SPEC 45303
CU 600/1000V XLPE Insulation 50% Ground AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
Type MC Power Cable 600Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Three Bare CU 50% Ground Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with. Silicone Free.

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Three separate Ground Wires with a combined circular mil of 50% of the phase conductor. Stranded class B compressed per ASTM B3 and ASTM B8
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polypropylene tape
- Armor:Aluminum Interlocked Armor (AIA)
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of op- erating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. The ground is sized to 50% of the phase conductor with three separate bare grounds one in each interstecie between condutors. Silicone Free.
Specifications:
Sample Print Legend:
SQFTG_DUAL} SOUTHWIRE {UL} 3/C (XXX KCMIL) XXXmm2 CU XX MILS XLP 600 VOLTS GW 3 X 1 AWG CU TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA -- {NOM}-ANCE Tipo MC XHHW-2 CT FT4
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | |||
| 655383 | 1/0 | 3 | 19 | 0.362 | 55 | 3 x 6 | 1.259 | 50 | 1.364 | 1233 | 1663 | BK |
| 665396 | 2/0 | 3 | 19 | 0.405 | 55 | 3 x 6 | 1.354 | 50 | 1.459 | 1491 | 1955 | BK |
| 655386 | 3/0 | 3 | 19 | 0.456 | 55 | 3 x 4 | 1.462 | 50 | 1.567 | 1960 | 2485 | BK |
| TBA | 4/0 | 3 | 19 | 0.512 | 55 | 3 x 4 | 1.657 | 50 | 1.757 | BK | ||
| TBA | 250 | 3 | 37 | 0.558 | 65 | 3 x 4 | 1.799 | 50 | 1.899 | BK | ||
| TBA | 300 | 3 | 37 | 0.611 | 65 | 3 x 3 | 1.914 | 60 | 2.034 | BK | ||
| 576888 | 350 | 3 | 37 | 0.661 | 65 | 3 x 2 | 2.005 | 60 | 2.131 | 3895 | 4752 | BK |
| 552598 | 500 | 3 | 37 | 0.789 | 65 | 3 x 1 | 2.275 | 75 | 2.432 | 5461 | 6558 | BK |
| TBA | 600 | 3 | 61 | 0.866 | 80 | 3 x 1/0 | 2.529 | 60 | 2.649 | BK | ||
| 588666 | 750 | 3 | 61 | 0.968 | 80 | 3 x 2/0 | 2.784 | 75 | 2.942 | 8262 | 9662 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| 655383 | 1/0 | 3 | 9.5 | 2534 | 0.102 | 0.127 | 0.044 | 150 | 170 |
| 665396 | 2/0 | 3 | 10.2 | 3194 | 0.082 | 0.102 | 0.043 | 175 | 195 |
| 655386 | 3/0 | 3 | 11 | 4027 | 0.064 | 0.079 | 0.042 | 200 | 225 |
| TBA | 4/0 | 3 | 12.3 | 5078 | 0.051 | 0.063 | 0.041 | 230 | 260 |
| TBA | 250 | 3 | 13.3 | 6000 | 0.043 | 0.053 | 0.041 | 255 | 290 |
| TBA | 300 | 3 | 14.2 | 7200 | 0.036 | 0.045 | 0.041 | 285 | 320 |
| 576888 | 350 | 3 | 14.9 | 8400 | 0.031 | 0.039 | 0.04 | 310 | 350 |
| 552598 | 500 | 3 | 17 | 12000 | 0.021 | 0.027 | 0.039 | 380 | 430 |
| TBA | 600 | 3 | 18.5 | 14400 | 0.018 | 0.024 | 0.039 | 420 | 475 |
| 588666 | 750 | 3 | 20.6 | 18000 | 0.014 | 0.019 | 0.038 | 475 | 535 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.006
Updated On: Dec. 31, 2024, 11:07 p.m. UTC

