SPEC 60267

Duraclad® Type MC THHN/THWN Circuit Size Copper Conductor 277/480V Colors Dashed-Blue Armor

Copper THHN/THWN Insulated Singles. Green Insulated Copper Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Steel Dashed-Blue Interlocked Armor.

...

Construction:

  1. Conductor:Solid bare copper per ASTM B3
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape
  5. Armor:Lightweight Steel Dashed-Blue Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Cable is suitable for use as follows:
- Branch and service power distribution in commercial, industrial, institutional, and multi- residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Binder tape with print legend wrapped around assembly.
- Type THHN/THWN rated 90ºC Dry.

Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    SOUTHWIRE E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ftlbs/1000ft
    12 AWG | SOLID Strands
    571098122BN,GY0.081SOLID151x120.48460154
    571923122OE,GY0.081SOLID151x120.48460154
    571105122YW,GY0.081SOLID151x120.48460154
    571108122PE,GY0.081SOLID151x120.48460154
    592572123YW,YW,GY0.081SOLID151x120.5188097
    592571123BN,BN,GY0.081SOLID151x120.5188097
    592570123PE,PE,GY0.081SOLID151x120.5188097
    592338123OE,PE,GY0.081SOLID151x120.5148097
    571119123YW,PE,GY0.081SOLID151x120.51480181
    571118123BN,PE,GY0.081SOLID151x120.51580181
    592339123OE,YW,GY0.081SOLID151x120.5148097
    571112123BN,OE,GY0.081SOLID151x120.51580184
    571113123BN,YW,GY0.081SOLID151x120.51580184
    571149124BN,YW,PE,GY0.081SOLID151x120.55100213
    571914124BN,OE,YW,GY0.081SOLID151x120.55100213
    10 AWG | SOLID Strands
    571921102PE,GY0.102SOLID201x100.5593205
    571917102OE,GY0.102SOLID201x100.5593112
    571152102YW,GY0.102SOLID201x100.5593205
    571151102BN,GY0.102SOLID201x100.5593205
    592568103PK,PK,GY0.102SOLID201x100.59124149
    571161104BN,YW,PE,GY0.102SOLID201x100.634155297
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutral. Does not include green ground.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    12 AWG | SOLID Strands
    1223.41.6622.0630.0542530
    1223.41.6622.0630.0542530
    1223.41.6622.0630.0542530
    1223.41.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1243.91.6622.0630.0542024
    1243.91.6622.0630.0542024
    10 AWG | SOLID Strands
    1023.91.041.2910.053540
    1023.91.041.2910.053540
    1023.91.041.2910.053540
    1023.91.041.2910.053540
    1034.11.041.2910.053540
    1044.41.041.2910.052832
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.005