SPEC 26632

HVTECK AL 1/C 420TRXLPE TS PVC AIA PVC 35kV 133% CSA

Single Conductor, 420 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:420 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 420 TRXLPE AIA 35kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchinchmilinchlb/1000ftlb/1000ftinch
    1/0190.3361.2144201.274801.4541.764601.88410517045
    2/0190.3761.2544201.314801.4941.804601.92410817885
    3/0190.4231.3014201.361801.5411.851601.97111218895
    4/0190.4751.3534201.413801.5931.903602.02311620055.5
    250370.521.4064201.466801.6461.956602.07612121215.5
    350370.6161.5024201.5621101.8022.112602.23212824726
    500370.7361.6224201.6821101.9222.232602.35213827946
    750610.9081.8044201.8641102.1042.414752.56415333817
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/013.26330.1670.2290.080.0610.570+j0.3210.230+j0.0653978221219
    2/013.57980.1330.1820.0750.0590.520+j0.3090.183+j0.0634102253246
    3/013.810060.1050.1440.0710.0570.479+j0.2970.145+j0.0614248288275
    4/014.212690.0840.1150.0660.0550.447+j0.2840.117+j0.0594409327305
    25014.515000.070.0960.0620.0540.424+j0.2720.098+j0.0574573367343
    35015.621000.0510.070.0560.0510.390+j0.2510.072+j0.0554871443399
    50016.530000.0360.050.050.0480.361+j0.2290.052+j0.0525242529451
    75017.945000.0230.0330.0430.0460.330+j0.2000.035+j0.0495806633505
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmmmkg/kmkg/kminch
    1/0198.5330.8410.6732.362.0336.9344.811.5247.8515625365
    2/0199.5531.8510.6733.382.0337.9545.821.5248.8716126615
    3/01910.7433.0510.6734.572.0339.1447.021.5250.0616728115
    4/01912.0734.3710.6735.892.0340.4648.341.5251.3817329845.5
    2503713.2135.7110.6737.242.0341.8149.681.5252.7318031565.5
    3503715.6538.1510.6739.672.7945.7753.641.5256.6919036796
    5003718.6941.2010.6742.722.7948.8256.691.5259.7420541586
    7506123.0645.8210.6747.352.7953.4461.321.9165.1322850317
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0335.2828170.54790.750.02440.20010.570+j0.3210.230+j0.0653978221219
    2/0342.9035510.43640.600.02290.19360.520+j0.3090.183+j0.0634102253246
    3/0350.5244770.34450.470.02160.18700.479+j0.2970.145+j0.0614248288275
    4/0360.6856470.27560.380.02010.18040.447+j0.2840.117+j0.0594409327305
    250368.3066750.22970.310.01890.17720.424+j0.2720.098+j0.0574573367343
    350396.2493450.16730.230.01710.16730.390+j0.2510.072+j0.0554871443399
    500419.10133500.11810.160.01520.15750.361+j0.2290.052+j0.0525242529451
    750454.66200250.07550.110.01310.15090.330+j0.2000.035+j0.0495806633505
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC