SPEC 25251

AL XLPE Type RPVU90 2KV

Single Aluminum Conductors, 1000V/2000V, 90°C MAX - 40°C MIN, Sunlight Resistant and FT4 Flame Test Rated

...

Construction:

  1. Conductor:AlumaFlex® Compact Stranded Aluminum Alloy (AA-8176)
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Single aluminum conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. Sunlight Resistant. This product meets the current RoHS requirements. No lead is added or used in manufacturing.

Specifications:

  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • RoHS Compliant Lead-Free, Silicone-Free
  • AA 8176 Stranded Aluminum Alloy Conductors
  • CSA Standard C22.2 No. 271 Photovoltaic Cables
  • Sample Print Legend:

    {SQMTR} SOUTHWIRE LL90458 {CSA} XXX KCMIL (XX{mm2}) COMPACT AL. --- {ALUMAFLEX}® AA8176 RPVU90 1000V/2000V XLPE FT1 (-40°C) SR DIR BUR RoHS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    TBA27800.4281071.73980.2670.3210.045100
    TBA119950.4881391.95020.2110.2540.046115
    TBA1/019950.5261662.16330.1680.2010.044135
    TBA2/019950.5661982.27980.1330.1600.043150
    TBA3/019950.6122382.410060.1050.1260.042175
    TBA4/019950.6642872.612690.0840.1000.041205
    TBA250351100.7403482.915000.0710.0860.041230
    618872300351100.8024233.218000.0590.0710.041260
    672571350351100.8364713.321000.0500.0620.040280
    TBA400351100.8795143.524000.0440.0540.040305
    669286500341100.9666443.830000.0350.0440.039350
    663031600411251.0557705.236000.0290.0370.039385
    669288750531251.1709475.845000.0240.0310.038435
    TBA1000581251.31011836.560000.0180.0250.037500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    TBA272.0310.8715943.1817710.881.050.1476100
    TBA1192.4112.4020748.2622340.690.830.1509115
    TBA1/0192.4113.3624753.3428170.550.660.1444135
    TBA2/0192.4114.3829555.8835510.440.520.1411150
    TBA3/0192.4115.5435460.9644770.340.410.1378175
    TBA4/0192.4116.8742766.0456470.280.330.1345205
    TBA250352.7918.8051873.6666750.230.280.1345230
    618872300352.7920.3762981.2880100.190.230.1345260
    672571350352.7921.2370183.8293450.160.200.1312280
    TBA400352.7922.3376588.90106800.140.180.1312305
    669286500342.7924.5495896.52133500.110.140.1280350
    663031600413.1826.801146132.08160200.100.120.1280385
    669288750533.1829.721409147.32200250.080.100.1247435
    TBA1000583.1833.271760165.10267000.060.080.1214500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Stock Code and Color (Other than Black)

    Stock CodeSize AWGColor
    672572350Red
    663032600Red
    669289750Red

    Revision: 1.000.002

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC