SPEC 26541

HVTECK CU 3/C 280NLEPR TS PVC AIA PVC 28kV 100% CSA

3 Conductor, 280 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:280 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 280 NLEPR AIA 28kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGAWGmilinchinchmilinchlb/1000ftlb/1000ftinch
    1190.3220.922800.981x661102.3632.673752.823110831643.5
    1/0190.3620.962801.021x661102.4492.759752.909132434843.5
    2/0190.4051.0032801.0631x661102.5422.852753.002159238634
    3/0190.4561.0542801.1141x441102.6522.962753.112197743814
    4/0190.5121.112801.171x441252.8033.113853.283240050164.5
    250370.5581.1642801.2241x441252.923.23853.4277455464.5
    350370.6611.2672801.3271x331253.1423.452853.622377068154.5
    500370.7891.3952801.4551x331253.4193.729853.899520585915
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    119.820080.1280.1750.0490.0320.544+j0.4050.175+j0.0483067202226
    1/020.425340.1020.1390.0460.030.507+j0.3890.139+j0.0463191231256
    2/02131940.0820.1120.0430.0280.478+j0.3730.112+j0.0453325265290
    3/021.840270.0640.0870.040.0270.450+j0.3560.087+j0.0433483303327
    4/02350780.0510.070.0370.0250.430+j0.3380.070+j0.0413656348369
    25023.860000.0430.0590.0340.0240.415+j0.3220.059+j0.0403823384408
    35025.484000.0310.0430.030.0220.391+j0.2940.043+j0.0384143468485
    50027.3120000.0210.030.0270.020.368+j0.2640.030+j0.0364539565571
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGAWGmmmmmmmmmmkg/kmkg/kminch
    1198.1823.377.1124.891x662.7960.0267.891.9171.70164947093.5
    1/0199.1924.387.1125.911x662.7962.2070.081.9173.89197051853.5
    2/01910.2925.487.1127.001x662.7964.5772.441.9176.25236957494
    3/01911.5826.777.1128.301x442.7967.3675.231.9179.04294265204
    4/01913.0028.197.1129.721x443.1871.2079.072.1683.39357274654.5
    2503714.1729.577.1131.091x443.1874.1782.042.1686.36412882534.5
    3503716.7932.187.1133.711x333.1879.8187.682.1692.005610101424.5
    5003720.0435.437.1136.961x333.1886.8494.722.1699.037746127855
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1502.9289360.41990.570.01490.10500.544+j0.4050.175+j0.0483067202226
    1/0518.16112760.33460.460.01400.09840.507+j0.3890.139+j0.0463191231256
    2/0533.40142130.26900.370.01310.09190.478+j0.3730.112+j0.0453325265290
    3/0553.72179200.21000.290.01220.08860.450+j0.3560.087+j0.0433483303327
    4/0584.20225970.16730.230.01130.08200.430+j0.3380.070+j0.0413656348369
    250604.52267000.14110.190.01040.07870.415+j0.3220.059+j0.0403823384408
    350645.16373800.10170.140.00910.07220.391+j0.2940.043+j0.0384143468485
    500693.42534000.06890.100.00820.06560.368+j0.2640.030+j0.0364539565571
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC