SPEC 83350

Transformer Riser Wire, Protected Ground Wire (PGW), Cathodic Protection (CP) Cables, LLDPE

Black Polyethylene Covered. Solid or Stranded Soft Drawn Copper Conductor

...

Construction:

  1. Conductor:Conductors are solid or stranded compressed copper
  2. Covering:Black Linear Low Density Polyethylene (LLDPE) also known as High Molecular Weight Polyethylene (HMWPE)

Applications and Features:

Used as covered grounding conductors, protected ground wires (PGW), cathodic protection (CP) cables, or on transformers as connection between line conductor and transformer primary bushing in applications where protection from momentary contact from wildlife is needed. Although not treated as an insulation, the thermoplastic polyethylene covering does provide an increased level of protection from momentary grounded contacts caused by wildlife, excessive wind and tree limbs or other grounded objects in the proximity of the high voltage lead. May be used on distribution system voltages up to 35kV line-to-line.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ICEA S-70-547 Weather Resistant Polyethylene Covers Conductors
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. StrandsDiameter Over ConductorInner Layer ThicknessApprox. ODApprox. WeightDC ResistanceAllowable Ampacity In Air 75°C†Allowable Ampacity In Air 90°C†
    AWG/Kcmil#inchmilinchlb/1000ftΩ/1000ftAmpAmp
    1510358SOLID0.1291100.348830.6537080
    207076870.1421100.362870.6537080
    6436506SOLID0.162450.252910.41195105
    1427526SOLID0.1621100.3821170.41195105
    614562670.178800.3381080.41195105
    368646670.1781100.3981220.41195105
    1427454SOLID0.2041100.4241700.258125140
    257998470.225600.3451520.258125140
    240093470.2251100.4451770.258125140
    661857470.2251250.4751860.258125140
    1092072SOLID0.258450.3482180.162170190
    6214632SOLID0.2581100.4782520.162170190
    109306270.283450.3732260.162170190
    109298270.283450.3732260.162170190
    109314270.283450.3732260.162170190
    616506270.283800.4432440.162170190
    403477270.2831100.5032620.162170190
    661821270.2831100.5032620.162170190
    109348870.362600.477361
    1094394/070.512600.6267030.051360405
    6068644/0190.5121100.7327440.051360405
    505461500370.7891201.02916890.021620700
    606862500370.7891201.02916890.021620700
    109579750610.968801.12824300.014785885
    All dimensions are nominal and subject to normal manufacturing tolerances
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.001

    Updated On: Dec. 31, 2024, 11:09 p.m. UTC