SPEC 85005

Multi-Conductor CU 600 V FR-XLPE PVC Jacket Control Cable Color Method 1 Table 2

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE)
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 66 Fixture Wire
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • CSA CSA marking is available upon request
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE {UL} XX AWG X/C FR-XLPE CDRS 90C PVC JKT 600V TYPE TC-ER SUN. RES. DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C PVC JKT 600V SUN. RES. DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.milmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    62055618425450.33420616.6698.0350.0361.3-11Black
    16 AWG
    60689516425450.35832784.1815.0370.0331.4-14Black
    62353316725450.425561204.1815.0370.0331.7-12Black
    62353516925450.492721504.1815.0370.0331.9-12Black
    14 AWG
    625291^14230450.35725682.6313.1700.0581.42025Black
    TBA14330450.37238852.6313.1700.0581.42025Black
    624097^14430450.424511122.6313.1700.0581.71620Black
    TBA14530450.443631222.6313.1700.0581.71620Black
    TBA14630450.482761432.6313.1700.0581.91620Black
    TBA14730450.482891612.6313.1700.0581.91417Black
    TBA14830600.5521021992.6313.1700.0582.21417Black
    TBA14930600.5911152222.6313.1700.0582.31417Black
    TBA141030600.6421272452.6313.1700.0582.51012Black
    624096^141230600.6691532982.6313.1700.0582.61012Black
    TBA141530600.7341913432.6313.1700.0582.91012Black
    662633^141930600.7782434412.6313.1700.0583.11012Black
    TBA142030600.8122554422.6313.1700.0583.21012Black
    TBA142530800.9423195772.6313.1700.0583.7911Black
    TBA143030800.9953836742.6313.1700.0583.9911Black
    TBA143730801.0724738102.6313.1700.0585.3810Black
    12 AWG
    TBA12230450.38840871.6622.0020.0541.52530Black
    62066112230450.39240881.6622.0020.0541.52530Black
    TBA12330450.411611151.6622.0020.0541.62530Black
    620722^12430450.459811491.6622.0020.0541.82024Black
    607613^12430450.467811521.6622.0020.0541.92024Black
    TBA12530450.4911011681.6622.0020.0541.92024Black
    TBA12630600.5661222161.6622.0020.0542.22024Black
    607615^12730600.5831422591.6622.0020.0542.31721Black
    62136312730600.6361622931.6622.0020.0542.51721Black
    TBA12830600.6371622831.6622.0020.0542.51721Black
    TBA12930600.6571833121.6622.0020.0542.61721Black
    TBA121030600.7142033371.6622.0020.0542.81215Black
    620554^121230600.7422444101.6622.0020.0542.91215Black
    607650^12430600.7462444121.6622.0020.0542.92024Black
    622458121530800.8613055321.6622.0020.0543.41215Black
    TBA121930800.9023866261.6622.0020.0543.61215Black
    TBA122030800.9474066581.6622.0020.0543.71215Black
    TBA122530801.0505088051.6622.0020.0545.21113Black
    TBA123030801.1106109451.6622.0020.0545.51113Black
    TBA123730801.19875211421.6622.0020.0545.91012Black
    10 AWG
    61908610230450.444641221.0401.2530.0501.73540Black
    618887^10230450.448641361.0401.2530.0501.73540Black
    620546^10330450.467971691.0401.2530.0501.83540Black
    60796010430450.5061292111.0401.2530.0502.02832Black
    618888^10430600.5581292281.0401.2530.0502.22832Black
    628424^10530600.5911612701.0401.2530.0502.32832Black
    619089^10730600.6402263541.0401.2530.0502.52428Black
    TBA10630600.6411943041.0401.2530.0502.52832Black
    TBA10830600.6942583891.0401.2530.0502.72428Black
    TBA10930600.7462914351.0401.2530.0502.92428Black
    TBA101030600.8143234821.0401.2530.0503.21720Black
    607647^101230800.8783886151.0401.2530.0503.51720Black
    619091^101230800.8873886241.0401.2530.0503.51720Black
    TBA101530800.9764857311.0401.2530.0503.91720Black
    TBA101930801.0276148961.0401.2530.0505.11720Black
    TBA102030801.0806469441.0401.2530.0505.41720Black
    TBA102430801.20077611211.0401.2530.0506.01518Black
    TBA102530801.20080811601.0401.2530.0506.01518Black
    TBA103030801.27097013681.0401.2530.0506.31518Black
    TBA103730801.373119616591.0401.2530.0506.81416Black
    8 AWG
    6080268245600.5841021960.6530.7860.0522.35055Black
    6205538245600.5981022180.6530.7860.0522.35055Black
    6607138345600.6401542910.6530.7860.0522.65055Black
    6080598445600.6782053420.6530.7860.0522.74044Black
    604092^8445600.6942053650.6530.7860.0522.74044Black
    607652^8445600.6942053540.6530.7860.0522.74044Black
    6 AWG
    6240956445600.7813275260.4110.4950.0513.15260Black
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.004

    Updated On: Dec. 31, 2024, 11:09 p.m. UTC