SPEC 26522

HVTECK AL 1/C 345NLEPR TS PVC AIA PVC 28kV 133% CSA

Single Conductor, 345 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:345 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 345 NLEPR AIA 28kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ftinch
    1190.2991.0273451.087801.577601.6978913864.5
    1/0190.3361.0643451.124801.614601.7349214544.5
    2/0190.3761.1043451.164801.654601.7749615334.5
    3/0190.4231.1513451.211801.701601.82110016274.5
    4/0190.4751.2033451.263801.753601.87310417365
    250370.521.2563451.316801.806601.92610818465
    350370.6161.3523451.412801.902602.02211620675.5
    500370.7361.4723451.5321102.082602.20212624826
    750610.9081.6543451.7141102.264752.41414130406.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    111.95020.2110.2890.0580.0620.639+j0.3700.290+j0.0653399193194
    1/012.16330.1670.2290.0550.0590.578+j0.3580.230+j0.0633514221219
    2/012.47980.1330.1820.0510.0570.529+j0.3440.183+j0.0613638253246
    3/012.710060.1050.1440.0480.0550.489+j0.3300.145+j0.0593783288275
    4/013.112690.0840.1150.0440.0530.457+j0.3150.116+j0.0573944327305
    25013.515000.070.0960.0420.0520.434+j0.3010.097+j0.0564108367343
    35014.221000.0510.070.0370.0490.402+j0.2780.072+j0.0534406443399
    50015.430000.0360.050.0330.0470.372+j0.2520.052+j0.0514778529451
    75016.945000.0230.0330.0280.0440.341+j0.2190.035+j0.0485342633505
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/kminch
    1197.5926.098.7627.612.0340.061.5243.1013220634.5
    1/0198.5327.038.7628.552.0341.001.5244.0413721644.5
    2/0199.5528.048.7629.572.0342.011.5245.0614322814.5
    3/01910.7429.248.7630.762.0343.211.5246.2514924214.5
    4/01912.0730.568.7632.082.0344.531.5247.5715525835
    2503713.2131.908.7633.432.0345.871.5248.9216127475
    3503715.6534.348.7635.862.0348.311.5251.3617330765.5
    5003718.6937.398.7638.912.7952.881.5255.9318836946
    7506123.0642.018.7643.542.7957.511.9161.3221045246.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1302.2622340.69230.950.01770.20340.639+j0.3700.290+j0.0653399193194
    1/0307.3428170.54790.750.01680.19360.578+j0.3580.230+j0.0633514221219
    2/0314.9635510.43640.600.01550.18700.529+j0.3440.183+j0.0613638253246
    3/0322.5844770.34450.470.01460.18040.489+j0.3300.145+j0.0593783288275
    4/0332.7456470.27560.380.01340.17390.457+j0.3150.116+j0.0573944327305
    250342.9066750.22970.310.01280.17060.434+j0.3010.097+j0.0564108367343
    350360.6893450.16730.230.01130.16080.402+j0.2780.072+j0.0534406443399
    500391.16133500.11810.160.01010.15420.372+j0.2520.052+j0.0514778529451
    750429.26200250.07550.110.00850.14440.341+j0.2190.035+j0.0485342633505
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC