SPEC 60013

SIMpull MC-AP™ QUIK2Ground™ Type MC All Purpose THHN/THWN Circuit Size Copper Conductor 120/208V Colors

Copper THHN Insulated Conductors. Full-Sized Aluminum Equipment Grounding/Bonding Conductor. UL Listed 600 Volt. Rated VW1. Lightweight Aluminum Interlocked Armor is Part of Equipment Bonding/Grounding Path. Lightweight Low Profile Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Binder:Mylar tape
  4. Ground:Full-sized bare 8000 series aluminum grounding/bonding conductor. Armor and bare aluminum conductor form the equipment ground path.
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire SIMpull MCAP™ All Purpose Type MC Cable is suitable for use as follows:
- Branch, feeder and service power distribution in commercial, industrial, institutional, and multi- residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Binder tape with print legend wrapped around assembly.
- Type THHN/THWN rated 90ºC Dry.

Southwire SIMpull MCAP™ Type MC Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS -- ARMOR IS EQUIPMENT GROUNDING PATH COMPONENT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessDiameter Over ArmorCopper WeightOverall Weight
    AWG/Kcmilinchmilsinchlbs/1000ftlbs/1000ft
    14 AWG | SOLID Strands
    TBA142BK,WE0.064SOLID200.42126100
    TBA143BK,RD,WE0.064SOLID200.43839120
    TBA144BK,RD,BE,WE0.064SOLID200.46552142
    12 AWG | SOLID Strands
    TBA122RD,WE0.081SOLID200.45540124
    TBA122BE,WE0.081SOLID200.45540124
    TBA122BK,RD0.081SOLID200.45540124
    459362122BK,WE0.081SOLID200.45540124
    459364123BK,RD,WE0.081SOLID200.47460151
    TBA123RD,WE,BE0.081SOLID200.47460151
    TBA123BK,WE,BE0.081SOLID200.47460151
    TBA124BK,RD,BE,WE0.081SOLID200.50680182
    TBA126BK,RD,BE,WE/BK,WE/RD,WE/BE0.081SOLID200.576121245
    TBA126BK,BK/WE,RD/WE,RD,WE/BK,WE0.081SOLID200.576121245
    TBA128BK,BK/WE,RD,RD/WE,BE,BE/WE,WE,WE/BK0.081SOLID200.614161301
    12 AWG | 19 Strands
    TBA123RD,PE,WE0.08919200.49260156
    TBA124BK,RD,WE/BK,WE/RD0.08919200.52580188
    10 AWG | SOLID Strands
    TBA102BK,WE0.102SOLID250.51764165
    TBA102BE,WE0.102SOLID250.51764165
    TBA102RD,WE0.102SOLID250.51764165
    459365103BK,RD,WE0.102SOLID250.54196208
    TBA104BK,RD,BE,WE0.102SOLID250.581129255
    TBA104BK,RD,WE/BK,WE/RD0.102SOLID250.581129255
    TBA106BK,RD,BE,WE/BK,WE/RD,WE/BE0.102SOLID250.669193350
    TBA106BK,BK/WE,RD,RD/WE,WE,WE/BK0.102SOLID250.669193350
    10 AWG | 19 Strands
    TBA104BK,WE,RD,BE0.11319250.607129266
    TBA106BK,RD,BE,WE/BK,WE/RD,WE/BE0.11319250.702193364
    TBA106BK,RD,BK/WE,RD/WE,WE/BK,WE0.11319250.702193364
    TBA82BK,WE0.14219350.637103242
    TBA83BK,RD,WE0.14219350.671154312
    12 AWG | 19 Strands
    TBA122BE,WE0.0919200.47340128
    TBA122RD,WE0.0919200.47340128
    459363122BK,WE0.0919200.47340128
    459367123BK,RD,WE0.0919200.49460156
    TBA124BK,RD,BE,WE0.0919200.52880188
    10 AWG | 19 Strands
    TBA102BK,WE0.11719250.54764173
    TBA103BK,RD,WE0.11719250.57496217
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    14 AWG | SOLID Strands
    1422.92.6313.2650.0582025
    1433.12.6313.2650.0582025
    1443.32.6313.2650.0581620
    12 AWG | SOLID Strands
    1223.21.6622.0630.0542530
    1223.21.6622.0630.0542530
    1223.21.6622.0630.0542530
    1223.21.6622.0630.0542530
    1233.31.6622.0630.0542530
    1233.31.6622.0630.0542530
    1233.31.6622.0630.0542530
    1243.51.6622.0630.0542024
    12641.6622.0630.0542024
    12641.6622.0630.0542024
    1284.31.6622.0630.0541821
    12 AWG | 19 Strands
    1233.41.6622.0630.0542530
    1243.71.6622.0630.0542024
    10 AWG | SOLID Strands
    1023.61.041.2910.053540
    1023.61.041.2910.053540
    1023.61.041.2910.053540
    1033.81.041.2910.053540
    1044.11.041.2910.052832
    1044.11.041.2910.052832
    1064.71.041.2910.052832
    1064.71.041.2910.052832
    10 AWG | 19 Strands
    1044.21.041.2910.052832
    1064.91.041.2910.052832
    1064.91.041.2910.052832
    824.50.6530.810.0525055
    834.70.6530.810.0525055
    12 AWG | 19 Strands
    1223.31.6622.0630.0542530
    1223.31.6622.0630.0542530
    1223.31.6622.0630.0542530
    1233.51.6622.0630.0542530
    1243.71.6622.0630.0542024
    10 AWG | 19 Strands
    1023.81.041.2910.053540
    10341.041.2910.053540
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.