SPEC 80102

ACSR/AW

Aluminum Conductor, Aluminum-Clad Steel Reinforced

...

Construction:

  1. Core: Stranded standard strength aluminum-clad steel core
  2. Stranding: Hard-drawn aluminum (1350-H19) round wire shaped strands with 61.2% conductivity

Applications and Features:

ACSR/AW (Aluminum Conductor, Aluminum-Clad Steel Reinforced) is a concentrically stranded conductor consisting of one or more layers of hard-drawn aluminum (1350-H19) wires surrounding an aluminum-clad steel core. The aluminum strands provide efficient electrical conductivity, while the aluminum-clad steel core supplies strength, improved sag performance, and enhanced corrosion resistance. ACSR/AW is widely used for overhead transmission and distribution applications where a combination of ampacity, strength, corrosion protection, and long-term reliability is required.

Continuous operating temperature - 75°C
Emergency operating temperature - 100°C

Specifications:

  • ASTM B230 Standard Specification for Aluminum 1350-H19 Wire for Electrical Purposes
  • ASTM B502 Standard Specification for Aluminum-Clad Steel Core Wire for Use in Overhead Electrical Aluminum Conductors
  • ASTM B549 Standard Specification for Concentric-Lay-Stranded Aluminum Conductors, Aluminum-Clad Steel Reinforced (ACSR/AW)
  • Weights, Measurements, Electrical and Engineering Data

    Stock NumberCode WordConductor SizeStrandingCross-Sectional AreaLayers of AlDiameterWeightRated Breaking StrengthDC Resistance @ 20°C
    Individual StrandsAW CoreComplete Conductor
    AlTotalAlAWAlTotalAW2AW3
    AWG/kcmilAl/AWin²in²ininininlb/1000ftlb/1000ftlblbΩ/mile
    TBASWAN/AW46/10.03280.038310.08340.08340.08340.25038.9554.661,7801,8602.0583
    TBASWANATE/AW47/10.03280.041110.07720.10290.10290.25738.9562.662,2802,3602.0037
    TBASPARROW/AW26/10.05220.060910.10520.10520.10520.31661.9986.852,7602,8501.2937
    TBASPARATE/AW27/10.05220.065510.09740.12990.12990.32561.9999.993,5103,6401.2583
    TBAROBIN/AW16/10.06570.076710.11810.11810.11810.35478.02109.53,4503,5501.0277
    TBARAVEN/AW1/06/10.08300.096810.13270.13270.13270.39898.57138.04,2504,3800.8138
    TBAQUAIL/AW2/06/10.10450.121910.14890.14890.14890.447124.1173.85,1305,3000.6463
    TBAPIGEON/AW3/06/10.13170.153710.16720.16720.16720.502156.4219.36,3006,6200.5127
    TBAPENGUIN/AW4/06/10.16620.193910.18780.18780.18780.563197.4276.57,6908,3500.4063
    TBAMAGPIE/AW20.873/40.01640.03830.50.08340.0834---0.25019.4882.744,1004,4203.0091
    TBASHRIKE/AW33.1853/40.02610.06090.50.10520.1052---0.31631.00131.56,4906,8301.8917
    TBASNIPE/AW52.773/40.04140.09660.50.13260.1326---0.39849.16208.710,00010,5001.1926
    TBAALBATROSS/AW54.957/10.04320.054210.08860.11810.11810.29551.3082.732,9803,0801.5206
    TBASHOEBILL/AW57.503/40.04510.10530.50.13840.1384---0.41553.56227.510,60011,5001.0944
    TBALOON/AW66.543/40.05220.12190.50.14890.1489---0.44761.99263.311,90012,6000.9454
    TBAGROUSE/AW80.008/10.06280.084610.10000.16670.16670.36774.95137.24,8805,1901.0213
    TBAPETREL/AW101.812/70.07990.126510.09210.09210.27630.46195.82229.59,91010,4000.7526
    TBAMINORCA/AW110.812/70.08700.137810.09610.09610.28830.481104.3250.010,80011,3000.6911
    TBALEGHORN/AW134.612/70.10570.167410.10590.10590.31770.530126.8303.813,00013,6000.5689
    TBAGUINEA/AW159.012/70.12490.197710.11510.11510.34530.576149.8358.615,30016,0000.4815
    TBADOTTEREL/AW176.912/70.13890.219910.12140.12140.36420.607166.6399.016,90017,3000.4330
    TBADORKING/AW190.812/70.14990.237310.12610.12610.37830.631179.8430.518,30018,7000.4012
    TBAAUK/AW203.08/70.15940.202510.15930.08850.26550.584190.2313.810,90011,5000.4121
    TBABRAHMA/AW203.216/190.15960.302010.11270.09770.48850.714191.4600.727,10028,4000.3466
    TBACOCHIN/AW211.312/70.16600.262810.13270.13270.39810.664199.1476.819,80020,7000.3623
    TBAJAEGER/AW228.218/10.17920.189220.11260.11260.11260.563213.9242.55,9206,0200.3926
    TBAWAXWING/AW266.818/10.20940.221020.12170.12170.12170.609249.9283.06,8206,8800.3360
    TBAPARTRIDGE/AW266.826/70.20950.243620.10130.07880.23640.642251.2349.010,80011,3000.3258
    TBAJUNCO/AW266.830/70.20950.258420.09430.09430.28290.660251.9392.213,50013,9000.3193
    TBAOSTRICH/AW300.026/70.23550.273820.10740.08350.25050.680282.4392.312,10012,7000.2899
    TBAMERLIN/AW336.418/10.26420.278920.13670.13670.13670.684315.3357.38,5408,6800.2663
    TBAWIDGEON/AW336.424/70.26420.298420.11840.07890.23670.710316.8414.912,00012,5000.2612
    TBALINNET/AW336.426/70.26400.307020.11370.08840.26520.720316.6440.013,50014,1000.2586
    TBAORIOLE/AW336.430/70.26420.325920.10590.10590.31770.741317.6494.616,70017,3000.2532
    TBACHICKADEE/AW397.518/10.31220.329520.14860.14860.14860.743372.6422.09,7809,9400.2254
    TBABRANT/AW397.524/70.31220.352720.12870.08580.25740.772374.4490.614,10014,6000.2210
    TBAIBIS/AW397.526/70.31200.362820.12360.09610.28830.783374.2519.915,80016,3000.2188
    TBALARK/AW397.530/70.31210.384920.11510.11510.34530.806375.2584.019,60020,3000.2144
    TBAPELICAN/AW477.018/10.37470.395520.16280.16280.16280.814447.2506.611,50011,8000.1878
    TBATOUCAN/AW477.022/70.37440.411220.14720.08180.24540.834449.0554.614,70015,2000.1862
    TBAFLICKER/AW477.024/70.37470.423320.14100.09400.28200.846449.4588.816,70017,2000.1841
    TBAHAWK/AW477.026/70.37440.435420.13540.10530.31590.858449.0624.018,90019,5000.1823
    TBAHEN/AW477.030/70.37470.462120.12610.12610.37830.883450.5701.223,40023,8000.1785
    TBAHERON/AW500.030/70.39270.484320.12910.12910.38730.904472.1734.924,10025,0000.1704
    TBAOSPREY/AW556.518/10.43690.461220.17580.17580.17580.879521.4590.813,20013,7000.1610
    TBASAPSUCKER/AW556.522/70.43680.479720.15900.08830.26490.901523.8646.917,00017,6000.1596
    TBAPARAKEET/AW556.524/70.43720.493820.15230.10150.30450.914524.3686.719,30019,8000.1578
    TBADOVE/AW556.526/70.43710.508320.14630.11380.34140.927524.2728.421,90022,6000.1562
    TBAEAGLE/AW556.530/70.43710.539120.13620.13620.40860.953525.5818.126,80027,8000.1531
    TBAPEACOCK/AW605.024/70.47530.537020.15880.10590.31770.953570.0747.021,00021,6000.1452
    TBASQUAB/AW605.026/70.47490.552220.15250.11860.35580.966569.5791.223,60024,3000.1437
    TBAWOOD DUCK/AW605.030/70.47510.586020.14200.14200.42600.994571.2889.328,40028,9000.1408
    TBATEAL/AW605.030/190.47510.583420.14200.08520.42600.994571.2882.528,50030,0000.1411
    TBADUCK/AW605.054/70.47470.536230.10580.10580.31740.952569.3745.721,60022,2000.1454
    TBAKINGBIRD/AW636.018/10.49970.527520.18800.18800.18800.940596.3675.715,00015,7000.1408
    TBASWIFT/AW636.036/10.49940.513330.13290.13290.13290.930596.0635.713,60013,8000.1422
    TBATURACOS/AW636.020/70.49940.533920.17830.07920.23760.951598.9697.916,90017,4000.1409
    TBAGOLDFINCH/AW636.022/70.49940.548420.17000.09440.28320.963598.9739.519,40019,8000.1396
    TBAROOK/AW636.024/70.49960.564320.16280.10850.32550.977599.1784.722,00022,6000.1381
    TBAGROSBEAK/AW636.026/70.49950.580820.15640.12160.36480.990599.0832.224,80025,2000.1367
    TBASCOTER/AW636.030/70.49950.616020.14560.14560.43681.019600.5934.729,30030,4000.1339
    TBAEGRET/AW636.030/190.49950.613520.14560.08740.43701.019600.5928.229,90031,5000.1342
    TBAGOOSE/AW636.054/70.49930.564030.10850.10850.32550.977598.8784.422,70023,3000.1382
    TBAFLAMINGO/AW666.624/70.52380.591720.16670.11110.33331.000628.2823.023,10023,7000.1317
    TBAGANNET/AW666.626/70.52340.608620.16010.12450.37351.014627.7872.126,00026,4000.1304
    TBAGULL/AW666.654/70.52350.591430.11110.11110.33331.000627.8822.623,50024,2000.1318
    TBASTILT/AW715.524/70.56220.635020.17270.11510.34531.036674.2883.024,80025,5000.1227
    TBASTARLING/AW715.526/70.56200.653520.16590.12900.38701.051674.0936.527,50028,4000.1215
    TBAREDWING/AW715.530/190.56170.689720.15440.09260.46301.081675.3104333,40034,6000.1193
    TBACROW/AW715.554/70.56190.634730.11510.11510.34531.036673.9882.725,30026,0000.1228
    TBACOOT/AW795.036/10.62440.641730.14860.14860.14861.040745.2794.616,60016,8000.1137
    TBATURBIT/AW795.020/70.62460.667820.19940.08860.26581.063749.1873.021,20021,8000.1127
    TBAPUFFIN/AW795.022/70.62440.685720.19010.10560.31681.077748.8924.624,20024,8000.1116
    TBACUCKOO/AW795.024/70.62440.705320.18200.12130.36391.092748.8980.927,50027,9000.1105
    TBADRAKE/AW795.026/70.62470.726420.17490.13600.40801.108749.2104130,50031,5000.1093
    TBASKIMMER/AW795.030/70.62450.770220.16280.16280.48841.140750.8116935,60037,7000.1071
    TBAMALLARD/AW795.030/190.62450.766920.16280.09770.48851.140750.8116037,10038,4000.1073
    TBATERN/AW795.045/70.62420.667430.13290.08860.26581.063748.6872.521,50022,1000.1128
    TBACONDOR/AW795.054/70.62400.704930.12130.12130.36391.092748.3980.427,80028,2000.1106
    TBARUDDY/AW900.045/70.70660.755530.14140.09430.28291.131847.4987.724,00024,4000.0996
    TBACANARY/AW900.054/70.70690.798530.12910.12910.38731.162847.7111131,00031,9000.0976
    TBACORNCRAKE/AW954.020/70.74920.801020.21840.09710.29131.165898.5104725,10025,6000.0939
    TBAREDBIRD/AW954.024/70.74950.846620.19940.13290.39871.196898.8117732,60033,5000.0921
    TBAMERGANSER/AW954.030/70.74910.923920.17830.17830.53491.248900.5140241,90045,2000.0893
    TBACANVASBACK/AW954.030/190.74910.919920.17830.10700.53501.248900.5139144,50046,1000.0895
    TBAPHOENIX/AW954.042/70.74910.787630.15070.08370.25111.155898.4100922,80023,4000.0945
    TBARAIL/AW954.045/70.74920.801030.14560.09710.29131.165898.5104725,40025,9000.0939
    TBATOWHEE/AW954.048/70.74950.815730.14100.10970.32911.175898.8108927,80028,5000.0933
    TBACARDINAL/AW954.054/70.74910.846230.13290.13290.39871.196898.4117732,90033,8000.0921
    TBASNOWBIRD/AW1033.542/70.81210.853930.15690.08720.26161.203973.9109424,80025,4000.0872
    TBAORTOLAN/AW1033.545/70.81120.867330.15150.10100.30301.212972.8113427,10027,7000.0868
    TBAWHOOPER/AW1033.548/70.81130.882930.14670.11410.34231.223973.0117830,10030,8000.0862
    TBACURLEW/AW1033.554/70.81120.916430.13830.13830.41491.245972.8127535,10036,6000.0851
    TBAAVOCET/AW1113.042/70.87430.919230.16280.09040.27121.2481049117826,60027,1000.0810
    TBABLUEJAY/AW1113.045/70.87450.935030.15730.10490.31471.2591049122329,30029,8000.0805
    TBABULLFINCH/AW1113.048/70.87440.951630.15230.11850.35551.2691049127132,10032,8000.0800
    TBAFINCH/AW1113.054/190.87460.985530.14360.08620.43101.2931054137337,50039,1000.0793
    TBAOXBIRD/AW1192.542/70.93660.984830.16850.09360.28081.2921123126128,50029,0000.0756
    TBABUNTING/AW1192.545/70.93671.001430.16280.10850.32551.3021123130931,30032,0000.0751
    TBACORMORANT/AW1192.548/70.93641.019030.15760.12260.36781.3131123136034,30034,7000.0747
    TBAGRACKLE/AW1192.554/190.93651.055230.14860.08920.44601.3381129147040,20041,9000.0741
    TBASCISSORTAIL/AW1272.042/70.99871.050130.17400.09670.29011.3341198134530,40030,9000.0709
    TBABITTERN/AW1272.045/70.99871.067830.16810.11210.33631.3451198139633,40034,1000.0705
    TBADIVER/AW1272.048/70.99921.087330.16280.12660.37981.3571198145136,60037,0000.0700
    TBAPHEASANT/AW1272.054/190.99931.125930.15350.09210.46051.3821204156842,40043,6000.0694
    TBARINGDOVE/AW1351.542/71.06171.116330.17940.09970.29911.3761273143032,40032,9000.0667
    TBADIPPER/AW1351.545/71.06141.134730.17330.11550.34651.3861273148335,50036,2000.0663
    TBAMARTIN/AW1351.554/191.06141.195830.15820.09490.47451.4241279166545,10046,3000.0654
    TBAPOPINJAY/AW1431.042/71.12411.182030.18460.10260.30781.4151348151434,30034,8000.0630
    TBABOBOLINK/AW1431.045/71.12361.201330.17830.11890.35671.4271347157037,60038,3000.0626
    TBAWAGTAIL/AW1431.048/71.12441.223630.17270.13430.40291.4391348163340,70041,7000.0622
    TBAPLOVER/AW1431.054/191.12411.266530.16280.09770.48851.4651355176447,70049,1000.0617
    TBANUTHATCH/AW1510.545/71.18621.268230.18320.12210.36631.4661423165839,70040,1000.0593
    TBAPARROT/AW1510.554/191.18561.335730.16720.10030.50151.5051429186050,30051,7000.0585
    TBARATITE/AW1590.042/71.24921.313430.19460.10810.32431.4921498168238,10038,7000.0567
    TBALAPWING/AW1590.045/71.24921.335530.18800.12530.37591.5041498174641,80042,2000.0563
    TBAHORNBILL/AW1590.048/71.24871.358930.18200.14160.42481.5171498181444,70045,3000.0560
    TBAFALCON/AW1590.054/191.24891.407230.17160.10300.51501.5451505196053,00054,5000.0556
    TBACHUKAR/AW1780.084/191.39861.512640.14560.08740.43701.6021685201349,40051,0000.0504
    TBAWOODPECKER/AW1843.072/71.44761.510240.16000.10670.32011.6001745192541,80042,4000.0493
    TBASEAHAWK/AW1869.068/71.46811.514740.16580.09210.27631.6031769190339,50040,0000.0488
    TBAMOCKINGBIRD/AW2034.572/71.59791.667040.16810.11210.33631.6811926212446,10046,8000.0446
    TBABLUEBIRD/AW2156.084/191.69311.830940.16020.09610.48051.7622040243659,00060,3000.0416
    TBAKIWI/AW2167.072/71.70221.775840.17350.11570.34711.7352051226249,10049,8000.0419
    TBATHRASHER/AW2312.076/191.81551.914440.17440.08140.40701.8022188247255,30056,7000.0391
    TBAJOREE/AW2515.076/191.97502.082640.18190.08490.42451.8802380268960,20061,7000.0360

    Revision: 1.000.010