SPEC 46302
CU Compressed 15kV NLEPR Insulation 133% IL Black SIM-PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial
Type MV-105 Single Conductor Copper, 220 Mil No Lead Ethylene Propylene Rubber (NL-EPR) Lead-Free EAM 133% Insulation Level, Tape Shield, SIMpull Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and B8 (tinned copper optional per ASTM B33)
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:15kV, 133% insulation level, 220 mil No Lead Ethylene Propylene Rubber (NL-EPR) / No-Lead Ethylene Alkene Copolymer (EAM)
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Overall Jacket:SIMpull® Polyvinyl Chloride (PVC)
Applications and Features:
Southwire’s 15kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), aerially supported by a messenger and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -25°C for cold bend and cold impact and marked with "LTGG" when CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lb/ft maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemicals, oils and acids and are flame retardant. Cable Tray CT rated 1/0 AWG and larger.
Specifications:
Sample Print Legend:
SOUTHWIRE SIMpull{R} POWER CABLE MASTER-DESIGN {UL} XXX KCMIL CU 220 MILS NL-EPR 15KV 133% INS LEVEL 25%TS MV-105 FOR CT USE SUN RES {NESC} -- {CSA} XXX KCMIL CU X.XXmm (220 mils) NL-EPR 15KV 133% INS LEVEL 25%TS MV68.10 SR 105{D}C FT4 -25{D}C LTDD -- PAT www.patentSW.com -- RoHS
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Diameter Over Insulation | Diameter Over Insulation Shield | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Max Pull Tension | Min Bending Radius | Conduit Size |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | inch | inch | mil | inch | lb/1000ft | lb/1000ft | lb | inch | inch | |
| 953638◊ | 2 | 7 | 0.283 | 0.761 | 0.821 | 80 | 1.001 | 276 | 648 | 530 | 12 | 2.5 |
| 955104 | 1 | 19 | 0.322 | 0.8 | 0.86 | 80 | 1.04 | 333 | 726 | 669 | 12.5 | 2.5 |
| 955989◊ | 1/0 | 19 | 0.362 | 0.84 | 0.9 | 80 | 1.08 | 403 | 820 | 844 | 13 | 2.5 |
| 955997◊ | 2/0 | 19 | 0.405 | 0.884 | 0.944 | 80 | 1.124 | 492 | 934 | 1064 | 13.5 | 3 |
| 956003 | 3/0 | 19 | 0.456 | 0.934 | 0.994 | 80 | 1.174 | 603 | 1074 | 1342 | 14.1 | 3 |
| 956011◊ | 4/0 | 19 | 0.512 | 0.99 | 1.05 | 80 | 1.23 | 744 | 1247 | 1692 | 14.8 | 3 |
| 956029◊ | 250 | 37 | 0.558 | 1.044 | 1.104 | 80 | 1.284 | 866 | 1403 | 2000 | 15.4 | 3.5 |
| 956037◊ | 350 | 37 | 0.661 | 1.147 | 1.207 | 80 | 1.387 | 1183 | 1780 | 2800 | 16.6 | 3.5 |
| 956045◊ | 500 | 37 | 0.789 | 1.252 | 1.312 | 80 | 1.492 | 1654 | 2313 | 4000 | 17.9 | 4 |
| 139631** | 500 | 37 | 0.789 | 1.275 | 1.335 | 80 | 1.515 | 1656 | 2328 | 4000 | 18.2 | 4 |
| 643755◊ | 600 | 61 | 0.866 | 1.336 | 1.396 | 80 | 1.576 | 1970 | 2682 | 4800 | 18.9 | 4 |
| 956052◊ | 750 | 61 | 0.968 | 1.464 | 1.524 | 110 | 1.764 | 2443 | 3329 | 6000 | 21.2 | 4.5 |
| 956060◊ | 1000 | 61 | 1.117 | 1.613 | 1.673 | 110 | 1.913 | 3226 | 4209 | 8000 | 23 | 5 |
| 581886 | 1250 | 91 | 1.25 | 1.78 | 1.84 | 110 | 2.08 | 4011 | 5115 | 10000 | 25 | 5.5 |
| 567443 | 1500 | 91 | 1.37 | 1.93 | 1.99 | 110 | 2.23 | 4795 | 6014 | 12000 | 26.8 | 6 |
| 550811 | 2000 | 127 | 1.583 | 2.143 | 2.203 | 110 | 2.443 | 6356 | 7724 | 16000 | 29.3 | 6.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Conduit size based on 3 phase 40% fill-factor without ground
** Tinned Copper
** Tinned Copper
Table 2 – Electrical and Engineering Data
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90/105°C | Allowable Ampacity In Air 90/105°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 0.162 | 0.221 | 0.045 | 0.051 | 0.581+j0.462 | 0.222+j0.057 | 2575 | 150/160 | 165/185 |
| 1 | 0.128 | 0.175 | 0.042 | 0.049 | 0.536+j0.444 | 0.176+j0.054 | 2696 | 170/185 | 185/210 |
| 1/0 | 0.102 | 0.139 | 0.039 | 0.047 | 0.500+j0.427 | 0.140+j0.052 | 2820 | 195/210 | 215/240 |
| 2/0 | 0.082 | 0.112 | 0.036 | 0.045 | 0.473+j0.409 | 0.113+j0.051 | 2956 | 220/235 | 245/275 |
| 3/0 | 0.064 | 0.087 | 0.033 | 0.043 | 0.447+j0.391 | 0.088+j0.049 | 3111 | 250/270 | 285/315 |
| 4/0 | 0.051 | 0.07 | 0.031 | 0.042 | 0.428+j0.371 | 0.071+j0.047 | 3284 | 285/305 | 325/360 |
| 250 | 0.043 | 0.059 | 0.029 | 0.041 | 0.415+j0.353 | 0.060+j0.046 | 3452 | 310/335 | 360/400 |
| 350 | 0.031 | 0.043 | 0.025 | 0.039 | 0.393+j0.323 | 0.044+j0.044 | 3771 | 375/400 | 435/490 |
| 500 | 0.021 | 0.03 | 0.021 | 0.036 | 0.373+j0.294 | 0.031+j0.042 | 4096 | 450/485 | 535/600 |
| 500 | 0.022 | 0.032 | 0.022 | 0.037 | 0.374+j0.289 | 0.033+j0.042 | 4167 | 450/485 | 535/600 |
| 600 | 0.018 | 0.026 | 0.019 | 0.035 | 0.363+j0.274 | 0.027+j0.040 | 4356 | 488/525 | 589/658 |
| 750 | 0.014 | 0.021 | 0.019 | 0.035 | 0.347+j0.248 | 0.022+j0.041 | 4753 | 545/585 | 670/745 |
| 1000 | 0.011 | 0.018 | 0.017 | 0.034 | 0.332+j0.221 | 0.019+j0.039 | 5215 | 615/660 | 770/860 |
| 1250 | 0.008 | 0.014 | 0.016 | 0.033 | 0.315+j0.196 | 0.015+j0.039 | 5732 | 685/735 | 870/975 |
| 1500 | 0.007 | 0.014 | 0.016 | 0.033 | 0.303+j0.177 | 0.015+j0.038 | 6197 | 780/835 | 1005/1120 |
| 2000 | 0.005 | 0.013 | 0.014 | 0.032 | 0.286+j0.154 | 0.015+j0.037 | 6857 | 895/960 | 1170/1320 |
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.
Revision: 1.000.021
Updated On: Nov. 11, 2026, 2:34 p.m. UTC



