SPEC 45252
CU 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Copper Ground (Bare or Insulated). CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free.

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8. (When present, cable conductor sizes 8 & 6 AWG have an insulated green ground)
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Specifications:
Sample Print Legend:
Bare Ground: {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{mm2}) 3/C TYPE TC-ER XHHW-2 CDRS 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT SR 600V 90C
Green Ground: {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{mm2}) CU 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU GREEN INSULATED 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT SR 600V 90C
Green Ground: {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{mm2}) CU 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU GREEN INSULATED 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT SR 600V 90C
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |||
| 555196◊ | 8 | 3 | 7 | 0.142 | 45 | 0.232 | 1 x 10 | 60 | 0.627 | 154 | 284 | BK |
| 555195 | 6 | 3 | 7 | 0.178 | 45 | 0.268 | 1 x 8 | 60 | 0.714 | 246 | 390 | BK |
| 480616◊ | 4 | 3 | 7 | 0.225 | 45 | 0.315 | 1 x 8 | 60 | 0.815 | 442 | 613 | BK |
| 480624◊ | 2 | 3 | 7 | 0.283 | 45 | 0.373 | 1 x 6 | 80 | 0.982 | 703 | 923 | BK |
| 480632◊ | 1 | 3 | 19 | 0.322 | 55 | 0.432 | 1 x 6 | 80 | 1.117 | 865 | 1137 | BK |
| 480640◊ | 1/0 | 3 | 19 | 0.362 | 55 | 0.472 | 1 x 6 | 80 | 1.213 | 1070 | 1396 | BK |
| 480657◊ | 2/0 | 3 | 19 | 0.405 | 55 | 0.515 | 1 x 6 | 80 | 1.304 | 1327 | 1684 | BK |
| 480665◊ | 3/0 | 3 | 19 | 0.456 | 55 | 0.566 | 1 x 4 | 80 | 1.412 | 1700 | 2073 | BK |
| 480673◊ | 4/0 | 3 | 19 | 0.512 | 55 | 0.622 | 1 x 4 | 80 | 1.507 | 2110 | 2540 | BK |
| 480681◊ | 250 | 3 | 37 | 0.558 | 65 | 0.688 | 1 x 4 | 80 | 1.641 | 2469 | 2939 | BK |
| 672206 | 350 | 3 | 37 | 0.661 | 65 | 0.791 | 1 x 1 | 115 | 1.915 | 3536 | 4258 | BK |
| 480707◊ | 350 | 3 | 37 | 0.661 | 65 | 0.791 | 1 x 3 | 115 | 1.919 | 3439 | 4088 | BK |
| 588013 | 350 | 3 | 37 | 0.661 | 65 | 0.791 | 1 x 3/0 | 115 | 2.117 | 3798 | 4531 | BK |
| 480715 | 400 | 3 | 37 | 0.706 | 65 | 0.836 | 1 x 3 | 115 | 2.014 | 3906 | 4644 | BK |
| 582435 | 500 | 3 | 37 | 0.789 | 65 | 0.919 | 1 x 2 | 110 | 2.177 | 4885 | 5728 | BK |
| 890148 | 500 | 3 | 37 | 0.789 | 65 | 0.919 | 1 x 1/0 | 115 | 2.189 | 5007 | 5824 | BK |
| 583697 | 500 | 3 | 37 | 0.789 | 65 | 0.919 | 1 x 2/0 | 115 | 2.274 | 5093 | 5956 | BK |
| 593173 | 600 | 3 | 61 | 0.866 | 80 | 1.026 | 1 x 3/0 | 115 | 2.418 | 6136 | 7120 | BK |
| 890388◊ | 600 | 3 | 61 | 0.866 | 80 | 1.026 | 1 x 2 | 115 | 2.418 | 5820 | 6736 | BK |
| 665766 | 600 | 3 | 61 | 0.866 | 80 | 1.026 | 1 x 1/0 | 115 | 2.418 | 5942 | 6926 | BK |
| 665768 | 600 | 3 | 61 | 0.866 | 80 | 1.026 | 1 x 400 | 115 | 2.503 | 6860 | 7877 | BK |
| 672210 | 600 | 3 | 61 | 0.866 | 80 | 1.026 | 1 x 250 | 115 | 2.546 | 6393 | 7418 | BK |
| 554410 | 750 | 3 | 61 | 0.968 | 80 | 1.128 | 1 x 1 | 115 | 2.694 | 7277 | 8521 | BK |
| 589359 | 750 | 3 | 61 | 0.968 | 80 | 1.128 | 1 x 4/0 | 115 | 2.694 | 7676 | 8919 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
GG: Green Insulated Ground
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| 555196◊ | 8 | 3 | 2.5 | 396 | 0.653 | 0.81 | 0.052 | 50 | 55 |
| 555195 | 6 | 3 | 2.9 | 629 | 0.411 | 0.51 | 0.051 | 65 | 75 |
| 480616◊ | 4 | 3 | 3.3 | 1001 | 0.258 | 0.32 | 0.048 | 85 | 95 |
| 480624◊ | 2 | 3 | 3.9 | 1592 | 0.162 | 0.201 | 0.045 | 115 | 130 |
| 480632◊ | 1 | 3 | 5.6 | 2008 | 0.128 | 0.159 | 0.046 | 130 | 145 |
| 480640◊ | 1/0 | 3 | 6.1 | 2534 | 0.102 | 0.127 | 0.044 | 150 | 170 |
| 480657◊ | 2/0 | 3 | 6.5 | 3194 | 0.082 | 0.102 | 0.043 | 175 | 195 |
| 480665◊ | 3/0 | 3 | 7.1 | 4027 | 0.064 | 0.079 | 0.042 | 200 | 225 |
| 480673◊ | 4/0 | 3 | 7.5 | 5078 | 0.051 | 0.063 | 0.041 | 230 | 260 |
| 480681◊ | 250 | 3 | 8.2 | 6000 | 0.043 | 0.053 | 0.041 | 255 | 290 |
| 672206 | 350 | 3 | 9.6 | 8400 | 0.031 | 0.039 | 0.04 | 310 | 350 |
| 480707◊ | 350 | 3 | 9.6 | 8400 | 0.031 | 0.039 | 0.04 | 310 | 350 |
| 588013 | 350 | 3 | 12.7 | 8400 | 0.031 | 0.039 | 0.04 | 310 | 350 |
| 480715 | 400 | 3 | 12.1 | 9600 | 0.027 | 0.035 | 0.04 | 335 | 380 |
| 582435 | 500 | 3 | 13.1 | 12000 | 0.021 | 0.027 | 0.039 | 380 | 430 |
| 890148 | 500 | 3 | 13.1 | 12000 | 0.021 | 0.027 | 0.039 | 380 | 430 |
| 583697 | 500 | 3 | 13.6 | 12000 | 0.021 | 0.027 | 0.039 | 380 | 430 |
| 593173 | 600 | 3 | 14.5 | 14400 | 0.018 | 0.024 | 0.039 | 420 | 475 |
| 890388◊ | 600 | 3 | 14.5 | 14400 | 0.018 | 0.024 | 0.039 | 420 | 475 |
| 665766 | 600 | 3 | 14.5 | 14400 | 0.018 | 0.024 | 0.039 | 420 | 475 |
| 665768 | 600 | 3 | 15 | 14400 | 0.018 | 0.024 | 0.039 | 420 | 475 |
| 672210 | 600 | 3 | 15.3 | 14400 | 0.018 | 0.024 | 0.039 | 420 | 475 |
| 554410 | 750 | 3 | 16.2 | 18000 | 0.014 | 0.019 | 0.038 | 475 | 535 |
| 589359 | 750 | 3 | 16.2 | 18000 | 0.014 | 0.019 | 0.038 | 475 | 535 |
*Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.012
Updated On: Oct. 1, 2026, 9:04 p.m. UTC


