SPEC 60360

Armorlite® Type MC THHN/THWN PVC Jacketed Aluminum Conductor Feeder Cable 120/208V Colors. Silicone Free

Aluminum THHN/THWN Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor. Overall PVC Jacket. Sunlight Resistant.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B801
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Bare aluminum ground
  4. Filler:Fillers as needed
  5. Binder:Mylar tape
  6. Armor:Aluminum Interlocked Armor
  7. Jacket:Polyvinyl Chloride (PVC) sunlight resistant, and corrosion resistant

Applications and Features:

Southwire Armorlite® Type MC Feeder cable is suitable for use as follows:
- Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Suitable for Wet Location per NEC 330.10(A)(11)
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Type THHN/THWN rated 90ºC Dry/ 75ºC Wet

Southwire Armorlite® Type MC Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Color Code - 3/C: Black, Red, White
- 4/C: Black, Red, Blue, White

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    SOUTHWIRE {UL} E96627 X/C XXX KCMIL COMPACT 8000 AL. --- TRIPLE E ALLOY AA8176 THHN OR THWN CDRS 600 VOLTS GW 1 X X AWG TYPE MC EZ-JKT FOR CT USE SUN. RES. 90 DEGREES C
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorJacket ThicknessApprox. ODOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchmilinchlbs/1000ft
    6782821/02BK,RD0.33610501x21.118501.224595
    6792783/02BK,RD0.42316501x1/01.358501.464847
    5930864/02BK,WE0.47519501x1/01.396501.502929
    6756743002BK,RD0.5721601x4/01.716601.8421448
    6792813502BK,RD0.61635601x2501.808601.9341618
    5525871/03BK,RD,WE0.33610501x41.257501.363768
    5524652/03BK,RD,WE0.37612501x41.343501.449882
    5524643/03BK,RD,WE0.42316501x41.465501.5711079
    5524844/03BK,RD,WE0.47519501x21.577601.7031311
    5556672503BK,RD,WE0.5222601x21.735601.8611481
    5638042503BK,RD,WE0.5222601x11.735601.8611501
    5993772503BK,RD,WE,GN0.5222601x1/01.789601.9151620
    5612483503BK,RD,WE0.61635601x11.926602.0521901
    5558095003BK,RD,WE0.73634601x12.184602.312469
    5635895003BK,RD,WE0.73634601x3/02.189602.3152563
    5558127503BK,RD,WE0.90853701x1/02.608752.7663568
    5542821/04BK,RD,BE,WE0.33610501x41.384501.49957
    5558072/04BK,RD,BE,WE0.37612501x41.472501.5781109
    5542834/04BK,RD,BE,WE0.47519501x21.738601.8641657
    6797302504BK,RD,BE,WE0.5222601x21.89602.0161932
    5542842504BK,RD,BE,WE0.5222601x11.901602.0271939
    5549353004BK,RD,BE,WE0.5721601x12.022602.1482186
    5558083504BK,RD,BE,WE0.61635601x1/02.131602.2572472
    5549325004BK,RD,BE,WE0.73634601x3/02.435752.5933330
    5558116004BK,RD,BE,WE0.81358701x3/02.64752.7983895
    5607826004BK,RD,BE,WE0.81358701x4002.756752.9144174
    5549337504BK,RD,BE,WE0.90853701x3/02.88753.0384664
    5636037504BK,RD,BE,WE0.90853701x7503.106853.2845330
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusMax Pull TensionDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesLbsΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    1/028.612670.1670.2080.044120135
    3/0210.220130.1050.1310.042155175
    4/0210.525390.0840.1050.041180205
    300212.936000.0590.0740.041230260
    350213.542000.0510.0640.04250280
    1/039.519000.1670.2080.044120135
    2/0310.123950.1330.1660.043135150
    3/031130200.1050.1310.042155175
    4/0311.938080.0840.1050.041180205
    25031345000.070.0870.041205230
    25031345000.070.0870.041205230
    250313.445000.070.0870.041205230
    350314.463000.0510.0640.04250280
    500316.290000.0360.0450.039310350
    500316.290000.0360.0450.039310350
    750319.4135000.0230.030.038385435
    1/0410.425340.1670.2080.04496108
    2/041131940.1330.1660.043108120
    4/041350780.0840.1050.041144164
    250414.160000.070.0870.041164184
    250414.260000.070.0870.041164184
    30041572000.0590.0740.041184208
    350415.884000.0510.0640.04200224
    500418.2120000.0360.0450.039248280
    600419.6144000.030.0380.039272308
    600420.4144000.030.0380.039272308
    750421.3180000.0230.030.038308348
    750423180000.0230.030.038308348
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.