SPEC 26612
HVTECK CU 1/C 420TRXLPE TS PVC AIA PVC 35kV 133% CSA
Single Conductor, 420 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:420 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 420 TRXLPE AIA 35kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 1/0 | 19 | 0.362 | 1.24 | 420 | 1.3 | 80 | 1.79 | 60 | 1.91 | 433 | 1968 | 5 |
| 2/0 | 19 | 0.405 | 1.283 | 420 | 1.343 | 80 | 1.833 | 60 | 1.953 | 521 | 2114 | 5 |
| 3/0 | 19 | 0.456 | 1.334 | 420 | 1.394 | 80 | 1.884 | 60 | 2.004 | 633 | 2295 | 5 |
| 4/0 | 19 | 0.512 | 1.39 | 420 | 1.45 | 80 | 1.94 | 60 | 2.06 | 772 | 2510 | 5.5 |
| 250 | 37 | 0.558 | 1.444 | 420 | 1.504 | 110 | 2.054 | 60 | 2.174 | 896 | 2825 | 5.5 |
| 350 | 37 | 0.661 | 1.547 | 420 | 1.607 | 110 | 2.157 | 60 | 2.277 | 1213 | 3288 | 6 |
| 500 | 37 | 0.789 | 1.675 | 420 | 1.735 | 110 | 2.285 | 75 | 2.435 | 1687 | 4007 | 6.5 |
| 750 | 61 | 0.968 | 1.864 | 420 | 1.924 | 110 | 2.474 | 75 | 2.624 | 2474 | 5075 | 7 |
| 1000 | 61 | 1.117 | 2.013 | 420 | 2.073 | 110 | 2.623 | 75 | 2.773 | 3258 | 6075 | 7.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 | 13.4 | 844 | 0.102 | 0.139 | 0.077 | 0.06 | 0.478+j0.315 | 0.140+j0.065 | 4059 | 278 | 272 |
| 2/0 | 13.7 | 1064 | 0.082 | 0.112 | 0.072 | 0.058 | 0.449+j0.303 | 0.113+j0.063 | 4192 | 316 | 303 |
| 3/0 | 14 | 1342 | 0.064 | 0.087 | 0.068 | 0.056 | 0.420+j0.290 | 0.089+j0.061 | 4350 | 356 | 333 |
| 4/0 | 14.4 | 1692 | 0.051 | 0.07 | 0.063 | 0.054 | 0.399+j0.277 | 0.072+j0.059 | 4524 | 403 | 367 |
| 250 | 15.2 | 2000 | 0.043 | 0.059 | 0.059 | 0.053 | 0.384+j0.265 | 0.061+j0.058 | 4691 | 455 | 411 |
| 350 | 15.9 | 2800 | 0.031 | 0.043 | 0.053 | 0.05 | 0.360+j0.244 | 0.045+j0.055 | 5010 | 537 | 459 |
| 500 | 17 | 4000 | 0.021 | 0.03 | 0.047 | 0.048 | 0.337+j0.221 | 0.032+j0.053 | 5407 | 616 | 499 |
| 750 | 18.4 | 6000 | 0.014 | 0.021 | 0.041 | 0.045 | 0.313+j0.193 | 0.023+j0.050 | 5992 | 716 | 557 |
| 1000 | 19.4 | 8000 | 0.011 | 0.018 | 0.037 | 0.043 | 0.299+j0.174 | 0.020+j0.048 | 6454 | 825 | 608 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | kg/km | inch |
| 1/0 | 19 | 9.19 | 31.50 | 10.67 | 33.02 | 2.03 | 45.47 | 1.52 | 48.51 | 644 | 2929 | 5 |
| 2/0 | 19 | 10.29 | 32.59 | 10.67 | 34.11 | 2.03 | 46.56 | 1.52 | 49.61 | 775 | 3146 | 5 |
| 3/0 | 19 | 11.58 | 33.88 | 10.67 | 35.41 | 2.03 | 47.85 | 1.52 | 50.90 | 942 | 3415 | 5 |
| 4/0 | 19 | 13.00 | 35.31 | 10.67 | 36.83 | 2.03 | 49.28 | 1.52 | 52.32 | 1149 | 3735 | 5.5 |
| 250 | 37 | 14.17 | 36.68 | 10.67 | 38.20 | 2.79 | 52.17 | 1.52 | 55.22 | 1333 | 4204 | 5.5 |
| 350 | 37 | 16.79 | 39.29 | 10.67 | 40.82 | 2.79 | 54.79 | 1.52 | 57.84 | 1805 | 4893 | 6 |
| 500 | 37 | 20.04 | 42.55 | 10.67 | 44.07 | 2.79 | 58.04 | 1.91 | 61.85 | 2511 | 5963 | 6.5 |
| 750 | 61 | 24.59 | 47.35 | 10.67 | 48.87 | 2.79 | 62.84 | 1.91 | 66.65 | 3682 | 7552 | 7 |
| 1000 | 61 | 28.37 | 51.13 | 10.67 | 52.65 | 2.79 | 66.62 | 1.91 | 70.43 | 4848 | 9041 | 7.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 | 340.36 | 3756 | 0.3346 | 0.46 | 0.0235 | 0.1969 | 0.478+j0.315 | 0.140+j0.065 | 4059 | 278 | 272 |
| 2/0 | 347.98 | 4735 | 0.2690 | 0.37 | 0.0219 | 0.1903 | 0.449+j0.303 | 0.113+j0.063 | 4192 | 316 | 303 |
| 3/0 | 355.60 | 5972 | 0.2100 | 0.29 | 0.0207 | 0.1837 | 0.420+j0.290 | 0.089+j0.061 | 4350 | 356 | 333 |
| 4/0 | 365.76 | 7529 | 0.1673 | 0.23 | 0.0192 | 0.1772 | 0.399+j0.277 | 0.072+j0.059 | 4524 | 403 | 367 |
| 250 | 386.08 | 8900 | 0.1411 | 0.19 | 0.0180 | 0.1739 | 0.384+j0.265 | 0.061+j0.058 | 4691 | 455 | 411 |
| 350 | 403.86 | 12460 | 0.1017 | 0.14 | 0.0162 | 0.1640 | 0.360+j0.244 | 0.045+j0.055 | 5010 | 537 | 459 |
| 500 | 431.80 | 17800 | 0.0689 | 0.10 | 0.0143 | 0.1575 | 0.337+j0.221 | 0.032+j0.053 | 5407 | 616 | 499 |
| 750 | 467.36 | 26700 | 0.0459 | 0.07 | 0.0125 | 0.1476 | 0.313+j0.193 | 0.023+j0.050 | 5992 | 716 | 557 |
| 1000 | 492.76 | 35600 | 0.0361 | 0.06 | 0.0113 | 0.1411 | 0.299+j0.174 | 0.020+j0.048 | 6454 | 825 | 608 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A