SPEC 70043

600V AMERICAN MUSTANG SAFEGUARD® Type SOOW Cord with Yellow Jacket 105°C. MSHA Approved

600V, 105°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation and Heat, Moisture and Oil Resistant Flexible CPE Jacket, UL/CSA Listed.

...

Construction:

  1. Conductor: Class K stranded bare copper per ASTM B-174
  2. Insulation: Heat, moisture and oil resistant EPDM
  3. Filler: Waxed paper
  4. Separator: Paper separator wrapped around the assembly
  5. Jacket:Yellow CPE (Other colors available upon request)

Applications and Features:

Southwire AMERICAN MUSTANG SAFEGUARD® Type SOOW Flexible Cords are UL/ CSA listed and permitted for use as specified by Article 400 and related articles of the 2023 National Electrical Code®. The cable is rated -40°C to 105°C, water, oil, and weather resistant. SAFEGUARD® Type SOOW Flexible Cords are designed for extra hard usage on industrial equipment and heavy tools in the food and beverage industry in Zone 2 Splash zone. Microbial additive helps to resist 99.9% of bacteria specifically S. Aureus and E. Coli.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • Exceeds Ecolab PM-40-1 Material Resistance Test With 30-day Exposure, UL Verified V747862
  • MSHA Approved
  • RoHS-3 Complies with European Directive 2015/863
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® American Mustang SAFEGUARD® CORD X/C XX AWG (XX{mm2}) SOOW E46194 {UL} 600V -40°C TO 105°C -- {CSA} LL90458 SOOW 600V -40°C TO 105°C FT2 WATER RESISTANT --- P-07-KA190005-MSHA
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacityInsul. ColorJacket Color
    AWG/KcmilNo.No.milmilinchlb/1000ftAmp
    1386551831630700.370747BK,WE,GNYW
    1386561626530700.3707113BK,WEYW
    1386571636530650.3978610BK,WE,GNYW
    1386581646530750.4271068BK,WE,RD,GNYW
    1386591424145800.53413818BK,WEYW
    1386601434145800.53415615BK,WE,GNYW
    1386611444145900.56918712BK,WE,RD,GNYW
    13866212365451150.60620920BK,WE,GNYW
    1386631246545950.66026116BK,WE,RD,GNYW
    138664103104451050.66527825BK,WE,GNYW
    13866610410445950.72033420BK,WE,RD,GNYW
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)of the 2023 National Electrical Code and CEC Table 12.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *Insul. ColorJacket Color
    AWG/KcmilNo.No.mmmmmmkg/kmAmp
    138655183160.761.789.401107BK,WE,GNYW
    138656162650.761.789.4010613BK,WEYW
    138657163650.761.6510.0812810BK,WE,GNYW
    138658164650.761.9110.851588BK,WE,RD,GNYW
    138659142411.142.0313.5620518BK,WEYW
    138660143411.142.0313.5623215BK,WE,GNYW
    138661144411.142.2914.4527812BK,WE,RD,GNYW
    138662123651.142.9215.3931120BK,WE,GNYW
    138663124651.142.4116.7638816BK,WE,RD,GNYW
    1386641031041.142.6716.8941425BK,WE,GNYW
    1386661041041.142.4118.2949720BK,WE,RD,GNYW
    * Ampacities are based on TABLE 400.5(A)of the 2023 National Electrical Code and CEC Table 12.* Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.

    Color Code

    # of ConductorColor Sequence
    2Black, White
    3Black, White, Green
    4Black, White, Red, Green

    Revision: 1.000.011