SPEC 83028

Quad Parallel 600 Volt USE-2 Underground Service Entrance

...

Construction:

  1. Conductor:Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Neutral:Cross Linked Polyethylene (XLPE) with three Yellow Extruded Stripes (YES)

For information about our Cable-Rejuvenation Services please visit us at:  Cable-Rejuvenation Services
You can email us at: Cable-Rejuvenation Services

Applications and Features:

Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum, insulated with cross-linked polyethylene. Neutrals are identified by three yellow extruded stripes. Cables with “YES” neutrals have sequential footage markers. Conductors are durably surface printed for identification. Three-phase conductors and one neutral conductor are quad paralleled. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL listed as USE-2 per UL 854 Service-Entrance Cables.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • UL 854 Service Entrance Cable
  • ICEA S-105-692 Standard For 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeNeutral StrandNeutral Insul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/KcmilNo.milinchlb/1000ft
    TBAAims470.225600.34546600.837304
    TBAGoshen270.282600.40226600.975418
    TBALinfield270.282600.40246600.975441
    TBAKellogg1/0190.361800.5211/07801.263683
    TBACerritos1/0190.361800.52126601.263719
    TBAItasca2/0190.405800.5652/011801.369824
    TBAAvila2/0190.405800.56517801.369869
    TBACarlow3/0190.456800.6163/015801.4931000
    TBALaney3/0190.456800.6161/07801.4931061
    TBAHiwassee4/0190.512800.6724/017801.6281216
    TBAAlfred4/0190.512800.6722/011801.6281288
    TBAJoliet350370.661950.8514/017802.0611961
    TBASullins500370.789950.97930018952.3712680
    TBAWilkes750610.9681101.18835024952.8773954
    All dimensions are nominal and subject to normal manufacturing tolerances
    Notes:
    1. The actual number of strands may differ for single input wire per ASTM B901
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity in Duct 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    Aims43.38010.4240.5110.04852 / 60
    Goshen23.912740.2660.3200.04572 / 80
    Linfield23.912740.2660.3200.04572 / 80
    Kellogg1/06.320270.1670.2010.04496 / 108
    Cerritos1/06.320270.1670.2010.04496 / 108
    Itasca2/06.825550.1330.1590.043108 / 120
    Avila2/06.825550.1330.1590.043108 / 120
    Carlow3/07.532210.1050.1260.042124 / 140
    Laney3/07.532210.1050.1260.042124 / 140
    Hiwassee4/08.140620.0840.1000.041144 / 164
    Alfred4/08.140620.0840.1000.041144 / 164
    Joliet35012.467200.0500.0620.040200 / 224
    Sullins50014.296000.0350.0440.039248 / 280
    Wilkes75017.3144000.0240.0310.038308 / 348
    Notes:
    1. Inductive reactance assumes cables are cradled in conduit, and the neutral is carrying no current.
    2. Triple parallel inductive reactance calculation assumes the phase conductors are adjacent to one another.
    3. Conductors assumed to be reverse lay stranded, compressed construction.
    4. Phase spacing assumes cables are touching.
    5. Resistances shown are for the Phase conductors only.
    6. Ampacity based on 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor.

    Revision: 1.000.000

    Updated On: July 3, 2024, 10:14 p.m. UTC