SPEC 70002

600V ROYAL® SOOW Power Cord Non-UL/CSA with Black Jacket 90°C. MSHA Approved

600 Volt, 90°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation and Heat, Moisture and Oil Resistant Flexible CPE Jacket, Non UL / Non CSA.

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant EPDM
  3. Filler:Waxed paper fillers
  4. Jacket:Black CPE (Other colors available upon request)

Applications and Features:

Southwire Royal® Non UL/Non CSA SOOW cord is designed for use with industrial equipment, heavy tools, battery chargers, portable lights and power extensions, suitable for outdoor applications. The cable is rated -40°C to 90°C, sunlight, water, oil, and weather resistant. Southwire Type SOOW Flexible Cords are permitted for use as specified by Article 400 and related articles of the 2014 National Electrical Code.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • MSHA flame test - P07-KA070018-1MSHA
  • RoHS-3 Complies with European Directive 2015/863
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • Federal Specification J-C-580B
  • Sample Print Legend:

    SOUTHWIRE® ROYAL® CORD X/C X AWG (X.XXmm2) SOOW 600V -40C TO 90C

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacityInsul. ColorJacket Color
    AWG/KcmilNo.No.milmilinchlb/1000ftAmp
    5699728222208213345750.61521840BK,WEBK
    5580888223208313345750.64528935BK,WE,GNBK
    5580938224208413345750.71137728BK,WE,RD,GNBK
    55810582247085133451050.83449228BK,WE,RD,GN,OEBK
    56997382222162133451000.72133555BK,WEBK
    5580928223216313345900.72641845BK,WE,GNBK
    5580918224216413345950.80354936BK,WE,RD,GNBK
    55816182252165133451100.93770236BK,WE,RD,GN,OEBK
    5581378223224313345950.82558960BK,WE,GNBK
    55809082242244133451000.95076148BK,WE,RD,GNBK
    56997582255245133451551.155112148BK,WE,RD,GN,OEBK
    55813682232323168451151.090102880BK,WE,GNBK
    55808982242324168451301.290132764BK,WE,RD,GNBK
    56997682255325168451201.373167164BK,WE,RD,GN,OEBK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *Insul. ColorJacket Color
    AWG/KcmilNo.No.mmmmmmkg/kmAmp
    569972822220821331.141.9115.6232440BK,WEBK
    558088822320831331.141.9116.3843035BK,WE,GNBK
    558093822420841331.141.9118.0656128BK,WE,RD,GNBK
    558105822470851331.142.6721.1873228BK,WE,RD,GN,OEBK
    569973822221621331.142.5418.3149955BK,WEBK
    558092822321631331.142.2918.4462245BK,WE,GNBK
    558091822421641331.142.4120.4081736BK,WE,RD,GNBK
    558161822521651331.142.7923.80104536BK,WE,RD,GN,OEBK
    558137822322431331.142.4120.9687760BK,WE,GNBK
    558090822422441331.142.5424.13113248BK,WE,RD,GNBK
    569975822552451331.143.9429.34166848BK,WE,RD,GN,OEBK
    558136822323231681.142.9227.69153080BK,WE,GNBK
    558089822423241681.143.3032.77197564BK,WE,RD,GNBK
    569976822553251681.143.0534.87248764BK,WE,RD,GN,OEBK
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.

    Revision: 1.000.002

    Updated On: April 22, 2025, 1:40 p.m. UTC