SPEC 41014

TELCOFLEX® L3 Telecom Power Wire and Cable

Limited smoke, Non-halogenated Insulation, 105°C Dry, 60°C Wet

...

Construction:

  1. Conductor:Class B stranded, tin-coated copper conforming to ASTM B-33
  2. Separator Tape:Opaque Mylar tape
  3. Insulation:Limited smoke, non-halogenated, 105°C Dry, 60°C Wet TelcoHyde® 5221. Conforms to UL 44, UL 758, CSA C22.2 No. 210-11, and Telcordia Specification GR-347- CORE. Insulation has a Limiting Oxygen Index of 35%
  4. Separator Tape:1 mil Clear Mylar tape on 6 AWG and larger
  5. Cotton Braid:Overall natural cotton braid conforming to UL 44
  6. Saturant and Colored Finisher:Moisture resistant, fire retardant saturant and a colored finisher

Applications and Features:

This specification covers the construction requirements for a limited smoke, non-halogenated power cable insulated with TelcoHyde® 5221 with an overall flame retardant saturated braid. UL listed Type RHH, FT4-ST1 in accordance with the National Electrical Code. Product is for use in Central Office, CATV Head End, Data Center and Cell Tower applications. Cable is suitable for UL “CT USE” (Cable Tray rated) in sizes 1/0 AWG and larger.

Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Type RHH, FT4-ST1, VW-1, 600 Volts DC or AC
  • UL 2731 Telecommunications Central Office Power Cable
  • CSA AWM IB 105°C 600V. FT4-ST1
  • IEC including 60674 and 60332
  • RoHS Compliant Lead-Free, Silicone-Free, Halogen Free
  • ATIS 0600017.2020 List 3
  • Telcordia GR-347-CORE
  • Sample Print Legend:

    SIZES 14 AWG THROUGH 10 AWG:
    {SQFTG} SOUTHWIRE AIW{TM} CORD BRAND TELCOFLEX® III ATIS 0600017.2020 L3 NON-HAL (UL) E30117 XX AWG 600 VOLTS RHH VW-1 ST1 FT4 OR AWM 3578 60°C WET --- LL90458 (CSA) AWM I B 105°C 600 VOLTS FT4 {YYYY} {HH:MM} {JULIAN} --- MEETS IEC INCLUDING 60674 & 60332---MEETS GR-347

    SIZES 8 AWG THROUGH 2 AWG:
    {SQFTG} SOUTHWIRE AIW{TM} CORD BRAND TELCOFLEX® III ATIS 0600017.2020 L3 NON-HAL (UL) E30117 XXX AWG 600 VOLTS RHH VW-1 ST1 FT4 OR AWM 3578 60°C WET --- LL90458 (CSA) AWM I B 105°C 600 VOLTS FT4 {YYYY} {HH:MM} {JULIAN} --- MEETS IEC INCLUDING 60674 & 60332---MEETS GR-347

    SIZES 1/0 AWG THROUGH 750 KCMIL:
    {SQFTG} SOUTHWIRE AIW{TM} CORD BRAND TELCOFLEX® III ATIS 0600017.2020 L3 NON-HAL {UL} E30117 XXX AWG 600 VOLTS RHH VW-1 ST1 FT4 SR FOR CT USE OR AWM 3578 60°C WET --- LL90458 {CSA} AWM I B 105°C 600 VOLTS FT4 {YYYY} {HH:MM} {JULIAN} --- MEETS IEC INCLUDING 60674 & 60332---MEETS GR-347

    NOTE: CABLE SHALL BE PRINTED ON BOTH SIDES USING INK OF CONTRASTING COLOR; SEQUENTIAL FOOTAGE MARKS SHALL BE APPLIED 2 FOOT INTERNALS ON ONE SIDE OF THE CABLE.

    Packaging:

    All put-ups one length only unless agreed to otherwise. Maximum lengths per size will be advised. The ends of the cable shall be capped or taped to prevent the entrance of moisture during shipment or storage.
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. StrandsDiameter Over Cond.Insul. ThicknessDiameter Over InsulationApprox. ODApprox. WeightDC Resistance @ 25°CMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWG/Kcmilstrandsinchmilinchinchlb/1000ftΩ/1000ftinchAmpAmp
    5715561470.071450.1610.218322.6311.72025
    5713371470.071450.1610.218322.6311.72025
    5713361470.071450.1610.218322.6311.72025
    5714571470.071450.1610.218322.6311.72025
    5713351470.071450.1610.218322.6311.72025
    5696951270.089450.1790.236421.6621.92530
    5696941270.089450.1790.236421.6621.92530
    5696971270.089450.1790.236421.6621.92530
    5696961270.089450.1790.236421.6621.92530
    5696931270.089450.1790.236421.6621.92530
    5696791070.113450.2030.266641.042.13540
    5696821070.113450.2030.266641.042.13540
    5696831070.113450.2030.266641.042.13540
    5696801070.113450.2030.266641.042.13540
    5705111070.113450.2030.266641.042.13540
    569879870.142600.2620.332980.6532.75055
    569881870.142600.2620.332980.6532.75055
    569880870.142600.2620.332980.6532.75055
    571267870.142600.2620.332980.6532.75055
    571490870.142600.2620.332980.6532.75055
    571410670.178600.2980.3661340.4112.96575
    569861670.178600.2980.3661340.4112.96575
    569864670.178600.2980.3661340.4112.96575
    569862670.178600.2980.3661340.4112.96575
    569866670.178600.2980.3661340.4112.96575
    569865670.178600.2980.3661340.4112.96575
    569826470.225600.3450.4131910.2583.38595
    571287470.225600.3450.4131910.2583.38595
    569831470.225600.3450.4131910.2583.38595
    569825470.225600.3450.4131910.2583.38595
    569829470.225600.3450.4131910.2583.38595
    569828470.225600.3450.4131910.2583.38595
    569824470.225600.3450.4131910.2583.38595
    569759270.283600.4030.4792820.1623.8115130
    569757270.283600.4030.4792820.1623.8115130
    569762270.283600.4030.4792820.1623.8115130
    569761270.283600.4030.4792820.1623.8115130
    569763270.283600.4030.4792820.1623.8115130
    569760270.283600.4030.4792820.1623.8115130
    569758270.283600.4030.4792820.1623.8115130
    6795751190.322800.4820.5523630.1284.4130145
    5696701/0190.362800.5220.5924420.1024.7150170
    5713841/0190.362800.5220.5924420.1024.7150170
    5696691/0190.362800.5220.5924420.1024.7150170
    5696671/0190.362800.5220.5924420.1024.7150170
    5696641/0190.362800.5220.5924420.1024.7150170
    5697792/0190.405800.5650.6355380.0825.1175195
    5697772/0190.405800.5650.6355380.0825.1175195
    5697812/0190.405800.5650.6355380.0825.1175195
    5713832/0190.405800.5650.6355380.0825.1175195
    5697752/0190.405800.5650.6355380.0825.1175195
    5698494/0190.512800.6720.7428070.0515.9230260
    5698474/0190.512800.6720.7428070.0515.9230260
    5698434/0190.512800.6720.7428070.0515.9230260
    5698424/0190.512800.6720.7428070.0515.9230260
    5698454/0190.512800.6720.7428070.0515.9230260
    571382350370.661950.8510.92313050.0317.4310350
    569810350370.661950.8510.92313050.0317.4310350
    569808350370.661950.8510.92313050.0317.4310350
    571492350370.661950.8510.92313050.0317.4310350
    571569350370.661950.8510.92313050.0317.4310350
    569630500370.789950.9791.03717830.0218.3380430
    569633500370.789950.9791.05118020.0218.4380430
    571555500370.789950.9791.05118020.0218.4380430
    569635500370.789950.9791.05118020.0218.4380430
    569613750610.9681101.1881.26226650.01410.1475535
    582037750610.9681101.1881.26226650.01410.1475535
    569617750610.9681101.1881.26226650.01410.1475535
    571262750610.9681101.1881.26226650.01410.1475535
    569615750610.9681101.1881.26226650.01410.1475535
    569611750610.9681101.1881.26226650.01410.1475535
    569612750610.9681101.1881.26226650.01410.1475535
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Allowable Ampacity In Raceway per NEC Table 310.15(B)(16)
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    TESTING:

    Physical and electrical tests in accordance with the requirements of UL Standard 44, Standard 758, and CSA Standard C22.2 No. 210-11 as AWM.

    LABELS

    UL and CSA tags and labels shall be applied to all packages.

    Stock Numbers and Colors

    Size (All Items are Braided)GrayGreenBlueRed
    GrayGreenBlueRed
    1457133601571457015715560157133701
    1256969501569696015696940156969701
    1057051101569682015696800156968302
    857126701569880015714900156988101
    656986402569865015698620156986602
    456982601569828015698240156982901
    256975701569760015697610156975801
    167957501
    1/056966701569669015696640156967001
    2/056977701569779015697750156978101
    4/056984501569847015698430156984901
    35056980801571569015714920156981001
    50056963301569635015696300157155501
    75056961301569615015696110156961701

    Size (All Items are Braided)BlackRed - Black StripeBlue - Black StripeGray - Black Stripe
    BlackRed/BlackBlue/BlackGray/Black
    1457133501
    1256969301
    1056967901
    856987901
    65698610257141001
    4571287015698310156982501
    2569759015697620156976301
    1/057138401
    2/057138301
    4/056984201
    35057138201
    500
    750582037015712620156961201

    Revision: 1.000.006

    Updated On: July 8, 2026, 8:16 p.m. UTC