SPEC 45411
CU 2000V XLPE Insulation. RHH/RHW-2 PV
Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Copper Conductor XLPE Insulation. Sizes 14 AWG through 1000 Kcmil. Heat, Moisture, Sunlight Resistant RoHS. 90°C

Construction:
- Conductor:Stranded bare copper per ASTM B3 and ASTM B8 or ASTM B787
- Insulation:Cross Linked Polyethylene (XLPE). Colors available upon request.
Applications and Features:
Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.
Specifications:
Sample Print Legend:
Non VW-1 Rated:
{SQFTG} SOUTHWIRE E316464 {UL} PV WIRE XX AWG or KCMIL (XX.X{MM2}) CU 2000V 90°C WET OR DRY -40°C SUN RES DIRECT BURIAL OR RHH-RHW-2 2000V --- RoHS
VW-1 Rated:
{SQFTG} SOUTHWIRE E316464 {UL} PV WIRE XX AWG (XX.X{MM2}) CU 2000V 90°C WET OR DRY (-40°C) SUN RES DIRECT BURIAL VW-1 OR RHW-2 2000V---RoHS
{SQFTG} SOUTHWIRE E316464 {UL} PV WIRE XX AWG or KCMIL (XX.X{MM2}) CU 2000V 90°C WET OR DRY -40°C SUN RES DIRECT BURIAL OR RHH-RHW-2 2000V --- RoHS
VW-1 Rated:
{SQFTG} SOUTHWIRE E316464 {UL} PV WIRE XX AWG (XX.X{MM2}) CU 2000V 90°C WET OR DRY (-40°C) SUN RES DIRECT BURIAL VW-1 OR RHW-2 2000V---RoHS
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | inch | inch | lb/1000ft | lb/1000ft | ||
| 597961 | 14 | 19 | 0.073 | 75 | 0.223 | 0.224 | 13 | 29 | BK |
| 597958 | 12 | 19 | 0.089 | 75 | 0.239 | 0.243 | 20 | 39 | BK |
| 579962 | 10 | 19 | 0.113 | 75 | 0.263 | 0.263 | 32 | 53 | BK |
| 569037 | 8 | 19 | 0.142 | 85 | 0.312 | 0.313 | 51 | 79 | BK |
| 569039 | 6 | 19 | 0.178 | 85 | 0.348 | 0.349 | 81 | 114 | BK |
| 569040 | 4 | 19 | 0.225 | 85 | 0.395 | 0.396 | 129 | 168 | BK |
| 138983 | 2 | 19 | 0.283 | 85 | 0.453 | 0.456 | 205 | 250 | BK |
| TBA | 1 | 19 | 0.322 | 105 | 0.532 | 0.532 | 258 | 337 | BK |
| 569043 | 1/0 | 19 | 0.362 | 105 | 0.572 | 0.57 | 326 | 397 | BK |
| 569044 | 2/0 | 19 | 0.405 | 105 | 0.615 | 0.614 | 411 | 489 | BK |
| 569045 | 3/0 | 19 | 0.456 | 105 | 0.666 | 0.664 | 518 | 604 | BK |
| 569047 | 4/0 | 19 | 0.512 | 105 | 0.722 | 0.72 | 655 | 751 | BK |
| 679559 | 250 | 37 | 0.558 | 120 | 0.798 | 0.782 | 772 | 879 | BK |
| 653096 | 300 | 37 | 0.611 | 120 | 0.851 | 0.851 | 926 | 1052 | BK |
| 590138 | 350 | 37 | 0.661 | 120 | 0.901 | 0.901 | 1081 | 1215 | BK |
| 587813 | 400 | 37 | 0.706 | 120 | 0.946 | 0.946 | 1235 | 1378 | BK |
| 578324 | 500 | 37 | 0.789 | 120 | 1.029 | 1.006 | 1544 | 1685 | BK |
| 672530 | 600 | 61 | 0.866 | 135 | 1.136 | 1.136 | 1853 | 2042 | BK |
| 588931 | 750 | 61 | 0.968 | 135 | 1.238 | 1.238 | 2316 | 2524 | BK |
| 457200 | 1000 | 61 | 1.117 | 135 | 1.387 | 1.387 | 3087 | 3324 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
*VW-1 Rated
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Min Bending Radius | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | |
| 597961 | 14 | 0.9 | 2.631 | 3.265 | 0.058 | 20 | 25 |
| 597958 | 12 | 1 | 1.662 | 2.063 | 0.054 | 25 | 30 |
| 579962 | 10 | 1.1 | 1.04 | 1.291 | 0.05 | 35 | 40 |
| 569037 | 8 | 1.3 | 0.653 | 0.81 | 0.052 | 50 | 55 |
| 569039 | 6 | 1.4 | 0.411 | 0.51 | 0.051 | 65 | 75 |
| 569040 | 4 | 1.6 | 0.258 | 0.32 | 0.048 | 85 | 95 |
| 138983 | 2 | 1.8 | 0.162 | 0.201 | 0.045 | 115 | 130 |
| TBA | 1 | 2.1 | 0.128 | 0.159 | 0.046 | 130 | 145 |
| 569043 | 1/0 | 2.3 | 0.102 | 0.127 | 0.044 | 150 | 170 |
| 569044 | 2/0 | 2.5 | 0.082 | 0.102 | 0.043 | 175 | 195 |
| 569045 | 3/0 | 2.7 | 0.064 | 0.079 | 0.042 | 200 | 225 |
| 569047 | 4/0 | 2.9 | 0.051 | 0.063 | 0.041 | 230 | 260 |
| 679559 | 250 | 3.1 | 0.043 | 0.053 | 0.041 | 255 | 290 |
| 653096 | 300 | 3.4 | 0.036 | 0.045 | 0.041 | 285 | 320 |
| 590138 | 350 | 3.6 | 0.031 | 0.039 | 0.04 | 310 | 350 |
| 587813 | 400 | 3.8 | 0.027 | 0.035 | 0.04 | 335 | 380 |
| 578324 | 500 | 5 | 0.021 | 0.027 | 0.039 | 380 | 430 |
| 672530 | 600 | 5.7 | 0.018 | 0.024 | 0.039 | 420 | 475 |
| 588931 | 750 | 6.2 | 0.014 | 0.019 | 0.038 | 475 | 535 |
| 457200 | 1000 | 6.9 | 0.011 | 0.016 | 0.037 | 545 | 615 |
Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.
Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.
Stock Code Colors
| Size | Black | White | Red | Green | Green/Yellow |
|---|---|---|---|---|---|
| AWG/kcmil | |||||
| 14 | 597961 | ||||
| 12 | 597958 | 596376 | 596377 | ||
| 10 | 579962 | 583665 | 583687 | ||
| 2 | 138983 | ||||
| 1/0 | 569043 | 677562 | |||
| 2/0 | 569044 | ||||
| 3/0 | 569045 | ||||
| 4/0 | 569047 | ||||
| 250 | 679559 | ||||
| 300 | 653096 | 599400 | 599401 | ||
| 350 | 590138 | ||||
| 400 | 587813 | ||||
| 500 | 578324 | ||||
| 600 | 672530 | ||||
| 750 | 588931 | 457948 | |||
| 1000 | 457200 |
Stock Code Colors (VW-1)
| Size | Black | White | Red | Green | Green/Yellow |
|---|---|---|---|---|---|
| AWG/kcmil | |||||
| 10 | 568110 | 577645 | |||
| 8 | 569037 | 585080 | 589110 | ||
| 6 | 569039 | 671956 | 585840 | ||
| 4 | 569040 | 673880 | 653094 | ||
| 2 | TBA |
Revision: 1.000.021
Updated On: Feb. 5, 2026, 3:47 p.m. UTC

