SPEC 81122

15kV AL 100% EPR (EAM) One-Third Neutral LLDPE

Single Conductor, 175 Mils Ethylene Propylene Rubber (EPR) / Ethylene Alkene Copolymer (EAM), 100% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed Aluminum ASTM B231 1350 ¾ hard H16/H26 ( Non Moisture Blocked Optional )
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:175 Mils Ethylene Propylene Rubber (EPR) / Ethylene Alkene Copolymer (EAM) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes; PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 15kV cables are suited for use in wet and dry areas, conduits, ducts, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation. 140°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Rural Utility Standard RUS 1728F-U1 or 1728.204 (Electric standards and specifications for materials and construction)
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA 68.5: -40ºC and MV 90ºC optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 15000 VOLTS EPR INSULATION 175 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    TBA2 (Solid)0.2570.6451750.7356x140.438500.9634257.7398
    6294592 (7)0.2820.6631750.7536x140.438500.9814617.8398
    TBA1 (Solid)0.2890.6771750.7676x140.438500.9954568.0502
    TBA1 (19)0.3220.7101750.8006x140.438501.0284728.2502
    TBA1/0 (Solid)0.3240.7121750.8026x140.438501.0304948.2633
    TBA1/0 (19)0.3510.7391750.8296x140.438501.0575088.5633
    TBA2/0 (19)0.3950.7831750.8737x140.375501.1015678.8798
    TBA3/0 (19)0.4430.8311750.9219x140.292501.1496499.21006
    6294664/0 (19)0.4980.8781750.96811x140.239501.1967799.61269
    TBA250 (37)0.5580.9541751.04413x140.202501.27284210.21500
    TBA350 (37)0.6611.0571751.16718x140.146501.395107311.22100
    622454500 (37)0.7891.1851751.29525x140.105501.523137112.23000
    622583?750 (61)0.9681.3681751.47824x120.069751.793205114.34500
    6218281000 (61)1.1171.5171751.62720x100.052751.984259715.96000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    † Solid Black Jacket
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence ImpedancePositive Sequence ImpedanceShort Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (Solid)0.1620.2040.0400.0520.21215.80.257 + j1.2810.204 + j0.5712092120150
    2 (7)0.2660.3360.0370.0500.22817.00.389 + j1.2240.336 + j0.5142092120150
    1 (Solid)0.1290.1620.0370.0500.22817.00.215 + j1.2110.162 + j0.5022092140175
    1 (19)0.2110.2660.0350.0480.24418.20.319 + j1.1520.266 + j0.4452092140175
    1/0 (Solid)0.1020.1280.0350.0480.24618.30.181 + j1.1470.128 + j0.4412092155195
    1/0 (19)0.1670.2110.0330.0470.25919.30.264 + j1.1070.211 + j0.4032092155195
    2/0 (19)0.1330.1670.0300.0450.28020.90.221 + j1.0560.167 + j0.3532441180220
    3/0 (19)0.1050.1320.0280.0440.30322.60.186 + j1.0120.132 + j0.3103138200250
    4/0 (19)0.0840.1050.0250.0420.33625.00.159 + j0.9700.105 + j0.2703836235285
    250 (37)0.0710.0900.0230.0410.36327.00.144 + j0.9330.090 + j0.2364533256309
    350 (37)0.0500.0650.0200.0390.41230.70.119 + j0.8840.065 + j0.1936277310370
    500 (37)0.0350.0460.0180.0370.47435.30.100 + j0.840.046 + j0.1558626370445
    750 (61)0.0240.0330.0150.0360.57342.70.087 + j0.7940.033 + j0.12013298460525
    1000 (61)0.0180.0260.0130.0350.64548.00.080 + j0.7670.026 + j0.10017615520575
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    TBA2 (Solid)6.5316.384.4418.676x141.441.2724.46632195.581771
    6294592 (7)7.1616.844.4419.136x141.441.2724.92686198.121771
    TBA1 (Solid)7.3417.204.4419.486x141.441.2725.27679203.202234
    TBA1 (19)8.1818.034.4420.326x141.441.2726.11702208.282234
    TBA1/0 (Solid)8.2318.084.4420.376x141.441.2726.16735208.282817
    TBA1/0 (19)8.9218.774.4421.066x141.441.2726.85756215.902817
    TBA2/0 (19)10.0319.894.4422.177x141.231.2727.97844223.523551
    TBA3/0 (19)11.2521.114.4423.399x140.961.2729.18966233.684477
    6294664/0 (19)12.6522.304.4424.5911x140.781.2730.381159243.845647
    TBA250 (37)14.1724.234.4426.5213x140.661.2732.311253259.086675
    TBA350 (37)16.7926.854.4429.6418x140.481.2735.431597284.489345
    622454500 (37)20.0430.104.4432.8925x140.341.2738.682040309.8813350
    622583?750 (61)24.5934.754.4437.5424x120.231.9145.543052363.2220025
    6218281000 (61)28.3738.534.4441.3320x100.171.9150.393865403.8626700
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    † Solid Black Jacket
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (Solid)0.53150.670.01220.17060.69651.83730.257 + j1.2810.204 + j0.5712092120150
    2 (7)0.87271.100.01130.16400.74855.77430.389 + j1.2240.336 + j0.5142092120150
    1 (Solid)0.42320.530.01130.16400.74855.77430.215 + j1.2110.162 + j0.5022092140175
    1 (19)0.69230.870.01070.15750.80159.71130.319 + j1.1520.266 + j0.4452092140175
    1/0 (Solid)0.33460.420.01070.15750.80760.03940.181 + j1.1470.128 + j0.4412092155195
    1/0 (19)0.54790.690.01010.15420.85063.32020.264 + j1.1070.211 + j0.4032092155195
    2/0 (19)0.43640.550.00910.14760.91968.56960.221 + j1.0560.167 + j0.3532441180220
    3/0 (19)0.34450.430.00850.14440.99474.14700.186 + j1.0120.132 + j0.3103138200250
    4/0 (19)0.27560.340.00760.13781.10282.02100.159 + j0.9700.105 + j0.2703836235285
    250 (37)0.23290.300.00700.13451.19188.58270.144 + j0.9330.090 + j0.2364533256309
    350 (37)0.16400.210.00610.12801.352100.72180.119 + j0.8840.065 + j0.1936277310370
    500 (37)0.11480.150.00550.12141.555115.81360.100 + j0.840.046 + j0.1558626370445
    750 (61)0.07870.110.00460.11811.880140.09190.087 + j0.7940.033 + j0.12013298460525
    1000 (61)0.05910.090.00400.11482.116157.48030.080 + j0.7670.026 + j0.10017615520575
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.

    Revision: 1.000.004

    Updated On: Aug. 10, 2025, 11:33 p.m. UTC

    Concentric Neutral Calculator
    QR Code