SPEC 85011

Multi-Conductor CU 600 V FR-XLPE Thermoplastic CPE-TP Jacket Control Cable Color Method 1 Table 2

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE XHHW-2 TYPE TC CDRS 90C CPE JKT 600V SUNLIGHT RESISTANT MM/YYYY{SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C CPE JKT 600V SUN. RES. DIRECT BURIAL YEAR SEQUENTIAL FOOTAGE MARKS SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessDiameter Over InsulationJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilinchmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    14 AWG
    TBA14370.071300.131450.37939812.6313.2650.0581.52025BK
    TBA14470.071300.131450.413531032.6313.2650.0581.71620BK
    619662$144190.071300.131450.424511142.6313.2650.0581.71620BK
    TBA14570.071300.131450.45661252.6313.2650.0581.81620BK
    TBA14670.071300.131450.489791462.6313.2650.05821620BK
    TBA14770.071300.131450.489921652.6313.2650.05821418BK
    TBA14870.071300.131600.561052012.6313.2650.0582.21418BK
    TBA14970.071300.131600.5991182232.6313.2650.0582.41418BK
    TBA141070.071300.131600.651312472.6313.2650.0582.61012BK
    604289141270.071300.131600.6731542962.6313.2650.0582.71012BK
    TBA141570.071300.131600.7431973502.6313.2650.05831012BK
    TBA141970.071300.131600.7812494272.6313.2650.0583.11012BK
    TBA142070.071300.131600.8222634512.6313.2650.0583.31012BK
    TBA142570.071300.131800.9523285852.6313.2650.0583.8911BK
    TBA143070.071300.131801.0063946862.6313.2650.0585911BK
    TBA143770.071300.131801.0834868272.6313.2650.0585.4810BK
    619661$142190.073300.133450.36826692.6313.2650.0581.52025BK
    619663$1412190.073300.133600.6921543042.6313.2650.0582.81012BK
    12 AWG
    606668^12270.089300.149450.40941891.6622.0630.0541.62530BK
    66194412370.089300.149450.429611201.6622.0630.0541.72530BK
    TBA12470.089300.149450.457811391.6622.0630.0541.82024BK
    624834!12470.089300.149450.477811531.6622.0630.0541.92024BK
    TBA12570.089300.149450.4981011691.6622.0630.05422024BK
    TBA12670.089300.149600.5731212131.6622.0630.0542.32024BK
    TBA12770.089300.149600.5731412391.6622.0630.0542.31821BK
    TBA12870.089300.149600.6191622721.6622.0630.0542.51821BK
    TBA12970.089300.149600.6641823031.6622.0630.0542.71821BK
    TBA121070.089300.149600.7222023351.6622.0630.0542.91215BK
    662180^121270.089300.149600.7672444161.6622.0630.0543.11215BK
    662211121270.089300.149600.7672444161.6622.0630.0543.11215BK
    TBA121570.089300.149800.8683035091.6622.0630.0543.51215BK
    606714^121970.089300.149800.923876541.6622.0630.0543.71215BK
    TBA122070.089300.149800.9574046551.6622.0630.0543.81215BK
    TBA122570.089300.149801.065058011.6622.0630.0545.31114BK
    TBA123070.089300.149801.1216069431.6622.0630.0545.61114BK
    TBA123770.089300.149801.20974711411.6622.0630.05461012BK
    604308$127190.09300.15600.5951412571.6622.0630.0542.41821BK
    10 AWG
    604290^10270.113300.173450.452651211.041.2910.051.83540BK
    TBA10370.113300.173450.47971541.041.2910.051.93540BK
    606503^10470.113300.1730.5411292231.041.2910.052.22832BK
    60429110470.113300.173600.5581292261.041.2910.052.22832BK
    TBA10570.113300.173600.5931622561.041.2910.052.42832BK
    TBA10670.113300.173600.6451943021.041.2910.052.62832BK
    62225410770.113300.173600.6612273611.041.2910.052.62428BK
    TBA10870.113300.173600.6992593881.041.2910.052.82428BK
    45986410970.113300.173800.7692914561.041.2910.053.12428BK
    TBA101070.113300.173600.8183234791.041.2910.053.31820BK
    606610^101270.113300.173800.9093886261.041.2910.053.61820BK
    TBA101570.113300.173800.9814857261.041.2910.053.91820BK
    TBA101970.113300.173801.0316148921.041.2910.055.21820BK
    TBA102070.113300.173801.0856469401.041.2910.055.41820BK
    TBA102570.113300.173801.20480811571.041.2910.0561618BK
    TBA103070.113300.173801.27597013671.041.2910.056.41618BK
    TBA103770.113300.173801.377119616601.041.2910.056.91416BK
    619664$102190.117300.177450.452651211.041.2910.051.83540BK
    619665$104190.117300.177600.5581292331.041.2910.052.22832BK
    619666$1012190.117300.177800.9093886261.041.2910.053.61820BK
    8 AWG
    6618668270.142450.232600.6021032160.6530.810.0522.45055BK
    6618658470.142450.232600.72063540.6530.810.0522.84044BK
    6 AWG
    6229916470.178450.268600.7873275110.4110.510.0513.15260BK
    603629†64190.178450.268600.7923275110.4110.510.0513.25260BK
    4 AWG
    6619464470.225450.315800.9335217680.2580.320.0483.76876BK
    603628$44190.225450.315800.9455217900.2580.320.0483.86876BK
    2 AWG
    603627†24190.286450.376801.09282811270.1620.2010.0455.592104BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    ! Tinned copper conductor per ASTM B33
    † 19 strand Class C conductor per ASTM B8
    $ 19 strand combination unilay conductor per ASTM B787
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.007

    Updated On: Dec. 31, 2024, 11:09 p.m. UTC