SPEC 22068

SIMpull® RWU90 Aluminum 1000 Volt

Single 8000 Series Aluminum Conductor, 1000V Alumaflex Strand, No. 6 AWG to 1000 Kcmil, 90°C MAX -40°C MIN, Sunlight Resistant. SIMpull® technology on sizes #8 and larger. Cable can be installed in conduit without the aid of lubrication.

...

Construction:

  1. Conductor:Class B compact stranded bare aluminum per ASTM B800 and ASTM B801 or Single Input Wire (SIW) Compact AL per ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Southwire’s RWU90 is designed for direct earth burial (with protection as required by the inspecting authority). For service entrance above or below ground. The minimum recommended installation temperature is minus 40°C (with suitable handling procedures). Maximum conductor temperature is 90°C. Note: Standard black is sunlight resistant and marked "SR". Standard coloured insulation is not sunlight resistant. SIMpull® technology on sizes #8 and larger. Cable can be installed in conduit without the aid of lubrication.

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • Sample Print Legend:

    {SQMTR} SOUTHWIRE{R} LL90458 {CSA} XXX AWG (XX.X{mm2}) COMPACT AL. --- {ALUMAFLEX}{R} AA8176 RWU90 XLPE 1000 VOLTS -40{D}C SR
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    661721◊6780RD0.339551.3001570.6740.8120.05155
    568942◊6780BK0.339551.3001570.6740.8120.05155
    568943◊4780BK0.383761.5002500.4240.5100.04875
    662964◊4780WE0.383761.5002500.4240.5100.04875
    568944◊2680BK0.4381061.7003980.2670.3210.045100
    568945◊11895BK0.4991301.9005020.2110.2540.046115
    568794◊1/01895BK0.5261522.1006330.1680.2010.044135
    662482◊1/01895BK0.5361622.1006330.1680.2010.044135
    570875◊2/01295BK0.5761872.3007980.1330.1600.043150
    663133◊2/01295BK0.5761942.3007980.1330.1600.043150
    570772◊3/01695BK0.6232262.40010060.1050.1260.042175
    663134◊3/01595BK0.6232342.50010060.1050.1260.042175
    568793◊4/01995BK0.6752752.70012690.0840.1000.041205
    663135◊4/01995BK0.6752832.70012690.0840.1000.041205
    568792◊25022110BK0.743252.90015000.0710.0860.041230
    663136◊25022110BK0.7523423.00015000.0710.0860.041230
    665531◊35035110BK0.8484533.40021000.0500.0620.040280
    568791◊35035110BK0.8484413.30021000.0500.0620.040280
    665428◊40035110BK0.8915083.60024000.0440.0540.040305
    568789◊50034110BK0.976013.80030000.0350.0440.039350
    665429◊50034110BK0.9706163.90030000.0350.0440.039350
    593373◊60037125BK1.0777475.30036000.0290.0370.039385
    138703◊75061125BK1.1729075.90045000.0240.0310.038435
    568788◊75061125BK1.1728875.80045000.0240.0310.038435
    604121◊100058125BK1.32411536.60060000.0180.0250.037500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    661721◊672.03RD8.618233.026992.212.660.167355
    568942◊672.03BK8.618233.026992.212.660.167355
    568943◊472.03BK9.7311338.1011131.391.670.157575
    662964◊472.03WE9.7311338.1011131.391.670.157575
    568944◊262.03BK11.1315843.1817710.881.050.1476100
    568945◊1182.41BK12.6719348.2622340.690.830.1509115
    568794◊1/0182.41BK13.3622653.3428170.550.660.1444135
    662482◊1/0182.41BK13.6124153.3428170.550.660.1444135
    570875◊2/0122.41BK14.6327858.4235510.440.520.1411150
    663133◊2/0122.41BK14.6328958.4235510.440.520.1411150
    570772◊3/0162.41BK15.8233660.9644770.340.410.1378175
    663134◊3/0152.41BK15.8234863.5044770.340.410.1378175
    568793◊4/0192.41BK17.1540968.5856470.280.330.1345205
    663135◊4/0192.41BK17.1542168.5856470.280.330.1345205
    568792◊250222.79BK18.8048473.6666750.230.280.1345230
    663136◊250222.79BK19.1050976.2066750.230.280.1345230
    665531◊350352.79BK21.5467486.3693450.160.200.1312280
    568791◊350352.79BK21.5465683.8293450.160.200.1312280
    665428◊400352.79BK22.6375691.44106800.140.180.1312305
    568789◊500342.79BK24.6489496.52133500.110.140.1280350
    665429◊500342.79BK24.6491799.06133500.110.140.1280350
    593373◊600373.18BK27.361112134.62160200.100.120.1280385
    138703◊750613.18BK29.771350149.86200250.080.100.1247435
    568788◊750613.18BK29.771320147.32200250.080.100.1247435
    604121◊1000583.18BK33.631716167.64267000.060.080.1214500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM

    Revision: 1.000.013

    Updated On: May 5, 2026, 6:35 p.m. UTC