SPEC 60200

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor Multi Circuits

Copper THHN/THWN Insulated Singles. Multiple Circuits Green Insulated Copper Grounding Conductor. UL Listed 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid copper per ASTM B3 or 19-strand class C compressed copper and ASTM B3 and B8
  2. Insulation:Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green Polyvinyl Chloride with Nylon Sheath Type THHN/THWN insulated ground conductor
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Multi-Circuit Cable is suitable for use as follow:
• Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings
• Fished or embedded in plaster
• Concealed or exposed installations
• Environmental air-handling spaces per NEC 300.22 (C)
• Places of Assembly per NEC 518.4 and theaters per NEC 520.5
• Installation in cable tray and approved raceways
• Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
• Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations
• Binder tape with print legend wrapped around assembly
• Unjacketed Type MC cables are rated for dry, indoor locations only per NEC 330.10(A)(10)
• Type THHN/THWN rated 90ºC dry

Southwire Armorlite® Type MC Multi-Circuit Cable meets or exceeds the following requirements:
• UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
• Federal Specification A-A59544 (formerly J-C-30B)
• NFPA 70 (National Electrical Code), Article 330
• Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS WITH X X XX AWG NEUTRAL FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeNum x Neutral SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGNo. x AWGinchlbs/1000ftlbs/1000ft
    12 AWG | Solid
    587820124BN,BN/GY,OE,OE/GY,GY,GY/BN,GN0.08Solid151x122x120.577139210
    580743126BK,BK/WE,RD,RD/WE,BE,BE/WE,GN0.08Solid151x120.577139210
    641929126BK,BK,RD,RD,BE,BE,GN0.08Solid201x123x120.577139210
    644479129BK1,RD1,WE1,BK2,RD2,WE2,BK3,RD3,WeE0.08Solid201x123x120.843201338
    555951125BK,RD,BE,WE,WE/BK,GN0.080Solid201x122x120.577119187
    690057126See Table0.080Solid201x122x120.577139211
    589122126See Table0.080Solid201x124x120.700219318
    563324126See Table0.080Solid201x121x120.577139211
    690065128See Table0.080Solid201x122x120.652179266
    596437128See Table0.080Solid201x120.661179266
    586407129See Table0.080Solid201x124x120.709199294
    6793701210See Table0.080Solid201x126x120.886339507
    6900731212See Table0.080Solid201x123x120.810259401
    12 AWG | 19 Strands
    551354122BK,BK/WE,WE,WE/BK,RD,RD/WE,BE,GN,BE/WE0.08819201x122x120.688180276
    591220126BK,RD,BE,WE,PK,PK/WE,GN0.08819201x122x120.607140219
    551353124See Table0.09019201x122x120.607140220
    10 AWG | Solid
    587191102BK,RD,BE,OE,GN,GN/YW,WE,WE/RD0.101Solid252x102x100.777247382
    679155105RD,WT/RD,BE,WT/BE,BK/WT,WT/BK,RD/YW,WT/YW,BE/BK,BK0.101Solid251x105x100.951402590
    552970106See Table0.101Solid251x102x100.671216311
    690081106See Table0.101Solid251x102x100.759278417
    587714106BK,RD,BE,OE,PK,PE,GN0.101Solid251x100.680216311
    5980311010See Table0.101Solid251x104x100.884340506
    6791611010See Table0.101Solid251x106x101.042528753
    5529861012See Table0.101Solid251x103x100.947402587
    10 AWG | 19 Strands
    674430102BK,RD,BK/BE,RD/BE,WE,WE/BE,GN0.11319251x102x100.775226365
    679451103BK,BK,RD,RD,BE,BE,WT/BK,WT/RD,WT/BE,GN0.11319251x103x100.944323505
    5979361012BK,BK,RD,RD,BE,BE,WT,WT,WT,WT,WT,WT,GN0.11319251x106x101.014420632
    6778361012BK,RD,BE,WT,BK,RD,BE,WT,BK,RD,WT,WT,GN0.11319251x104x101.014420632
    674737104See Table0.11719251x102x100.776226365
    640523105See Table0.11719251x104x100.945323504
    551356108See Table0.11719251x102x100.879291457
    58364288See Table0.14319351x83x81.049463696
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberNeutral StrandingMin. Bend RadiusMax Pull TensionDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 60°CAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesLbsΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    12 AWG | Solid
    124242501.6622.0020.054162024
    12642501.6622.0020.054162024
    126341.6622.0020.0542024
    12935.91.6622.0020.0541715
    12524.11.6622.0020.0542024
    12624.11.6622.0020.0542024
    12645.01.6622.0020.0541215
    12614.11.6622.0020.0542024
    12824.61.6622.0020.0541721
    1284.61.6622.0020.0541721
    12945.01.6622.0020.0541721
    121066.21.6622.0020.0541215
    121235.71.6622.0020.0541215
    12 AWG | 19 Strands
    12224.81.6622.0020.0541215
    12624.21.6622.0020.0541721
    12424.31.6622.0020.0542024
    10 AWG | Solid
    10225.41.041.2530.052428
    10556.71.041.2530.051720
    10624.81.0401.2530.0502832
    10625.31.0401.2530.0502428
    1064.81.0401.2530.0502832
    101046.21.0401.2530.0501720
    101067.31.0401.2530.0501720
    101236.61.0401.2530.0501720
    10 AWG | 19 Strands
    10225.41.041.2530.052428
    10336.61.041.2530.051720
    101267.11.041.2530.051720
    101247.11.041.2530.051720
    10425.41.0401.2530.0502832
    10546.61.0401.2530.0502428
    10826.11.0401.2530.0501720
    8837.38450.6530.7860.0523538
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Color Table - ( / means stripe RD/WE is Red with White Stripe)

    Size (Strand)Cond. NumStock CodeColor
    12 (Solid)5555951BK, RD, BE, WE, WE/BK, GN
    12 (Solid)6690057BK, BK/WE, WE, WE/BK, RD, RD/WE, GN
    12 (Solid)6589122BK, RD, BE, BK/WE, RD/WE, BE/WE, WE, WE/BK, WE/RD, WE/BE, GN
    12 (Solid)6563324BK, BK/WE, RD, RD/WE, BE, WE, GN
    12 (Solid)8690065BK, BK/WE, WE, WE/BK, RD, RD/WE, BE, BE/WE, GN
    12 (Solid)8596437BK, RD, BE, BK/WE, RD/WE, BE/WE, RD/BK, BK/RD, GN
    12 (Solid)9586407OE, GY/OE, BK, WE/BK, RD, WE/RD, BE, BK/WE, GN, WE
    12 (Solid)10679370BK, RD, BK/RD, RD/BK, BE/RD, BK 1, BK 2, BK/WE, RD/WE, BE/WE, WE/BK, WE/BE, WE/RD, WE, WE 1, WE 2, GN
    12 (Solid)12690073BK, BK/WE, BK/RD, RD, RD/WE, RD/BK, BE, BE/WE, BE/RD, WE, WE/BK, WE/RD, GN
    12 (19)4551353BK, BK/WE, WE, WE/BK, RD, GN, RD/WE
    10 (Solid)6552970BK, RD, BK/WE, RD/WE, WE, WE/BK, GN
    10 (Solid)6690081BK, BK/WE, WE, WE/BK, RD, RD/WE, BE, BE/WE, GN
    10 (Solid)6587714BK, RD, BE, OE, PK, PE, GN
    10 (Solid)10679161BK, WE, RD, WE/RD, BE, WE/BE, BK/WE, WE/BK, RD/YW, WE/YW, BE/OE, WE/OE, PE, PE/WE, PK, PK/WE, GN
    10 (Solid)10598031BK, RD, BE, BK/WE, RD/WE, BE/WE, WE, WE/BK, WE/RD, WE/BE, GN
    10 (Solid)12552986BK, BK/WE, BK/RD, WE, WE/BK, WE/RD, RD, RD/WE, RD/BE, BE, BE/WE, BE/RD, GN
    10 (19)4674737BK, BK/WE, RD, RD/WE, WE, WE/BK, GN
    10 (19)5640523BK, RD, BE, OE, YW, WE/BK, WE/RD, WE/OE, WE/YW, GN
    10 (19)8551356BK, BK/WE, WE, WE/BK, RD, RD/WE, BE, GN, BE/WE
    8 (19)8583642BK, BK/WE, RD, RD/WE, BE, WE, WE/BK, WE/RD, GN

    Revision: 1.000.021

    Updated On: Feb. 17, 2026, 6:46 p.m. UTC