SPEC 60360
Armorlite® Type MC THHN/THWN PVC Jacketed Aluminum Conductor Feeder Cable 120/208V Colors. Silicone Free
Aluminum THHN/THWN Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor. Overall PVC Jacket. Sunlight Resistant.
Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B801
- Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
- Ground:Bare aluminum ground
- Filler:Fillers as needed
- Binder:Mylar tape
- Armor:Aluminum Interlocked Armor
- Jacket:Polyvinyl Chloride (PVC) sunlight resistant, and corrosion resistant
Applications and Features:
Southwire Armorlite® Type MC Feeder cable is suitable for use as follows:
- Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Suitable for Wet Location per NEC 330.10(A)(11)
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Type THHN/THWN rated 90ºC Dry/ 75ºC Wet
Southwire Armorlite® Type MC Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
Color Code - 3/C: Black, Red, White
- 4/C: Black, Red, Blue, White
- Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Suitable for Wet Location per NEC 330.10(A)(11)
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Type THHN/THWN rated 90ºC Dry/ 75ºC Wet
Southwire Armorlite® Type MC Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
Color Code - 3/C: Black, Red, White
- 4/C: Black, Red, Blue, White
Specifications:
Sample Print Legend:
SOUTHWIRE {UL} E96627 X/C XXX KCMIL COMPACT 8000 AL. --- TRIPLE E ALLOY AA8176 THHN OR THWN CDRS 600 VOLTS GW 1 X X AWG TYPE MC EZ-JKT FOR CT USE SUN. RES. 90 DEGREES C
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Conductor Number | Color | Diameter Over Conductor | Conductor Stranding | Insulation Thickness | Ground Size | Diameter Over Armor | Jacket Thickness | Approx. OD | Overall Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | mils | No. x AWG | inch | mil | inch | lbs/1000ft | ||||
678282 | 1/0 | 2 | BK,RD | 0.336 | 10 | 60 | 1x2 | 1.118 | 50 | 1.218 | 587 |
679278 | 3/0 | 2 | BK,RD | 0.422 | 16 | 60 | 1x1/0 | 1.292 | 55 | 1.402 | 811 |
593086 | 4/0 | 2 | BK,WE | 0.474 | 19 | 60 | 1x1/0 | 1.396 | 55 | 1.506 | 934 |
675674 | 300 | 2 | BK,RD | 0.569 | 21 | 70 | 1x4/0 | 1.843 | 65 | 1.975 | 1468 |
679281 | 350 | 2 | BK,RD | 0.615 | 35 | 70 | 1x250 | 1.942 | 65 | 2.074 | 1639 |
552587 | 1/0 | 3 | BK,RD,WE | 0.336 | 10 | 60 | 1x4 | 1.190 | 50 | 1.290 | 723 |
552465 | 2/0 | 3 | BK,RD,WE | 0.376 | 12 | 60 | 1x4 | 1.276 | 55 | 1.386 | 846 |
552464 | 3/0 | 3 | BK,RD,WE | 0.422 | 16 | 60 | 1x4 | 1.377 | 50 | 1.477 | 968 |
552484 | 4/0 | 3 | BK,RD,WE | 0.474 | 19 | 60 | 1x2 | 1.590 | 65 | 1.722 | 1297 |
555667 | 250 | 3 | BK,RD,WE | 0.520 | 22 | 70 | 1x2 | 1.735 | 65 | 1.867 | 1492 |
563804 | 250 | 3 | BK,RD,WE | 0.520 | 22 | 70 | 1x1 | 1.735 | 65 | 1.867 | 1512 |
599377 | 250 | 3 | BK,RD,WE,GN | 0.520 | 22 | 70 | 1x1/0 GG | 1.813 | 65 | 1.945 | 1608 |
561248 | 350 | 3 | BK,RD,WE | 0.615 | 35 | 70 | 1x1 | 1.942 | 65 | 2.074 | 1905 |
555809 | 500 | 3 | BK,RD,WE | 0.735 | 35 | 70 | 1x1 | 2.201 | 65 | 2.333 | 2466 |
563589 | 500 | 3 | BK,RD,WE | 0.735 | 35 | 70 | 1x3/0 | 2.201 | 65 | 2.333 | 2547 |
555812 | 750 | 3 | BK,RD,WE | 0.908 | 58 | 80 | 1x1/0 | 2.620 | 80 | 2.786 | 3553 |
554282 | 1/0 | 4 | BK,RD,BE,WE | 0.336 | 10 | 60 | 1x4 | 1.304 | 55 | 1.414 | 925 |
555807 | 2/0 | 4 | BK,RD,BE,WE | 0.376 | 12 | 60 | 1x4 | 1.400 | 55 | 1.510 | 1072 |
554283 | 4/0 | 4 | BK,RD,BE,WE | 0.474 | 19 | 60 | 1x2 | 1.749 | 65 | 1.881 | 1648 |
679730 | 250 | 4 | BK,RD,BE,WE | 0.520 | 22 | 70 | 1x2 | 1.901 | 65 | 2.033 | 1864 |
554284 | 250 | 4 | BK,RD,BE,WE | 0.520 | 22 | 70 | 1x1 | 1.901 | 65 | 2.033 | 1928 |
554935 | 300 | 4 | BK,RD,BE,WE | 0.569 | 21 | 70 | 1x1 | 2.022 | 65 | 2.154 | 2197 |
555808 | 350 | 4 | BK,RD,BE,WE | 0.615 | 35 | 70 | 1x1/0 | 2.133 | 65 | 2.265 | 2462 |
554932 | 500 | 4 | BK,RD,BE,WE | 0.735 | 35 | 70 | 1x3/0 | 2.423 | 80 | 2.589 | 3347 |
555811 | 600 | 4 | BK,RD,BE,WE | 0.812 | 58 | 80 | 1x3/0 | 2.662 | 75 | 2.812 | 3798 |
560782 | 600 | 4 | BK,RD,BE,WE | 0.812 | 58 | 80 | 1x400 | 2.919 | 80 | 3.085 | 4163 |
554933 | 750 | 4 | BK,RD,BE,WE | 0.908 | 53 | 80 | 1x3/0 | 2.895 | 80 | 3.061 | 4704 |
563603 | 750 | 4 | BK,RD,BE,WE | 0.908 | 53 | 80 | 1x750 | 3.200 | 90 | 3.388 | 5406 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 2 – Electrical and Engineering Data
Cond. Size | Conductor Number | Min. Bend Radius | Max Pull Tension | DC Resistance at 25°C | AC Resistance at 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity Raceway 75°C | Allowable Ampacity Raceway 90°C |
---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Inches | Lbs | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | |
1/0 | 2 | 8.5 | 1267 | 0.168 | 0.201 | 0.044 | 120 | 135 |
3/0 | 2 | 9.8 | 2013 | 0.105 | 0.126 | 0.042 | 155 | 175 |
4/0 | 2 | 10.5 | 2539 | 0.084 | 0.100 | 0.041 | 180 | 205 |
300 | 2 | 13.8 | 3600 | 0.059 | 0.071 | 0.041 | 230 | 260 |
350 | 2 | 14.5 | 4200 | 0.050 | 0.062 | 0.040 | 250 | 280 |
1/0 | 3 | 9.0 | 1900 | 0.168 | 0.201 | 0.044 | 120 | 135 |
2/0 | 3 | 9.7 | 2395 | 0.133 | 0.160 | 0.043 | 135 | 150 |
3/0 | 3 | 10.3 | 3020 | 0.105 | 0.126 | 0.042 | 155 | 175 |
4/0 | 3 | 12.1 | 3808 | 0.084 | 0.100 | 0.041 | 180 | 205 |
250 | 3 | 13.1 | 4500 | 0.071 | 0.086 | 0.041 | 205 | 230 |
250 | 3 | 13.1 | 4500 | 0.071 | 0.086 | 0.041 | 205 | 230 |
250 | 3 | 13.6 | 4500 | 0.071 | 0.086 | 0.041 | 205 | 230 |
350 | 3 | 14.5 | 6300 | 0.050 | 0.062 | 0.040 | 250 | 280 |
500 | 3 | 16.3 | 9000 | 0.035 | 0.044 | 0.039 | 310 | 350 |
500 | 3 | 16.3 | 9000 | 0.035 | 0.044 | 0.039 | 310 | 350 |
750 | 3 | 19.5 | 13500 | 0.024 | 0.031 | 0.038 | 385 | 435 |
1/0 | 4 | 9.9 | 2027 | 0.168 | 0.201 | 0.044 | 96 | 108 |
2/0 | 4 | 10.6 | 2555 | 0.133 | 0.160 | 0.043 | 108 | 120 |
4/0 | 4 | 13.2 | 4062 | 0.084 | 0.100 | 0.041 | 144 | 164 |
250 | 4 | 14.2 | 4800 | 0.071 | 0.086 | 0.041 | 164 | 184 |
250 | 4 | 14.2 | 4800 | 0.071 | 0.086 | 0.041 | 164 | 184 |
300 | 4 | 15.1 | 5760 | 0.059 | 0.071 | 0.041 | 184 | 208 |
350 | 4 | 15.9 | 6720 | 0.050 | 0.062 | 0.040 | 200 | 224 |
500 | 4 | 18.1 | 9600 | 0.035 | 0.044 | 0.039 | 248 | 280 |
600 | 4 | 19.7 | 11520 | 0.029 | 0.037 | 0.039 | 272 | 308 |
600 | 4 | 21.6 | 11520 | 0.029 | 0.037 | 0.039 | 272 | 308 |
750 | 4 | 21.4 | 14400 | 0.024 | 0.031 | 0.038 | 308 | 348 |
750 | 4 | 23.7 | 14400 | 0.024 | 0.031 | 0.038 | 308 | 348 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
Revision: 1.000.007