SPEC 81104

15kV CU 100% TRXLPE One-Third Neutral LLDPE

Single Conductor, 175 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed stranded soft drawn bare copper per ASTM B3 and ASTM B8 (Conductor moisture block optional and tinned copper per ASTM B33 optional)
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes; PowerGlide® LLDPE jacket optional

For information about our Cable-Rejuvenation Services please visit us at:  Cable-Rejuvenation Services
You can email us at: Cable-Rejuvenation Services

Applications and Features:

Southwire's 15kV cables are suited for use in wet and dry areas, conduits, ducts, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation. 130°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Rural Utility Standard RUS 1728F-U1 or 1728.204 (Electric standards and specifications for materials and construction)
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA 68.5: -40ºC and MV 90ºC optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] CU 15000 VOLTS TRXLPE INSULATION 175 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    TBA2 (Solid)0.2570.6451750.7356x140.438500.9635687.7530
    6281842 (7)0.2820.6631750.7536x140.438500.9815717.8530
    689828#!2 (7)0.2820.6631750.7536x140.438500.9815697.8530
    TBA1 (Solid)0.2890.6771750.7677x140.375500.9956518.0669
    TBA1 (19)0.3220.7101750.8007x140.375501.0286688.2669
    TBA1/0 (Solid)0.3240.7121750.8029x140.292501.0307638.2844
    6161541/0 (19)0.3610.7421750.8329x140.292501.0607678.5844
    6281872/0 (19)0.4050.7861750.87611x140.239501.1048988.81064
    TBA3/0 (19)0.4560.8441750.93414x140.187501.16210879.31342
    6281894/0 (19)0.5120.8921750.98218x140.146501.21012789.71692
    614035#4/0 (19)0.5120.8921750.98211x120.150501.24312889.91692
    600829§250 (37)0.5580.9481751.03813x120.127501.299149010.42000
    628192350 (37)0.6611.0511751.16118x120.092501.422197211.42800
    614878#350 (37)0.6611.0511751.16118x120.092501.422195311.42800
    622071500 (37)0.7891.1791751.28926x120.063501.550266312.44000
    611445#500 (37)0.7891.1791751.28926x120.063501.550266312.44000
    628194500 (37)0.7891.1791751.28917x100.061501.592272412.74000
    628195750 (61)0.9681.3681751.47825x100.041751.835392814.76000
    6281971000 (61)1.1171.5171751.62726x90.031752.009507016.18000
    628576^1000 (61)1.1171.5171751.62726x90.031752.009507116.18000
    6281991000 (61)1.1171.5171751.62721x80.031752.038539316.38000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ! No moisture block on conductor
    ^ HiDri Plus - Water Blocking Powder. Black Jacket
    # All black jacket
    § HiDri Plus - Water Blocking Powder. Black Jacket. CSA Listed
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence ImpedancePositive Sequence ImpedanceShort Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (Solid)0.1620.2040.0530.0520.1630.40.257 + j1.2810.204 + j0.5712092160195
    2 (7)0.1620.2040.0490.0500.1750.50.257 + j1.2240.204 + j0.5142092160195
    2 (7)0.1620.2040.0490.0500.1750.50.257 + j1.2240.204 + j0.5142092160195
    1 (Solid)0.1280.1620.0490.0500.1750.50.216 + j1.2120.162 + j0.5022441180220
    1 (19)0.1280.1620.0460.0480.1870.50.216 + j1.1530.162 + j0.4452441180220
    1/0 (Solid)0.1020.1280.0450.0480.1880.50.182 + j1.1500.128 + j0.4413138200250
    1/0 (19)0.1020.1280.0420.0460.2050.50.182 + j1.0980.128 + j0.3903138200250
    2/0 (19)0.0810.1020.0390.0450.2210.60.156 + j1.0490.102 + j0.3433836230285
    3/0 (19)0.0640.0810.0360.0430.2370.60.135 + j1.0020.081 + j0.2994882260320
    4/0 (19)0.0510.0650.0320.0410.2630.70.119 + j0.9620.065 + j0.2616277300360
    4/0 (19)0.0510.0650.0320.0420.2630.70.119 + j0.9590.065 + j0.2626094300360
    250 (37)0.0430.0560.0300.0410.2820.70.110 + j0.9320.056 + j0.2377203325
    350 (37)0.0310.0410.0260.0390.3200.80.095 + j0.8830.041 + j0.1939973390460
    350 (37)0.0310.0410.0260.0390.3200.80.095 + j0.8830.041 + j0.1939973390460
    500 (37)0.0220.0300.0230.0370.3681.00.084 + j0.8390.030 + j0.15514406455525
    500 (37)0.0220.0300.0230.0370.3681.00.084 + j0.8390.030 + j0.15514406455525
    500 (37)0.0220.0300.0230.0380.3681.00.084 + j0.8370.030 + j0.15614973455525
    750 (61)0.0140.0230.0190.0360.4391.10.077 + j0.7930.023 + j0.12122019545580
    1000 (61)0.0110.0190.0170.0350.4941.30.073 + j0.7660.019 + j0.10028878
    1000 (61)0.0110.0190.0170.0350.4941.30.073 + j0.7660.019 + j0.10028878
    1000 (61)0.0110.0190.0170.0360.4941.30.073 + j0.7660.019 + j0.10129419
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    TBA2 (Solid)6.5316.384.4418.676x141.441.2724.46845195.582359
    6281842 (7)7.1616.844.4419.136x141.441.2724.92850198.122359
    689828#!2 (7)7.1616.844.4419.136x141.441.2724.92847198.122359
    TBA1 (Solid)7.3417.204.4419.487x141.231.2725.27969203.202977
    TBA1 (19)8.1818.034.4420.327x141.231.2726.11994208.282977
    TBA1/0 (Solid)8.2318.084.4420.379x140.961.2726.161135208.283756
    6161541/0 (19)9.1718.854.4421.139x140.961.2726.921141215.903756
    6281872/0 (19)10.2919.964.4422.2511x140.781.2728.041336223.524735
    TBA3/0 (19)11.5821.444.4423.7214x140.611.2729.511618236.225972
    6281894/0 (19)13.0022.664.4424.9418x140.481.2730.731902246.387529
    614035#4/0 (19)13.0022.664.4424.9411x120.491.2731.571917251.467529
    600829§250 (37)14.1724.084.4426.3713x120.421.2732.992217264.168900
    628192350 (37)16.7926.704.4429.4918x120.301.2736.122935289.5612460
    614878#350 (37)16.7926.704.4429.4918x120.301.2736.122906289.5612460
    622071500 (37)20.0429.954.4432.7426x120.211.2739.373963314.9617800
    611445#500 (37)20.0429.954.4432.7426x120.211.2739.373963314.9617800
    628194500 (37)20.0429.954.4432.7417x100.201.2740.444054322.5817800
    628195750 (61)24.5934.754.4437.5425x100.131.9146.615846373.3826700
    6281971000 (61)28.3738.534.4441.3326x90.101.9151.037545408.9435600
    628576^1000 (61)28.3738.534.4441.3326x90.101.9151.037546408.9435600
    6281991000 (61)28.3738.534.4441.3321x80.101.9151.778026414.0235600
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ! No moisture block on conductor
    ^ HiDri Plus - Water Blocking Powder. Black Jacket
    # All black jacket
    § HiDri Plus - Water Blocking Powder. Black Jacket. CSA Listed
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (Solid)0.53150.670.01620.17060.5351.31230.257 + j1.2810.204 + j0.5712092160195
    2 (7)0.53150.670.01490.16400.5741.64040.257 + j1.2240.204 + j0.5142092160195
    2 (7)0.53150.670.01490.16400.5741.64040.257 + j1.2240.204 + j0.5142092160195
    1 (Solid)0.41990.530.01490.16400.5741.64040.216 + j1.2120.162 + j0.5022441180220
    1 (19)0.41990.530.01400.15750.6141.64040.216 + j1.1530.162 + j0.4452441180220
    1/0 (Solid)0.33460.420.01370.15750.6171.64040.182 + j1.1500.128 + j0.4413138200250
    1/0 (19)0.33460.420.01280.15090.6731.64040.182 + j1.0980.128 + j0.3903138200250
    2/0 (19)0.26570.330.01190.14760.7251.96850.156 + j1.0490.102 + j0.3433836230285
    3/0 (19)0.21000.270.01100.14110.7781.96850.135 + j1.0020.081 + j0.2994882260320
    4/0 (19)0.16730.210.00980.13450.8632.29660.119 + j0.9620.065 + j0.2616277300360
    4/0 (19)0.16730.210.00980.13780.8632.29660.119 + j0.9590.065 + j0.2626094300360
    250 (37)0.14110.180.00910.13450.9252.29660.110 + j0.9320.056 + j0.2377203325
    350 (37)0.10170.130.00790.12801.0502.62470.095 + j0.8830.041 + j0.1939973390460
    350 (37)0.10170.130.00790.12801.0502.62470.095 + j0.8830.041 + j0.1939973390460
    500 (37)0.07220.100.00700.12141.2073.28080.084 + j0.8390.030 + j0.15514406455525
    500 (37)0.07220.100.00700.12141.2073.28080.084 + j0.8390.030 + j0.15514406455525
    500 (37)0.07220.100.00700.12471.2073.28080.084 + j0.8370.030 + j0.15614973455525
    750 (61)0.04590.080.00580.11811.4403.60890.077 + j0.7930.023 + j0.12122019545580
    1000 (61)0.03610.060.00520.11481.6214.26510.073 + j0.7660.019 + j0.10028878
    1000 (61)0.03610.060.00520.11481.6214.26510.073 + j0.7660.019 + j0.10028878
    1000 (61)0.03610.060.00520.11811.6214.26510.073 + j0.7660.019 + j0.10129419
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.

    Revision: 1.000.001