.64267000.060.080.1214500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM