SPEC 84017
3-Layer 15kV AAC CAMV™ Covered Conductor (Tree Wire or Spacer Cable)
An Alternative and Robust Design to Bare AAC Conductors to Harden the Electrical Grid. 
 3-Layer, 15kV, Covered Conductor, Concentrically Stranded AAC, Track-Resistant Crosslinked Polyethylene.

Construction:
- Conductor:Concentrically stranded AAC
- Strand Shield:Semi-conducting cross linked polymer
- Inner Layer:Low-Density Crosslinked Polyethylene (LDXLPE)
- Outer Layer:High-Density Track-Resistant Crosslinked Polyethylene (HDTRXLPE)
Applications and Features:
Specifications:
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Strands | Diameter Over Conductor | Conductor Shield Thickness | Inner Layer Thickness | Outer Layer Thickness | Approx. OD | Approx. Weight | Rated Strength | 
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | # | inch | mil | mil | mil | inch | lb/1000ft | lb | |
| TBA | 1/0 | 7 | 0.336 | 15 | 75 | 75 | 0.666 | 210 | 1791 | 
| TBA | 2/0 | 7 | 0.376 | 15 | 75 | 75 | 0.706 | 246 | 2259 | 
| TBA | 3/0 | 7 | 0.423 | 15 | 75 | 75 | 0.753 | 289 | 2736 | 
| TBA | 4/0 | 7 | 0.475 | 15 | 75 | 75 | 0.805 | 343 | 3447 | 
| TBA | 266.8 | 19 | 0.537 | 15 | 75 | 75 | 0.867 | 407 | 4473 | 
| TBA | 336.4 | 19 | 0.603 | 15 | 75 | 75 | 0.933 | 487 | 5535 | 
| TBA | 397.5 | 19 | 0.659 | 15 | 75 | 75 | 0.989 | 558 | 6399 | 
| 662400 | 397.5 | 19 | 0.659 | 25 | 75 | 75 | 1.073 | 578 | 6399 | 
| TBA | 477 | 19 | 0.722 | 15 | 75 | 75 | 1.052 | 648 | 7524 | 
All dimensions are nominal and subject to normal manufacturing tolerances
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Revision: 1.000.005
Updated On: Oct. 9, 2025, 3:01 p.m. UTC

