SPEC 84021
3-Layer 25kV ACSR CAMV™ Covered Conductor (Tree Wire or Spacer Cable)
An Alternative and Robust Design to Bare ACSR Conductors to Harden the Electrical Grid.
3-Layer, 25kV, Covered Conductor, Concentrically Stranded ACSR, Track-Resistant Crosslinked Polyethylene.

Construction:
- Conductor:Concentrically stranded ACSR
- Strand Shield:Semi-conducting cross linked polymer
- Inner Layer:Low-Density Crosslinked Polyethylene (LDXLPE)
- Outer Layer:High-Density Track-Resistant Crosslinked Polyethylene (HDTRXLPE)
Applications and Features:
Specifications:
Table 1 – Weights and Measurements
| Cond. Size | Cond. Strands | Diameter Over Conductor | Conductor Shield Thickness | Inner Layer Thickness | Outer Layer Thickness | Approx. OD | Approx. Weight | Rated Strength |
|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | # | inch | mil | mil | mil | inch | lb/1000ft | lb |
| 1/0 | 6/1 | 0.398 | 15 | 125 | 125 | 0.928 | 385 | 4161 |
| 2/0 | 6/1 | 0.447 | 15 | 125 | 125 | 0.977 | 443 | 5045 |
| 3/0 | 6/1 | 0.502 | 15 | 125 | 125 | 1.032 | 513 | 6289 |
| 4/0 | 6/1 | 0.563 | 15 | 125 | 125 | 1.093 | 600 | 7933 |
All dimensions are nominal and subject to normal manufacturing tolerances
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Revision: 1.000.002
Updated On: Oct. 9, 2025, 1:58 p.m. UTC
