SPEC 10012

SIMpull® THHN/THWN-2 Aluminum with AlumaFlex® Brand Conductors

600 Volt Alumaflex® Brand Aluminum Alloy (AA-8176) Conductor. PVC Insulation/SIMpull® Nylon Sheath, Heat, Moisture, Gasoline and Oil Sunlight Resistant. Also Rated THWN-2. SIMpull® Technology for Easier Pulling

...

Construction:

  1. Conductor:Class B compact stranded bare aluminum per ASTM B800 and ASTM B801 or Single Input Wire (SIW) Compact AL per ASTM B836
  2. Insulation:Heat and moisture resistant PVC insulation in various colors
  3. Insulation:Nylon jacket utilizing SIMpull® Technology

Applications and Features:

APPLICATION
Southwire SIMpull® THHN Aluminum Wire & Cable with Alumaflex® Brand conductors are primarily used in conduit and cable trays for services, feeders, and branch circuits in commercial or industrial applications as specified in the National Electrical Code and other applicable codes and standards. Voltage for all applications is 600 volts. SIMpull® THHN/THWN-2 aluminum conductors are designed to be installed without the application of a pulling lubricant. These conductors have multiple ratings depending on the product application. Allowable temperatures are as follows:
- THHN or T90 Nylon- Dry locations not to exceed 90°C
- THWN-2 Wet or dry locations not to exceed 90°C or locations not to exceed 75°C when exposed to oil
- TWN75 Wet locations not to exceed 75°C

FEATURES - Sunlight Resistant- Sizes #2 and larger
- Oil and Gasoline Resistant II
- CT- Sizes 1/0 AWG and larger
- VW-1 All Sizes
- FT1 All Sizes
- T90 Nylon on all sizes
- TWN75 All sizes
- National Electrical Code, NFPA
- NEMA WC-70 Construction Requirements
- RoHS Compliant

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • CSA C22.2 No. 75 Thermoplastic Insulated Wires and Cables
  • Federal Specification A-A-59544
  • Sample Print Legend:

    SOUTHWIRE SIMpull{TM} E23919 {UL} 600 VOLTS (XXX KCMIL) XXX{mm2} COMPACT AL. --- {ALUMAFLEX}® AA8176 TYPE THWN-2 OR THHN OR GASOLINE AND OIL RESISTANT II FOR CT USE SUNLIGHT RESISTANT VW-1 --- {CUL} T90 NYLON OR TWN75 600 VOLTS FT1 90°C --- RoHS SOUTHWIRE® {NOLUBE}® {900} {SIMpull} {THHN}® {SIMpull} {T90}{TM} {listed THWN-2} PAT www.patentSW.com
    Table 1 – Weights and Measurements
    Cond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    6170.1693060.2432439
    4170.2124070.3093963
    2160.2684070.3646292
    1180.2985080.41778118
    1/01100.3365080.45699143
    2/01120.3765080.496125174
    3/01150.4225080.543158213
    4/01190.4745080.595199261
    2501220.5206090.662235314
    3001210.5696090.712282372
    3501350.6156090.758329424
    4001350.6596090.801376475
    5001350.7356090.878471581
    6001580.81270100.969565704
    7001580.87770101.041659811
    7501580.90870101.072706867
    9001580.99970101.1638471034
    10001581.06070101.2249411124
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    611.01570.6740.8120.0515055
    411.22500.4240.5100.0486575
    211.53980.2670.3210.04590100
    111.75020.2110.2540.046100115
    1/011.86330.1680.2010.044120135
    2/012.07980.1330.1600.043135150
    3/012.210060.1050.1260.042155175
    4/012.412690.0840.1000.041180205
    25012.615000.0710.0860.041205230
    30012.818000.0590.0710.041230260
    35013.021000.0500.0620.040250280
    40013.224000.0440.0540.040270305
    50013.530000.0350.0440.039310350
    60013.936000.0290.0370.039340385
    70015.242000.0250.0330.038375425
    75015.445000.0240.0310.038385435
    90015.854000.0200.0270.037425480
    100016.160000.0180.0250.037445500
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Table 3 - Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)

    Size (strand)BlackRedBlueWhiteBrownOrangeYellow
    6 (7)563768573834573835578332
    4 (7)563769573544573833577628
    2 (6)563770573541573542563493587026587027587028
    1 (8)563771583155583156578328587023587024587025
    1/0 (10)562747562748562749562750562753562754562752
    2/0 (12)562212562214562621562213562758562759562757
    3/0 (16)562663562665562666562664562763562764562762
    4/0 (19)562671562673562674562672561805561806561807
    250 (22)560444562626562627562625561863561864561865
    300 (21)562667562669562670562668562771562772562770
    350 (35)560443562623562624562622561858561859561861
    400 (35)562677562776562778562779562781562782562780
    500 (34)560442562696562697562698561853561854561855
    600 (58)560441562630562631562628561847561848561849
    700 (58)562689562690562691562692561843561844561846
    750 (58)562632562634562635562633561838561839561840
    900 (58)562679562681562682562683561782561783561785
    1000 (58)562680564280564282

    Table 3 - Cont. Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)

    Size (strand)GrayGreenPurplePinkTanGray/PurpleGray/Orange
    6 (7)566358
    4 (7)562211
    2 (6)578329562745
    1 (8)578327562746
    1/0 (10)562755562756573380
    2/0 (10)562760562761
    3/0 (10)562765562766573371671296671192671310
    4/0 (19)562767562768
    250 (22)561866561867573373581834581833
    300 (21)562773562774573374
    350 (35)561862562775573375641125641127669737
    400 (35)562783562699573376678467674297
    500 (34)561856561857573377584173584172675375
    600 (58)561850561851573379589106
    700 (58)562693671948671945671674
    750 (58)561841561842573481590187
    900 (58)561786562684
    1000 (58)564281

    Revision: 1.000.024