SPEC 26516

HVTECK CU 1/C 345TRXLPE CB PVC AIA PVC 28kV 133% CSA

Single Conductor, 345 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:345 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 345 TRXLPE AIA 28kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    1190.3221.053451.117x12801.87601.9947821675
    1/0190.3621.093451.157x12801.91602.0355022975.5
    2/0190.4051.1333451.1937x12801.953602.07363824485.5
    3/0190.4561.1843451.2449x121102.064602.18478327825.5
    4/0190.5121.243451.39x121102.12602.2492330066
    250370.5581.2943451.35411x121102.174602.294108832576
    350370.6611.3973451.45713x121102.277752.427145938496.5
    500370.7891.5253451.58517x121102.405752.555200045886.5
    750610.9681.7143451.77421x121102.594752.744287357627.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    113.96690.1280.1750.0730.0640.416+j0.1370.179+j0.0693879245244
    1/014.28440.1020.1390.0680.0610.379+j0.1350.143+j0.0673879278272
    2/014.510640.0820.1120.0640.0590.352+j0.1340.116+j0.0643879316303
    3/015.313420.0640.0870.0590.0580.287+j0.0970.092+j0.0634987356333
    4/015.716920.0510.070.0550.0560.269+j0.0950.074+j0.0614987403367
    25016.120000.0430.0590.0520.0540.228+j0.0740.064+j0.0596095455411
    3501728000.0310.0430.0460.0520.190+j0.0600.049+j0.0567203537459
    50017.940000.0210.030.0410.0490.145+j0.0440.037+j0.0529420616499
    75019.260000.0140.0210.0350.0460.115+j0.0350.030+j0.04811636716557
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    1198.1826.678.7628.197x122.0347.501.5250.5571132255
    1/0199.1927.698.7629.217x122.0348.511.5251.5681834185.5
    2/01910.2928.788.7630.307x122.0349.611.5252.6594936435.5
    3/01911.5830.078.7631.609x122.7952.431.5255.47116541405.5
    4/01913.0031.508.7633.029x122.7953.851.5256.90137444736
    2503714.1732.878.7634.3911x122.7955.221.5258.27161948476
    3503716.7935.488.7637.0113x122.7957.841.9161.65217157286.5
    5003720.0438.738.7640.2617x122.7961.091.9164.90297668286.5
    7506124.5943.548.7645.0621x122.7965.891.9169.70427585757.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1353.0629770.41990.570.02230.21000.416+j0.1370.179+j0.0693879245244
    1/0360.6837560.33460.460.02070.20010.379+j0.1350.143+j0.0673879278272
    2/0368.3047350.26900.370.01950.19360.352+j0.1340.116+j0.0643879316303
    3/0388.6259720.21000.290.01800.19030.287+j0.0970.092+j0.0634987356333
    4/0398.7875290.16730.230.01680.18370.269+j0.0950.074+j0.0614987403367
    250408.9489000.14110.190.01580.17720.228+j0.0740.064+j0.0596095455411
    350431.80124600.10170.140.01400.17060.190+j0.0600.049+j0.0567203537459
    500454.66178000.06890.100.01250.16080.145+j0.0440.037+j0.0529420616499
    750487.68267000.04590.070.01070.15090.115+j0.0350.030+j0.04811636716557
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC