SPEC 60103

Armorlite® Type MC THHN/THWN 600V Circuit Size Copper Conductor PVC Jacketed 120/208V Colors. Silicone Free

Copper THHN/THWN Insulated Singles. Green Insulated Copper Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor. PVC Jacketed, Sunlight Resistant.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor
  6. Jacket:Polyvinyl Chloride (PVC) Jacket, sunlight resistant, corrosion resistant

Applications and Features:

Southwire Armorlite® Jacketed Type MC Cable is suitable for use as follows:
- Branch and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Suitable for Wet Location per NEC 330.10(A)(11)
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC Article 645
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Type THHN/THWN rated 90ºC Dry/ 75ºC Wet
- Anti-Short bushing not required

Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE {UL} E96627 X/C XX AWG CU THHN OR THWN CDRS 600 VOLTS GG 1 X X AWG CU TYPE MC EZ-JKT FOR CT USE SUN. RES. 90°C
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorJacket ThicknessApprox. ODCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchmilinchlbs/1000ftlbs/1000ft
    14 AWG | SOLID Strands
    610037142BK,WE0.064SOLID151x140.451500.55738144
    610041143BK,RD,WE0.064SOLID151x140.478500.58450165
    610045144BK,RD,BE,WE0.064SOLID151x140.504500.6163186
    12 AWG | SOLID Strands
    554666122BK,WE,GN0.081SOLID151x120.484500.5960162
    610050122BK,WE0.081SOLID151x120.484500.5960174
    561041122RD,WE0.081SOLID151x120.484500.5960174
    561045122BE,WE0.081SOLID151x120.484500.5960174
    610054123BK,RD,WE0.081SOLID151x120.515500.62180205
    610059124BK,RD,BE,WE0.081SOLID151x120.55500.656100237
    10 AWG | SOLID Strands
    561052102BE,WE0.102SOLID201x100.551500.65793229
    561048102RD,WE0.102SOLID201x100.551500.65793229
    610064102BK,WE0.102SOLID201x100.551500.65793229
    610068103BK,RD,WE0.102SOLID201x100.59500.696124276
    610074104BK,RD,BE,WE0.102SOLID201x100.634500.74155322
    10 AWG | 19 Strands
    678176103BK,WE,BE,GN0.11319201x100.626500.732129295
    14 AWG | 19 Strands
    564289143BK,RD,WE0.06419151x140.497500.60351173
    12 AWG | 19 Strands
    561439122BK,WE0.0919151x120.505500.61160182
    567274123BK,RD,WE0.0919151x120.539500.64580215
    677379124BK,RD,BE,WE0.0919151x120.577500.683100248
    10 AWG | 19 Strands
    552808102BK,WE0.11719201x100.583500.68997246
    585616102RD,WE0.11719201x100.584500.6997246
    553631103BK,RD,WE0.11719201x100.626500.732129295
    556420104BK,RD,BE,WE0.11719201x100.674500.78162347
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    14 AWG | SOLID Strands
    1423.92.6313.2650.0582025
    1434.12.6313.2650.0582025
    1444.32.6313.2650.0581620
    12 AWG | SOLID Strands
    1224.11.6622.0630.0542530
    1224.11.6622.0630.0542530
    1224.11.6622.0630.0542530
    1224.11.6622.0630.0542530
    1234.31.6622.0630.0542530
    1244.61.6622.0630.0542024
    10 AWG | SOLID Strands
    1024.61.041.2910.053540
    1024.61.041.2910.053540
    1024.61.041.2910.053540
    1034.91.041.2910.053540
    1045.21.041.2910.052832
    10 AWG | 19 Strands
    1035.11.041.2910.053540
    14 AWG | 19 Strands
    1434.22.6313.2650.0582025
    12 AWG | 19 Strands
    1224.31.6622.0630.0542530
    1234.51.6622.0630.0542530
    1244.81.6622.0630.0542024
    10 AWG | 19 Strands
    1024.81.041.2910.053540
    1024.81.041.2910.053540
    1035.11.041.2910.053540
    1045.51.041.2910.052832
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.012

    Updated On: June 24, 2025, 3:25 p.m. UTC