SPEC 85040

Multi-Conductor CU 600 V FR-XLPE Shielded Thermoplastic LSZH-TP Jacket Control Cable Color Method 1 Table 1

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE)
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Shielding:5 mil copper Helically-Applied Tape shield
  6. Rip Cord:Rip cord for ease of jacket removal
  7. Overall Jacket:Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE CDRS SHIELDED 90C LSZH JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS SHIELDED 90C LSZH JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    16 AWG
    626227161270.05625600.5891302414.1815.0370.0337.1-9
    14 AWG
    TBA14270.07030450.34926682.6303.2880.0361.41515
    TBA14370.07030450.37038872.6303.2880.0361.51515
    TBA14470.07030450.403511092.6303.2880.0361.61515
    TBA14570.07030450.440641322.6303.2880.0361.81515
    TBA14670.07030450.479771552.6303.2880.0361.91515
    TBA14770.07030450.479901712.6303.2880.0361.91515
    TBA14870.07030450.5191021952.6303.2880.0362.11515
    TBA14970.07030600.5881152362.6303.2880.0362.41515
    TBA141070.07030600.6381282662.6303.2880.0362.61112
    TBA141270.07030600.6591543032.6303.2880.0362.61112
    TBA141570.07030600.7301923712.6303.2880.0362.91112
    TBA141970.07030600.7682434462.6303.2880.0363.11112
    TBA142070.07030600.8082564752.6303.2880.0363.21112
    TBA142570.07030800.9373206192.6303.2880.0363.7911
    TBA143070.07030800.9913847192.6303.2880.0364.0911
    TBA143770.07030801.0674748622.6303.2880.0365.3810
    12 AWG
    TBA12270.08830450.38441901.6622.0020.0541.52020
    TBA12370.08830450.408611181.6622.0020.0541.62020
    TBA12470.08830450.4831091811.6622.0020.0545.82024
    TBA12570.08830450.4871021811.6622.0020.0541.92020
    TBA12670.08830450.5321222141.6622.0020.0542.12020
    66093512770.08830600.6031762971.6622.0020.0547.21721
    TBA12870.08830600.6071632881.6622.0020.0542.41720
    TBA12970.08830600.6511833241.6622.0020.0542.61720
    TBA121070.08830600.7092043651.6622.0020.0542.81215
    TBA121570.08830600.8133055161.6622.0020.0543.31215
    TBA121970.08830800.8963876571.6622.0020.0543.61215
    TBA122070.08830800.9424076991.6622.0020.0543.81215
    TBA122570.08830801.0435098601.6622.0020.0545.21113
    TBA123070.08830801.10461110051.6622.0020.0545.51113
    TBA123770.08830801.19175312111.6622.0020.0546.01012
    10 AWG
    62622410270.11330450.472901521.0401.2530.0505.71720
    TBA10370.11330450.4911292001.0401.2530.05053540
    62622310470.11330600.5781592641.0401.2530.0506.91720
    TBA10570.11330600.5811622731.0401.2530.0502.32830
    TBA10670.11330600.6321943231.0401.2530.0502.52830
    TBA10770.11330600.6322273581.0401.2530.0502.52428
    TBA10870.11330600.6852594101.0401.2530.0502.72428
    TBA10970.11330600.7362914611.0401.2530.0502.92428
    TBA101070.11330800.8033845191.0401.2530.050121720
    626222101270.11330800.8994386721.0401.2530.05010.81720
    TBA101570.11330800.9644867771.0401.2530.0503.91720
    TBA101970.11330801.0146159411.0401.2530.0505.11720
    TBA102070.11330801.06764810011.0401.2530.0505.31720
    TBA102570.11330801.18481012361.0401.2530.0505.91518
    TBA103070.11330801.25497114501.0401.2530.0506.31518
    TBA103770.11330801.355119817551.0401.2530.0506.81416
    6 AWG
    6262406270.17745600.6942033340.4110.4950.0518.36575
    62623861270.17745801.324107715640.4110.4950.0516.63237
    2 AWG
    6255832270.28245800.9344656980.1620.1950.0456.5115130
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.

    Revision: 1.000.004

    Updated On: July 3, 2024, 10:14 p.m. UTC