SPEC 87035

Cable-in-Conduit (CIC) AL 15kV UD Primary EPEC-17

...

Construction:

• Conductors: 15kV AL 133% TRXLPE Full Neutral LLDPE JKT
• Conduit: High-Density Polyethylene (HDPE)

Applications and Features:

Southwire’s SIMpull® CIC has been utilized by end users in various applications, including the US Department of Transportation (DOT), the US Department of Energy (DOE), commercial constructions, EV infrastructure expansions, Utility grid-hardening efforts, airports, mass transit, renewables, petrochemical, agriculture, and data centers. Manufactured by continuously extruding HDPE loosely around the cable assembly with no adhesion between the conduit and the cable, thus leaving the cables free in the conduit. Lubrication is applied to the cable, allowing for cables to be pulled out and replaced if necessary. May be installed directly buried or encased in concrete as permitted by The National Electrical Code® Article 353. For above ground applications, HDPE conduit must be encased in a minimum of 2 inches of concrete.

Specifications:

  • ASTM D3350 Standard Specification for Polyethylene Plastics Pipe and Fittings Materials
  • ASTM D3485 Standard Specification for Coilable High Density Polyethylene (HDPE) Cable in Conduit (CIC)
  • CSA CSA marking is available upon request
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • NEMA TC-7 Smooth-Wall Coilable Electrical Polyethylene Conduit
  • Sample Print Legend:

    {SQFTG} FEET (LOGO) SOUTHWIRE CABLE IN CONDUIT HDPE X" EPEC-17 NEMA TC 7 (NESC) {MMM/DD/YYYY} {MACH/SHFT/OP}
    Table 1 – Physical and Electrical Data
    Stock NumberDescriptionDuct Nominal SizeDuct Nominal Outside Dia.Duct Min. Wall ThicknessDuct Nominal Inside Dia.Duct Min. Bending RadiusDuct Max. Pull TensionApprox. Cable and Duct Weight
    inchinchinchinchinchlblb/1000ft
    TBACable-in-Conduit (CIC) AL 15kV UD Primary EPEC-170.751.0500.0620.9061241092
    TBACable-in-Conduit (CIC) AL 15kV UD Primary EPEC-171.001.3150.0771.14114635140
    TBACable-in-Conduit (CIC) AL 15kV UD Primary EPEC-171.251.6600.0981.444181020219
    6301342CR MBAL 15KV220X 10x14 PES 1-1/2" EPEC-17 BLACK-RED STRIPES HDPE CIC1.501.9000.1121.656211335817
    630273CR AL 15KV175X 10X14 PES 1-1/2" EPEC-17 BLACK-RED STRIPES HDPE CIC1.501.9000.1121.656211335817
    6308944/0CR MBAL 15KV220E 11X14 PES 2" EPEC-17 BLACK-RED STRIPES HDPE CIC2.002.3750.1402.075262090437
    TBACable-in-Conduit (CIC) AL 15kV UD Primary EPEC-172.502.8750.1692.517323060632
    TBACable-in-Conduit (CIC) AL 15kV UD Primary EPEC-173.003.5000.2063.063394525939
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Cell Classification for HDPE Conduit

    PropertyTest MethodValue
    DensityD48830.953 g/cc
    Melt IndexD12380.25 g/10 min
    Flexural ModulusD790168,000 psi
    Tensile StrengthD6383900 yield @ 2 in/min
    SP-NCLS ESCRF2136>1000 hrs
    Hydrostatic Design BasisD2837N/A

  • (PE436580C-BK), (PE436580E-Colors)
  • Revision: 1.000.014

    Updated On: Oct. 1, 2026, 6:34 p.m. UTC

    CIC Labor Saving Calculator
    QR Code