SPEC 85012

Multi-Conductor CU 600 V PE/PVC Insulation PVC Jacket Power Cable Color Method 1 Table 1

Power Cable 600 Volt Copper Conductors, Polyethylene and Polyvinyl Chloride (PE/PVC) Insulation Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Polyethylene (PE) and Polyvinyl Chloride (PVC)
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C for normal operation in wet and dry locations, 90°C for emergency overload, and 150°C for short circuit conditions.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA CSA marking is available upon request
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    Non UL Listed
    SOUTHWIRE XX AWG X/C PE/PVC CDRS 75C PVC JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    60678618770.04615450.39835916.6698.2770.0361.6-10BK
    606787181270.04615450.514611436.6698.2770.0362.1-7BK
    16 AWG
    61912716270.05720450.3416574.1815.1890.0331.4-18BK
    61912816470.05720450.3932844.1815.1890.0331.6-14BK
    66906416570.05720450.42540994.1815.1890.0331.7-14BK
    671351161270.05720600.634972164.1815.1890.0332.5-9BK
    14 AWG
    62064614470.07120450.424511102.6313.2650.0581.71620BK
    60677614770.07120450.494901672.6313.2650.05821418BK
    606777141270.07120600.6921542982.6313.2650.0582.81012BK
    12 AWG
    616691!12270.08920450.40441891.6622.0630.0541.62530BK
    61917012370.08920450.429611211.6622.0630.0541.72530BK
    61685612470.08920450.468811531.6622.0630.0541.92024BK
    62209012470.08920450.468811481.6622.0630.0541.92024BK
    61741612570.08920600.5441021921.6622.0630.0542.22024BK
    61917312670.08920600.5891222271.6622.0630.0542.42024BK
    60689612770.08920600.5891432541.6622.0630.0542.41821BK
    61742112770.08920600.5891432531.6622.0630.0542.41821BK
    61938212970.08920600.671833141.6622.0630.0542.71821BK
    617420!121270.08920600.7672444031.6622.0630.0543.11215BK
    619383121270.08920600.7672444091.6622.0630.0543.11215BK
    619993$1212190.0920600.7712454091.6622.0630.0543.11215BK
    10 AWG
    60677810270.11320450.452651271.041.2910.051.83540BK
    61871910270.11320450.452651231.041.2910.051.83540BK
    61911710370.11320450.481971701.041.2910.051.93540BK
    60677910370.11320450.481971701.041.2910.051.93540BK
    61673310470.113200.5521292251.041.2910.052.22832BK
    61872010470.11320600.5581292321.041.2910.052.22832BK
    61930110470.11320600.5581292321.041.2910.052.22832BK
    60678110570.11320600.6081622791.041.2910.052.42832BK
    61917810770.11320600.6612273571.041.2910.052.62428BK
    61917910870.11320600.7162593991.041.2910.052.92428BK
    60678210970.11320600.7692914551.041.2910.053.12428BK
    619181101070.11320800.883245351.041.2910.053.51820BK
    619119101270.11320800.9063886341.041.2910.053.61820BK
    606783101270.11320800.9093886201.041.2910.053.61820BK
    618911$1012190.11720800.8883885991.041.2910.053.61820BK
    61734792190.13120450.48771380.8251.0240.0511.9BK
    61734994190.13120600.5911542530.8251.0240.0512.4BK
    61735098190.13120600.7633094570.8251.0240.0513.1BK
    8 AWG
    6191218270.14245600.6661032280.6530.810.0522.75055BK
    6067848270.14245600.6661032490.6530.810.0522.75055BK
    6184268370.14245600.7091543210.6530.810.0522.85055BK
    6202888570.14245800.8962574980.6530.810.0523.64044BK
    66150284190.14345600.782063840.6530.810.0523.14044BK
    6 AWG
    6067756270.17845600.7781643310.4110.510.0513.16575BK
    6067636370.17845800.8722464900.4110.510.0513.56575BK
    4 AWG
    6191254270.22545800.9282604920.2580.320.0483.78595BK
    6191324370.22545800.9883907000.2580.320.04848595BK
    2 AWG
    6191332270.28345801.014146690.1620.2010.0455115130BK
    6191342370.28345801.0866219370.1620.2010.0455.4115130BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    $ 19 strand combination unilay conductor per ASTM B787
    ! No rip cord
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.003