SPEC 45043

Southwire® Machine Flex® CU 600/1000V PVC-Nylon Insulation THHN TPE Black Jacket. Silicone-Free

Type TC-ER Machine Tray Power Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4. Silicone-Free

...

Construction:

  1. Conductor:Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer THHN
  3. Ground:One Green Ground with Yellow Stripe THHN
  4. Jacket:Black Thermoplastic Elastomer TPE: Other jacket colors available upon request

Applications and Features:

Southwire’s Machine Flex® tray power cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Southwire’s machine tray cable is ideal to power CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and beverage, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Specifications:

  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 13 Power-Limited Circuit Cables
  • UL 66 Fixture Wire
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 AWM Style 2587
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2250 Instrumentation Tray Cable
  • UL 2277 Type WTTC
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Exceeds Ecolab PM-40-1 Material Resistance Test With 30-day Exposure, UL Verified V747862
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79 Electrical Standard for Industrial Machinery
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    18 - 12 AWG:
    SOUTHWIRE® XX AWG (X.XXmm2) X/C PVC/NYLON TYPE TC-ER E75755 (UL) 600V 90°C DRY 75°C WET SUN RES OIL RES I/II DIR BUR -40°C OR MTW FLEXING OR DP-1 OR WTTC 1000V OR PLTC OR ITC OR AWM 2587 -- LL90458 CSA CIC/TC FT4 OR AWM I/II A/B 105°C 1000V -40°C FT4 -- {NOM}-ANCE PLTC -- {CE} RoHS-2 MADE IN USA

    10 AWG and Larger:
    {SQFTG} SOUTHWIRE® XX AWG (XX{mm2}) X/C PVC/NYLON TYPE TC-ER E75755 {UL} 600V 90{D}C DRY 75{D}C WET SUN RES OIL RES I/II DIR BUR -40{D}C OR MTW FLEXING OR DP-1 OR WTTC 1000V OR AWM 2587 -- LL90458 {CSA} CIC/TC FT4 OR AWM I/II A/B 105{D}C 1000V -40{D}C FT4 -- {NOM}-ANCE 90{D}C PVC/NYLON PVC-TPE THHN/THWN FT4 600V -- {CE} RoHS-2 -- MADE IN USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    677315◊18370.04415500.28815526.6598.2650.0361.2-14BK
    677530◊184160.04415500.30620556.6598.2650.0361.2-11BK
    677316◊185160.04415500.33225756.6598.2650.0361.3-11BK
    665090186160.04415450.34830856.6598.2650.0361.4-11BK
    677531◊187160.04415500.35835926.6598.2650.0361.4-10BK
    665089188160.04415450.401401116.6598.2650.0361.6-10BK
    677532◊189160.04415500.411451226.6598.2650.0361.6-10BK
    6650911810160.04415450.438501376.6598.2650.0361.8-7BK
    677533◊1812160.04415500.456601296.6598.2650.0361.8-7BK
    6650921814160.04415450.469711406.6598.2650.0361.9-7BK
    6650931816160.04415450.495811656.6598.2650.0362-7BK
    665094◊1819160.04415650.56962376.6598.2650.0362.27BK
    677317◊1825160.04415650.6351262556.6598.2650.0362.56BK
    6650951837160.04415650.7321864236.6598.2650.0362.9-6BK
    16 AWG
    665096162260.05915500.30216484.1815.1890.0331.2-18BK
    677535◊163260.05915500.31824604.1815.1890.0331.3-18BK
    677536◊164260.05915500.33932724.1815.1890.0331.4-14BK
    677318◊165260.05915500.3741874.1815.1890.0331.5-14BK
    665098◊167260.05915500.4571234.1815.1890.0331.6-13BK
    665099168260.05915500.431651434.1815.1890.0331.7-13BK
    665097166260.05915500.462491404.1815.1890.0331.8-14BK
    677320◊169260.05915500.462731644.1815.1890.0331.8-13BK
    6651001610260.05915500.509811544.1815.1890.0332-9BK
    677321◊1612260.05915500.509971754.1815.1890.0332-9BK
    6651011616260.05915650.6011302424.1815.1890.0332.4-9BK
    665102◊1619260.05915650.631543164.1815.1890.0332.5-9BK
    6651031624260.05915650.7171953404.1815.1890.0332.9-8BK
    6651041630260.05915850.8112434394.1815.1890.0333.2-8BK
    6651051637260.05915850.873005284.1815.1890.0333.5-7BK
    14 AWG
    677258◊143410.07315500.34238782.6213.2530.0581.42025BK
    677259◊144410.07315500.37551972.6213.2530.0581.51620BK
    665106146410.07315500.445771372.6213.2530.0581.81620BK
    653005148410.07315500.4951021762.6213.2530.05821418BK
    677261◊149410.07315500.5161151902.6213.2530.0582.11418BK
    6651071410410.07315650.6021282272.6213.2530.0582.41012BK
    677322◊1412410.07315650.6081532592.6213.2530.0582.41012BK
    6651081416410.07315650.6662053322.6213.2530.0582.71012BK
    677262◊1418410.07315600.692304152.6213.2530.0582.81012BK
    677263◊1425410.07315650.8063184892.6213.2530.0583.2911BK
    12 AWG
    677256◊123650.09415500.389611091.6522.050.0541.62530BK
    677537◊124650.09415500.42811371.6522.050.0541.72024BK
    677538◊125650.09415500.4621011661.6522.050.0541.82024BK
    665109126650.09415500.5021221951.6522.050.05422024BK
    677257◊127650.09415550.5541422281.6522.050.0542.21821BK
    665111◊1212650.09415650.6872434261.6522.050.0542.71215BK
    10 AWG
    653009◊1031050.11720500.463971611.041.2910.051.93540BK
    677539◊1041050.11720500.5051292041.041.2910.0522832BK
    6772541051050.11720600.581622931.041.2910.052.32832BK
    6772551071050.11720600.6282273721.041.2910.052.52428BK
    45593210121050.11720850.8743886761.041.2910.053.51820BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Cond. Number includes green/yellow ground conductor. Constructions with only 2/C do not have a green/yellow ground conductor.
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.019

    Updated On: Aug. 17, 2026, 1:57 p.m. UTC