SPEC 26432

HVTECK AL 1/C 320TRXLPE TS PVC AIA PVC 25kV 133% CSA

Single Conductor, 320 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:320 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 320 TRXLPE AIA 25kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ft
    1/0190.3361.0143201.074801.586601.7061133
    2/0190.3761.0543201.114801.650601.7701233
    3/0190.4221.1003201.160801.696601.8161317
    4/0190.4741.1523201.212801.748601.8681415
    250370.5201.2063201.266801.802601.9221513
    350370.6151.3013201.361801.897602.0171802
    500370.7351.4213201.4811102.077602.1972202
    750610.9081.6043201.6641102.260752.4102737
    1000611.0601.7563201.8161102.412752.5623160
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/020.56330.1680.2110.0710.0590.562 + j0.3290.212 + j0.0583358221219
    2/021.27980.1330.1670.0660.0570.515 + j0.3160.168 + j0.0563482253246
    3/021.810060.1050.1330.0620.0550.477 + j0.3010.134 + j0.0543625288275
    4/022.412690.0840.1050.0570.0530.445 + j0.2860.106 + j0.0523786327305
    25023.115000.0710.0900.0540.0520.425 + j0.2720.091 + j0.0503953367343
    35024.221000.0500.0650.0480.0490.392 + j0.2480.066 + j0.0474247443399
    50026.430000.0350.0460.0420.0470.361 + j0.2230.047 + j0.0454619529451
    75028.945000.0240.0330.0360.0440.331 + j0.1920.034 + j0.0435186633505
    100030.760000.0180.0260.0320.0420.310 + j0.1700.027 + j0.0415657711544
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/km
    1/0198.5325.768.1327.282.0340.281.5243.331686
    2/0199.5526.778.1328.302.0341.911.5244.961835
    3/01910.7227.948.1329.462.0343.081.5246.131960
    4/01912.0429.268.1330.782.0344.401.5247.452106
    2503713.2130.638.1332.162.0345.771.5248.822252
    3503715.6233.058.1334.572.0348.181.5251.232682
    5003718.6736.098.1337.622.7952.761.5255.803277
    7506123.0640.748.1342.272.7957.401.9161.214073
    10006126.9244.608.1346.132.7961.261.9165.074703
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0520.7028170.55120.690.02160.19360.562 + j0.3290.212 + j0.0583358221219
    2/0538.4835510.43640.550.02010.18700.515 + j0.3160.168 + j0.0563482253246
    3/0553.7244770.34450.440.01890.18040.477 + j0.3010.134 + j0.0543625288275
    4/0568.9656470.27560.340.01740.17390.445 + j0.2860.106 + j0.0523786327305
    250586.7466750.23290.300.01650.17060.425 + j0.2720.091 + j0.0503953367343
    350614.6893450.16400.210.01460.16080.392 + j0.2480.066 + j0.0474247443399
    500670.56133500.11480.150.01280.15420.361 + j0.2230.047 + j0.0454619529451
    750734.06200250.07870.110.01100.14440.331 + j0.1920.034 + j0.0435186633505
    1000779.78267000.05910.090.00980.13780.310 + j0.1700.027 + j0.0415657711544
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.001

    Updated On: Nov. 7, 2024, 7:11 p.m. UTC