SPEC 26632
HVTECK AL 1/C 420TRXLPE TS PVC AIA PVC 35kV 133% CSA
Single Conductor, 420 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:420 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 420 TRXLPE AIA 35kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | mil | inch | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 1/0 | 19 | 0.336 | 1.214 | 420 | 1.274 | 80 | 1.454 | 1.764 | 60 | 1.884 | 105 | 1704 | 5 |
| 2/0 | 19 | 0.376 | 1.254 | 420 | 1.314 | 80 | 1.494 | 1.804 | 60 | 1.924 | 108 | 1788 | 5 |
| 3/0 | 19 | 0.423 | 1.301 | 420 | 1.361 | 80 | 1.541 | 1.851 | 60 | 1.971 | 112 | 1889 | 5 |
| 4/0 | 19 | 0.475 | 1.353 | 420 | 1.413 | 80 | 1.593 | 1.903 | 60 | 2.023 | 116 | 2005 | 5.5 |
| 250 | 37 | 0.52 | 1.406 | 420 | 1.466 | 80 | 1.646 | 1.956 | 60 | 2.076 | 121 | 2121 | 5.5 |
| 350 | 37 | 0.616 | 1.502 | 420 | 1.562 | 110 | 1.802 | 2.112 | 60 | 2.232 | 128 | 2472 | 6 |
| 500 | 37 | 0.736 | 1.622 | 420 | 1.682 | 110 | 1.922 | 2.232 | 60 | 2.352 | 138 | 2794 | 6 |
| 750 | 61 | 0.908 | 1.804 | 420 | 1.864 | 110 | 2.104 | 2.414 | 75 | 2.564 | 153 | 3381 | 7 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 | 13.2 | 633 | 0.167 | 0.229 | 0.08 | 0.061 | 0.570+j0.321 | 0.230+j0.065 | 3978 | 221 | 219 |
| 2/0 | 13.5 | 798 | 0.133 | 0.182 | 0.075 | 0.059 | 0.520+j0.309 | 0.183+j0.063 | 4102 | 253 | 246 |
| 3/0 | 13.8 | 1006 | 0.105 | 0.144 | 0.071 | 0.057 | 0.479+j0.297 | 0.145+j0.061 | 4248 | 288 | 275 |
| 4/0 | 14.2 | 1269 | 0.084 | 0.115 | 0.066 | 0.055 | 0.447+j0.284 | 0.117+j0.059 | 4409 | 327 | 305 |
| 250 | 14.5 | 1500 | 0.07 | 0.096 | 0.062 | 0.054 | 0.424+j0.272 | 0.098+j0.057 | 4573 | 367 | 343 |
| 350 | 15.6 | 2100 | 0.051 | 0.07 | 0.056 | 0.051 | 0.390+j0.251 | 0.072+j0.055 | 4871 | 443 | 399 |
| 500 | 16.5 | 3000 | 0.036 | 0.05 | 0.05 | 0.048 | 0.361+j0.229 | 0.052+j0.052 | 5242 | 529 | 451 |
| 750 | 17.9 | 4500 | 0.023 | 0.033 | 0.043 | 0.046 | 0.330+j0.200 | 0.035+j0.049 | 5806 | 633 | 505 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | kg/km | inch |
| 1/0 | 19 | 8.53 | 30.84 | 10.67 | 32.36 | 2.03 | 36.93 | 44.81 | 1.52 | 47.85 | 156 | 2536 | 5 |
| 2/0 | 19 | 9.55 | 31.85 | 10.67 | 33.38 | 2.03 | 37.95 | 45.82 | 1.52 | 48.87 | 161 | 2661 | 5 |
| 3/0 | 19 | 10.74 | 33.05 | 10.67 | 34.57 | 2.03 | 39.14 | 47.02 | 1.52 | 50.06 | 167 | 2811 | 5 |
| 4/0 | 19 | 12.07 | 34.37 | 10.67 | 35.89 | 2.03 | 40.46 | 48.34 | 1.52 | 51.38 | 173 | 2984 | 5.5 |
| 250 | 37 | 13.21 | 35.71 | 10.67 | 37.24 | 2.03 | 41.81 | 49.68 | 1.52 | 52.73 | 180 | 3156 | 5.5 |
| 350 | 37 | 15.65 | 38.15 | 10.67 | 39.67 | 2.79 | 45.77 | 53.64 | 1.52 | 56.69 | 190 | 3679 | 6 |
| 500 | 37 | 18.69 | 41.20 | 10.67 | 42.72 | 2.79 | 48.82 | 56.69 | 1.52 | 59.74 | 205 | 4158 | 6 |
| 750 | 61 | 23.06 | 45.82 | 10.67 | 47.35 | 2.79 | 53.44 | 61.32 | 1.91 | 65.13 | 228 | 5031 | 7 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 | 335.28 | 2817 | 0.5479 | 0.75 | 0.0244 | 0.2001 | 0.570+j0.321 | 0.230+j0.065 | 3978 | 221 | 219 |
| 2/0 | 342.90 | 3551 | 0.4364 | 0.60 | 0.0229 | 0.1936 | 0.520+j0.309 | 0.183+j0.063 | 4102 | 253 | 246 |
| 3/0 | 350.52 | 4477 | 0.3445 | 0.47 | 0.0216 | 0.1870 | 0.479+j0.297 | 0.145+j0.061 | 4248 | 288 | 275 |
| 4/0 | 360.68 | 5647 | 0.2756 | 0.38 | 0.0201 | 0.1804 | 0.447+j0.284 | 0.117+j0.059 | 4409 | 327 | 305 |
| 250 | 368.30 | 6675 | 0.2297 | 0.31 | 0.0189 | 0.1772 | 0.424+j0.272 | 0.098+j0.057 | 4573 | 367 | 343 |
| 350 | 396.24 | 9345 | 0.1673 | 0.23 | 0.0171 | 0.1673 | 0.390+j0.251 | 0.072+j0.055 | 4871 | 443 | 399 |
| 500 | 419.10 | 13350 | 0.1181 | 0.16 | 0.0152 | 0.1575 | 0.361+j0.229 | 0.052+j0.052 | 5242 | 529 | 451 |
| 750 | 454.66 | 20025 | 0.0755 | 0.11 | 0.0131 | 0.1509 | 0.330+j0.200 | 0.035+j0.049 | 5806 | 633 | 505 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC