SPEC 45051

CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable 600 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Type THHN/THWN or TFFN/TFN, Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free - VW-1 Rated.

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and B8 for 14, 12, and 10 AWG cables. Class K bare copper per ASTM B3 and B174 for 16 AWG (26 strands) and 18 AWG (16 strands) cables.
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer. Type TFFN/TFN for 18 and 16 AWG cables. Type THHN or THWN for 14, 12, and 10 AWG cables. Types THHN or THWN are VW-1 rated.
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Polyvinyl Chloride (PVC)

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 66 Fixture Wire
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{mm2}) CU XX CDRS TYPE TC-ER THHN OR THWN CDRS 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    577879182720450.26811366.6698.0350.0361.1-14Black
    652188183720450.28015456.6698.0350.0361.1-14Black
    577878184720450.30420546.6698.0350.0361.2-11Black
    652191185720450.33625666.6698.0350.0361.3-11Black
    652194186720450.35830746.6698.0350.0361.4-11Black
    652197188720450.38540936.6698.0350.0361.5-9Black
    6522001810720450.438501406.6698.0350.0361.8-7Black
    6522031812720450.454601556.6698.0350.0361.8-7Black
    6522151816720450.508801656.6698.0350.0362.0-7Black
    6522091819720450.560952396.6698.0350.0362.2-7Black
    6522121824720600.6541213196.6698.0350.0362.6-6Black
    16 AWG
    604843◊1622620450.29216444.1815.0370.0331.2-18Black
    604850◊1632620450.30824584.1815.0370.0331.2-18Black
    604868◊1642620450.33332704.1815.0370.0331.3-14Black
    604876◊1652620450.36240814.1815.0370.0331.4-14Black
    TBA166720450.380561014.1815.0370.0331.5-14Black
    6792571662620450.39347974.1815.0370.0331.6-14Black
    604892◊1672620450.393551074.1815.0370.0331.6-12Black
    TBA168720450.410721244.1815.0370.0331.6-12Black
    604918◊1692620450.454721354.1815.0370.0331.8-12Black
    TBA1610720450.476881514.1815.0370.0331.9-9Black
    604942◊16122620450.510951744.1815.0370.0332.0-9Black
    60497516152620450.5951202264.1815.0370.0332.4-9Black
    605014◊16192620600.6251522744.1815.0370.0332.5-9Black
    TBA1620720600.6321682864.1815.0370.0332.5-9Black
    60507116252620600.7002013504.1815.0370.0332.8-8Black
    60512116302620600.7672424124.1815.0370.0333.1-8Black
    605196◊16372620600.8672975294.1815.0370.0333.5-7Black
    14 AWG
    408484◊142720450.30525562.6313.1700.0581.22025Black
    408518◊143720450.32238742.6313.1700.0581.32025Black
    408542◊144720450.35151942.6313.1700.0581.41620Black
    408575◊145720450.380641092.6313.1700.0581.51620Black
    608836146720450.416761302.6313.1700.0581.71620Black
    TBA148720450.4561151762.6313.1700.0581.81417Black
    408740◊149720450.4901151892.6313.1700.0582.01417Black
    6054771410720450.5561282222.6313.1700.0582.21012Black
    408807◊1412720450.5731532562.6313.1700.0582.31012Black
    4128741415720600.6321923122.6313.1700.0582.51012Black
    412908◊1419720600.6642433812.6313.1700.0582.71012Black
    6087291420720600.6972564012.6313.1700.0582.81012Black
    552133◊1425720600.8023205072.6313.1700.0583.2911Black
    5575531430720600.8753846202.6313.1700.0583.5911Black
    552190◊1437720800.9494757592.6313.1700.0583.8810Black
    12 AWG
    408468◊122720450.34840771.6622.0020.0541.42530Black
    408526◊123720450.369611081.6622.0020.0541.52530Black
    408559◊124720450.401811491.6622.0020.0541.62024Black
    408583◊125720450.4381011831.6622.0020.0541.82024Black
    408641◊127720450.4771422371.6622.0020.0541.91721Black
    608737126720450.4811221891.6622.0020.0541.92024Black
    TBA128720600.5461822681.6622.0020.0542.21721Black
    408757◊129720600.5801833321.6622.0020.0542.31721Black
    TBA1210720600.6342233261.6622.0020.0542.51215Black
    408815◊1212720600.6572444251.6622.0020.0542.61215Black
    4128821215720600.7343054541.6622.0020.0542.91215Black
    6224201216720600.7383254781.6622.0020.0543.01215Black
    4129161219720600.7723885621.6622.0020.0543.11215Black
    TBA1220720600.8024265851.6622.0020.0543.21215Black
    5521661225720800.9435097611.6622.0020.0543.81113Black
    TBA1230720800.9826308791.6622.0020.0543.91113Black
    5522241237720801.06475510841.6622.0020.0545.31012Black
    10 AWG
    408492◊102725450.420641151.0401.2530.0501.73540Black
    408534◊103725450.446971591.0401.2530.0501.83540Black
    408567◊104725450.5051292071.0401.2530.0502.02832Black
    408591◊105725450.5651612581.0401.2530.0502.32832Black
    TBA106725600.6112263251.0401.2530.0502.42832Black
    408658◊107725600.6152263811.0401.2530.0502.52428Black
    TBA108725600.6622904061.0401.2530.0502.62428Black
    408765◊109725600.7152915011.0401.2530.0502.92428Black
    TBA1010725600.7743554961.0401.2530.0503.11720Black
    408823◊1012725600.8063886521.0401.2530.0503.21720Black
    6016661019725800.9936139031.0401.2530.0504.01720Black
    TBA1020725801.0286789411.0401.2530.0505.11720Black
    TBA1025725801.14084011491.0401.2530.0505.71518Black
    TBA1030725801.207100213491.0401.2530.0506.01518Black
    TBA1037725801.303122816311.0401.2530.0506.51416Black
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.