SPEC 25085

CU 1000V SOLONONplus™ RWU90

Single Copper Conductors, LSZH Insulation, Sunlight Resistant, 1000V, 90ºC MAX, -40°C MIN, Gasoline & Oil Resistant

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Low Smoke Zero Halogen (LSZH), SOLONONplus™

Applications and Features:

Southwire’s RWU90 is designed for direct earth burial (with protection as required by the inspecting authority). For service entrance above or below ground. The minimum recommended installation temperature is minus 40°C (with suitable handling procedures). Maximum conductor temperature is 90°C.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA ST1 Smoke Test - Marked FT4-ST1 (2 AWG and Larger)
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger)
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways (non-emergency circuits only)
  • Sample Print Legend:

    SOUTHWIRE SOLONONplus{TM} LSZH 156205 {CSA} XXX KCMIL (XXX{mm2}) CU RWU90 1000V VW-1 HAL-FREE TC PRI PRII GRI GRII -40°C SR FT4 ST-1
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    TBA147600.190250.7332.6313.1700.05825
    TBA127600.217340.8521.6622.0020.05430
    TBA107600.239480.9831.0401.2530.05040
    TBA67800.3461101.32100.4111.2530.05175
    TBA27800.4512471.85310.1620.1950.045130
    TBA119950.5223132.06700.1280.1540.046145
    TBA1/019950.5523832.28450.1020.1220.044170
    TBA2/019950.5964802.310650.0810.0970.043195
    TBA3/019950.6545912.613420.0640.0780.042225
    TBA4/019950.7107442.816930.0510.0620.041260
    TBA250371100.7788673.120000.0430.0530.041290
    TBA350371100.88111913.528000.0310.0390.040350
    TBA500371101.00916735.040000.0220.0290.039430
    TBA600621251.13020195.648000.0180.0250.039475
    TBA750611251.21824896.060000.0140.0220.038535
    TBA1000621251.36732856.880000.0110.0190.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2021 Canadian Electrical Code Table 1 for not more than three insulated copper conductors, rated not more than 5000 V and unshielded, in raceway or cable (based on an ambient temperature of 30 °C)
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    TBA1471.524.833717.781478.6310.400.190325
    TBA1271.525.515120.322315.456.570.177230
    TBA1071.526.077122.863693.414.110.164040
    TBA672.038.7916433.029351.354.110.167375
    TBA272.0311.4636845.7223630.530.640.1476130
    TBA1192.4113.2646650.8029820.420.510.1509145
    TBA1/0192.4114.0257055.8837600.330.400.1444170
    TBA2/0192.4115.1471458.4247390.270.320.1411195
    TBA3/0192.4116.6188066.0459720.210.260.1378225
    TBA4/0192.4118.03110771.1275340.170.200.1345260
    TBA250372.7919.76129078.7489000.140.170.1345290
    TBA350372.7922.38177288.90124600.100.130.1312350
    TBA500372.7925.632490127.00178000.070.100.1280430
    TBA600623.1828.703005142.24213600.060.080.1280475
    TBA750613.1830.943704152.40267000.050.070.1247535
    TBA1000623.1834.724889172.72356000.040.060.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2021 Canadian Electrical Code Table 1 for not more than three insulated copper conductors, rated not more than 5000 V and unshielded, in raceway or cable (based on an ambient temperature of 30 °C)
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.012

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC