SPEC 80123
AAC/TW
All Aluminum Conductor. Trapezoidal Shaped Aluminum Strands. Bare

Construction:
- Conductor:Aluminum 1350-H19 trapezoidal shaped wires, concentrically stranded.
Applications and Features:
Shaped Wire Compact Concentric-Lay-Stranded Aluminum Conductor (AAC/TW) is designed for use as a bare overhead conductor. There are two designs of AAC/TW. One design gives an equal area of aluminum when compared to the standard AAC conductor sizes. The other design is conductor with overall outside diameters that are in fixed-increments. Use of this conductor in the equal area design allows comparable ampacity in a smaller diameter conductor when compared with standard AAC conductor. Use of this conductor in the fixed-increment diameter design allows more ampacity in an equal diameter conductor when compared with standard AAC conductor.
Specifications:
Area Equal to Standard AAC Sizes - Weights and Measurements
| Stock Number | Code Name | Size | No. of Wires | No. of Layers | Overall OD | Overall Weight |
|---|---|---|---|---|---|---|
| (AWG or kcmil) | inch | lbs/1,000' | ||||
| Tulip/TW | 336.4 | 17 | 2 | 0.612 | 315.2 | |
| Canna/TW | 397.5 | 17 | 2 | 0.661 | 372.4 | |
| Cosmos/TW | 477 | 17 | 2 | 0.72 | 446.9 | |
| Zinnia/TW | 500 | 17 | 2 | 0.736 | 468.4 | |
| Mistletoe/TW | 556.5 | 17 | 2 | 0.775 | 521.3 | |
| Meadowsweet/TW | 600 | 17 | 2 | 0.803 | 652.1 | |
| Orchid/TW | 636 | 17 | 2 | 0.825 | 595.8 | |
| Verbena/TW | 700 | 17 | 2 | 0.864 | 655.7 | |
| Nasturtium/TW | 750 | 17 | 2 | 0.893 | 702.6 | |
| Arbutus/TW | 795 | 17 | 2 | 0.919 | 744.7 | |
| Cockscomb/TW | 900 | 17 | 3 | 0.99 | 846.6 | |
| Magnolia/TW | 954 | 31 | 3 | 1.018 | 897.4 | |
| Hawkweed/TW | 1000 | 31 | 3 | 1.041 | 940.6 | |
| Bluebell/TW | 1033.5 | 31 | 3 | 1.057 | 972.2 | |
| Marigold/TW | 1113 | 31 | 3 | 1.095 | 1047 | |
| Hawthorn/TW | 1192.5 | 31 | 3 | 1.132 | 1122 | |
| Narcissus/TW | 1272 | 31 | 3 | 1.168 | 1196 | |
| Columbine/TW | 1351.5 | 31 | 3 | 1.202 | 1271 | |
| Carnation/TW | 1431 | 31 | 3 | 1.236 | 1346 | |
| Coreopsis/TW | 1590 | 49 | 4 | 1.315 | 1503 | |
| Jessamine/TW | 1750 | 49 | 4 | 1.377 | 1654 | |
| Cowslip/TW | 2000 | 49 | 4 | 1.468 | 1890 | |
| Lupine/TW | 2500 | 71 | 5 | 1.648 | 2369 | |
| Trillium/TW | 3000 | 71 | 5 | 1.799 | 2843 |
Area Equal to Standard AAC Sizes - Electrical and Engineering Data
| Stock Number | Code Name | Size | Rated Strength | DC Resistance @ 25ºC | AC Resistance @ 75ºC | Allowable Ampacities+ |
|---|---|---|---|---|---|---|
| (AWG or kcmil) | lbs | Ohms/1,000' | Ohms/1,000' | Amps | ||
| Tulip/TW | 336.4 | 6220 | 0.0514 | 0.063 | 502 | |
| Canna/TW | 397.5 | 7230 | 0.0435 | 0.0534 | 557 | |
| Cosmos/TW | 477 | 8530 | 0.0363 | 0.0445 | 623 | |
| Zinnia/TW | 500 | 8940 | 0.0346 | 0.0425 | 641 | |
| Mistletoe/TW | 556.5 | 9950 | 0.0311 | 0.0383 | 685 | |
| Meadowsweet/TW | 600 | 10700 | 0.0288 | 0.0355 | 718 | |
| Orchid/TW | 636 | 11400 | 0.0272 | 0.0335 | 744 | |
| Verbena/TW | 700 | 12500 | 0.0247 | 0.0305 | 789 | |
| Nasturtium/TW | 750 | 13400 | 0.023 | 0.0286 | 823 | |
| Arbutus/TW | 795 | 13900 | 0.0217 | 0.027 | 853 | |
| Cockscomb/TW | 900 | 15800 | 0.0192 | 0.0239 | 924 | |
| Magnolia/TW | 954 | 16700 | 0.0181 | 0.0226 | 957 | |
| Hawkweed/TW | 1000 | 17500 | 0.0173 | 0.0216 | 984 | |
| Bluebell/TW | 1033.5 | 18100 | 0.0167 | 0.021 | 1004 | |
| Marigold/TW | 1113 | 19500 | 0.0155 | 0.0195 | 1049 | |
| Hawthorn/TW | 1192.5 | 20900 | 0.0145 | 0.0183 | 1094 | |
| Narcissus/TW | 1272 | 22300 | 0.0136 | 0.0173 | 1136 | |
| Columbine/TW | 1351.5 | 23700 | 0.0128 | 0.0163 | 1177 | |
| Carnation/TW | 1431 | 24600 | 0.0121 | 0.0155 | 1218 | |
| Coreopsis/TW | 1590 | 27300 | 0.0109 | 0.0141 | 1298 | |
| Jessamine/TW | 1750 | 30000 | 0.0099 | 0.0129 | 1371 | |
| Cowslip/TW | 2000 | 34500 | 0.0086 | 0.0115 | 1477 | |
| Lupine/TW | 2500 | 42400 | 0.007 | 0.0097 | 1661 | |
| Trillium/TW | 3000 | 50900 | 0.0058 | 0.0084 | 1822 |
+Ampacity calculated assuming: ambient 25°C, conductor 75°C wind 2 ft./sec., sun.
Fixed Diameter Increments - Weights and Measurements
| Stock Number | Code Name | Size | No. of Wires | No. of Layers | Overall OD | Overall Weight |
|---|---|---|---|---|---|---|
| (AWG or kcmil) | inch | lbs/1,000' | ||||
| Logan/TW | 322.5 | 17 | 2 | 0.6 | 302.1 | |
| Wheeler/TW | 449.4 | 17 | 2 | 0.7 | 421 | |
| Robson/TW | 595.8 | 17 | 2 | 0.8 | 558.2 | |
| McKinley/TW | 761.5 | 17 | 2 | 0.9 | 713.3 | |
| Rainier/TW | 918.8 | 31 | 3 | 1 | 864.3 | |
| Helens/TW | 1123.1 | 31 | 3 | 1.1 | 1056 | |
| Baker/TW | 1346.8 | 31 | 3 | 1.2 | 1267 | |
| Hood/TW | 1583.2 | 34 | 3 | 1.3 | 1489 | |
| Whitney/TW | 1812.7 | 49 | 4 | 1.4 | 1713 | |
| Powell/TW | 2093.6 | 49 | 4 | 1.5 | 1978 | |
| Jefferson/TW | 2388.1 | 52 | 4 | 1.6 | 2256 | |
| Shasta/TW | 2667.2 | 71 | 5 | 1.7 | 2528 | |
| Adams/TW | 3006.2 | 71 | 5 | 1.8 | 2848 |
Fixed Diameter Increments - Electrical and Engineering Data
| Stock Number | Code Name | Size | Rated Strength | DC Resistance @ 25ºC | AC Resistance @ 75ºC | Allowable Ampacities+ |
|---|---|---|---|---|---|---|
| (AWG or kcmil) | lbs | Ohms/1,000' | Ohms/1,000' | Amps | ||
| Logan/TW | 322.5 | 5960 | 0.0536 | 0.0657 | 489 | |
| Wheeler/TW | 449.4 | 8030 | 0.0385 | 0.0472 | 601 | |
| Robson/TW | 595.8 | 10700 | 0.029 | 0.0358 | 715 | |
| McKinley/TW | 761.5 | 13400 | 0.0227 | 0.0281 | 831 | |
| Rainier/TW | 918.8 | 16100 | 0.0188 | 0.0235 | 935 | |
| Helens/TW | 1123.1 | 19700 | 0.0154 | 0.0194 | 1055 | |
| Baker/TW | 1346.8 | 23600 | 0.0128 | 0.0164 | 1175 | |
| Hood/TW | 1583.2 | 27200 | 0.0109 | 0.0141 | 1292 | |
| Whitney/TW | 1812.7 | 31100 | 0.0095 | 0.0125 | 1398 | |
| Powell/TW | 2093.6 | 35900 | 0.0083 | 0.0112 | 1508 | |
| Jefferson/TW | 2388.1 | 40100 | 0.0073 | 0.01 | 1618 | |
| Shasta/TW | 2667.2 | 45200 | 0.0065 | 0.0092 | 1718 | |
| Adams/TW | 3006.2 | 51000 | 0.0059 | 0.0085 | 1818 |
+Ampacity calculated assuming: ambient 25°C, conductor 75°C wind 2 ft./sec., sun.