SPEC 25077

CU 1000V LSZH Solononplus™ Insulation. RW90

Single Copper Conductors, LSZH Insulation Solononplus™, Sunlight Resistant, 1000V, 90ºC MAX, -40ºC MIN, Gasoline & Oil Resistant

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Low Smoke Zero Halogen Solononplus™ (XLPO)

Applications and Features:

Suitable for installation in Cable Trays, Underground Duct Banks - As per CE Code limitations (see Rule 12-2202) for grounding and bonding applications. Standard colour is black. Some sizes may be availabe in white, red, blue, yellow, brown, orange or grey. Green Duraground™ also available.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA ST1 Smoke Test - Marked FT4-ST1 (2 AWG and Larger)
  • Oil Res I & Sun Res
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (2 AWG and larger)
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways (non-emergency circuits only)
  • Sample Print Legend:

    SOUTHWIRE SOLONONplus{TM} LSZH XLPO 156205 {CSA} XXX KCMIL (XXX{mm2}) CU RW90 1000V VW-1 HAL-FREE TC PRI PRII GRI GRII -40°C SR FT4 ST-1
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    TBA14745Black0.160200.6322.6313.1700.05825
    45627712745BK0.185360.7521.6622.0020.05430
    45628210745BK0.209500.8831.041.2530.05040
    TBA8745Black0.231630.91320.6530.7860.05255
    TBA6760Black0.2971041.12090.4110.4950.05175
    TBA4760Black0.3451551.33330.2580.3100.04895
    TBA2760Black0.4022371.65300.1620.1950.045130
    TBA1/01980Black0.5213822.08440.1020.1220.044170
    TBA2/01980Black0.5654732.210640.0810.0970.043195
    TBA3/01980Black0.6165882.413420.0640.0780.042225
    TBA4/01980Black0.6727302.616920.0510.0620.041260
    TBA2503790Black0.7388662.920000.0430.0530.041290
    TBA3503790Black0.84111913.328000.0310.0390.040350
    6644755003790Black0.95617163.840000.0220.0290.039430
    TBA7506190Black1.14824715.760000.0140.0220.038535
    66447810006190Black1.30733476.580000.0110.0180.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    TBA1471.14Black4.063015.241428.6310.400.190325
    4562771271.14BK4.705417.782315.456.570.177230
    4562821071.14BK5.317420.323693.414.110.164040
    TBA871.14Black5.879422.865872.142.580.170655
    TBA671.52Black7.5415527.949301.351.620.167375
    TBA471.52Black8.7623133.0214820.851.020.157595
    TBA271.52Black10.2135340.6423590.530.640.1476130
    TBA1/0192.03Black13.2356850.8037560.330.400.1444170
    TBA2/0192.03Black14.3570455.8847350.270.320.1411195
    TBA3/0192.03Black15.6587560.9659720.210.260.1378225
    TBA4/0192.03Black17.07108666.0475290.170.200.1345260
    TBA250372.29Black18.75128973.6689000.140.170.1345290
    TBA350372.29Black21.36177283.82124600.100.130.1312350
    664475500372.29Black24.28255496.52178000.070.100.1280430
    TBA750612.29Black29.163677144.78267000.050.070.1247535
    6644781000612.29Black33.204981165.10356000.040.060.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.