SPEC 83233

Triplex XLPE Service Drop. Reduced ACSR Neutral - Messenger

Aluminum Conductors With Crosslinked Polyethylene Insulation.

...

Construction:

  1. Conductor:Conductors are stranded, compressed 1350-H19 aluminum
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Messenger:ACSR Neutral

Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B400 Standard Specification for Compact Round Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • ICEA S-76-474 Standard for Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulation Rated 600V
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeNeutral StrandApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/KcmilNo.inchlb/1000ft
    TBAScallop4Solid0.204300.26466/10.26473
    104927Strombus470.225300.28566/10.679148
    104935Cockle270.282450.37246/10.806225
    104950Ranella1/090.361600.48126/11.019361
    104943Janthina1/070.361600.48126/11.031362
    104976Clio2/0110.405600.52516/11.112445
    104968Cavolinia2/070.405600.52516/11.126446
    104984Aega3/0170.456600.5761/06/11.216547
    102897!Aega3/0170.456600.5761/06/11.216547
    104992Cerapus4/0180.512600.6322/06/11.334277
    227314Cowry336.4190.646600.7664/06/11.7411090
    All dimensions are nominal and subject to normal manufacturing tolerances
    1. The actual number of strands may differ for single input wire per ASTM B901
    ! Linear Low Density Polyethylene (LLDPE) instead of XLPE insulation
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeNeutral Rated Breaking StrengthDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzGMRAllowable Ampacity In Air 75/90°C
    AWG/KcmillbΩ/1000ftΩ/1000ftΩ/1000ftftAmp
    Scallop411900.2580.3100.0480.007100 / 115
    Strombus411900.4240.5110.0480.007100 / 115
    Cockle218600.2660.3200.0450.008135 / 150
    Ranella1/028530.1670.2010.0440.011180 / 205
    Janthina1/028500.1670.2010.0440.011180 / 205
    Clio2/035500.1330.1590.0430.013210 / 235
    Cavolinia2/035500.1330.1590.0430.013210 / 235
    Aega3/043800.1050.1260.0420.014240 / 270
    Aega3/043800.1050.1260.0420.014240 / 270
    Cerapus4/053100.0840.1000.0410.016280 / 315
    Cowry336.483500.0510.0620.0410.021395 / 445
    Notes:
    1. DC resistances include a 1% length factor for plexing.
    2. Inductive reactance assumes the neutral is carrying current.
    3. Phase conductors assumed to be reverse lay stranded, compressed construction.
    4. Phase spacing assumes cables are touching.
    5. Resistances shown are for the phase conductor only.
    6. Ampacity based on conductor temperature of 90°; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

    Neutral Code Word

    Size-StrandsCode WordOD (inches)
    #4Swan0.250
    #2Sparrow0.316
    1/0Raven0.398
    2/0Quail0.447
    3/0Pigeon0.502
    4/0Penguin0.684
    336.4Merlin0.563

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:09 p.m. UTC