SPEC 26462
HVTECK AL 3/C 320NLEPR TS PVC AIA PVC 25kV 133% CSA
3 Conductor, 320 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:320 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 320 NLEPR AIA 25kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch | |
| TBA | 1 | 19 | 0.299 | 0.977 | 320 | 1.037 | 1x6 | 110 | 2.796 | 75 | 2.946 | 342 | 2865 | 4 |
| 580658^ | 1/0 | 10 | 0.336 | 1.014 | 320 | 1.074 | 1x6 | 110 | 2.934 | 75 | 3.084 | 361 | 3766 | 4 |
| TBA | 2/0 | 19 | 0.376 | 1.054 | 320 | 1.114 | 1x6 | 110 | 2.962 | 75 | 3.112 | 361 | 3242 | 4 |
| TBA | 3/0 | 19 | 0.423 | 1.101 | 320 | 1.161 | 1x6 | 125 | 3.094 | 85 | 3.264 | 373 | 3554 | 4 |
| TBA | 4/0 | 19 | 0.475 | 1.153 | 320 | 1.213 | 1x6 | 125 | 3.206 | 85 | 3.376 | 386 | 3840 | 4.5 |
| TBA | 250 | 37 | 0.52 | 1.206 | 320 | 1.266 | 1x4 | 125 | 3.321 | 85 | 3.491 | 446 | 4174 | 4.5 |
| TBA | 350 | 37 | 0.616 | 1.302 | 320 | 1.362 | 1x4 | 125 | 3.528 | 85 | 3.698 | 470 | 4761 | 5 |
| TBA | 500 | 37 | 0.736 | 1.422 | 320 | 1.482 | 1x3 | 125 | 3.787 | 85 | 3.957 | 538 | 5606 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 20.6 | 1506 | 0.211 | 0.289 | 0.056 | 0.035 | 0.656+j0.386 | 0.289+j0.049 | 3244 | 158 | 177 |
| 1/0 | 21.6 | 1900 | 0.167 | 0.229 | 0.052 | 0.033 | 0.594+j0.373 | 0.229+j0.047 | 3359 | 181 | 200 |
| 2/0 | 21.8 | 2395 | 0.133 | 0.182 | 0.049 | 0.031 | 0.545+j0.359 | 0.182+j0.046 | 3483 | 208 | 228 |
| 3/0 | 22.8 | 3020 | 0.105 | 0.144 | 0.045 | 0.029 | 0.504+j0.343 | 0.144+j0.044 | 3628 | 239 | 258 |
| 4/0 | 23.6 | 3808 | 0.084 | 0.115 | 0.042 | 0.028 | 0.472+j0.327 | 0.115+j0.042 | 3789 | 273 | 292 |
| 250 | 24.4 | 4500 | 0.07 | 0.096 | 0.039 | 0.026 | 0.449+j0.312 | 0.096+j0.041 | 3954 | 302 | 321 |
| 350 | 25.9 | 6300 | 0.051 | 0.07 | 0.035 | 0.024 | 0.415+j0.287 | 0.070+j0.039 | 4251 | 368 | 385 |
| 500 | 27.7 | 9000 | 0.036 | 0.05 | 0.031 | 0.022 | 0.386+j0.259 | 0.050+j0.037 | 4623 | 454 | 462 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch | |
| TBA | 1 | 19 | 7.59 | 24.82 | 8.13 | 26.34 | 1x6 | 2.79 | 71.02 | 1.91 | 74.83 | 509 | 4264 | 4 |
| 580658^ | 1/0 | 10 | 8.53 | 25.76 | 8.13 | 27.28 | 1x6 | 2.79 | 74.52 | 1.91 | 78.33 | 537 | 5604 | 4 |
| TBA | 2/0 | 19 | 9.55 | 26.77 | 8.13 | 28.30 | 1x6 | 2.79 | 75.23 | 1.91 | 79.04 | 537 | 4825 | 4 |
| TBA | 3/0 | 19 | 10.74 | 27.97 | 8.13 | 29.49 | 1x6 | 3.18 | 78.59 | 2.16 | 82.91 | 555 | 5289 | 4 |
| TBA | 4/0 | 19 | 12.07 | 29.29 | 8.13 | 30.81 | 1x6 | 3.18 | 81.43 | 2.16 | 85.75 | 574 | 5715 | 4.5 |
| TBA | 250 | 37 | 13.21 | 30.63 | 8.13 | 32.16 | 1x4 | 3.18 | 84.35 | 2.16 | 88.67 | 664 | 6212 | 4.5 |
| TBA | 350 | 37 | 15.65 | 33.07 | 8.13 | 34.59 | 1x4 | 3.18 | 89.61 | 2.16 | 93.93 | 699 | 7085 | 5 |
| TBA | 500 | 37 | 18.69 | 36.12 | 8.13 | 37.64 | 1x3 | 3.18 | 96.19 | 2.16 | 100.51 | 801 | 8343 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 523.24 | 6702 | 0.6923 | 0.95 | 0.0171 | 0.1148 | 0.656+j0.386 | 0.289+j0.049 | 3244 | 158 | 177 |
| 1/0 | 548.64 | 8455 | 0.5479 | 0.75 | 0.0158 | 0.1083 | 0.594+j0.373 | 0.229+j0.047 | 3359 | 181 | 200 |
| 2/0 | 553.72 | 10658 | 0.4364 | 0.60 | 0.0149 | 0.1017 | 0.545+j0.359 | 0.182+j0.046 | 3483 | 208 | 228 |
| 3/0 | 579.12 | 13439 | 0.3445 | 0.47 | 0.0137 | 0.0951 | 0.504+j0.343 | 0.144+j0.044 | 3628 | 239 | 258 |
| 4/0 | 599.44 | 16946 | 0.2756 | 0.38 | 0.0128 | 0.0919 | 0.472+j0.327 | 0.115+j0.042 | 3789 | 273 | 292 |
| 250 | 619.76 | 20025 | 0.2297 | 0.31 | 0.0119 | 0.0853 | 0.449+j0.312 | 0.096+j0.041 | 3954 | 302 | 321 |
| 350 | 657.86 | 28035 | 0.1673 | 0.23 | 0.0107 | 0.0787 | 0.415+j0.287 | 0.070+j0.039 | 4251 | 368 | 385 |
| 500 | 703.58 | 40050 | 0.1181 | 0.16 | 0.0094 | 0.0722 | 0.386+j0.259 | 0.050+j0.037 | 4623 | 454 | 462 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC