SPEC 26411

HVTECK CU 1/C 260TRXLPE TS PVC AIA PVC 25kV 100% CSA

Single Conductor, 260 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:260 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 260 TRXLPE AIA 25kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ftinch
    1190.3220.882600.94801.33501.4333511783.5
    1/0190.3620.922600.98801.37501.4740712894
    2/0190.4050.9632601.023801.413501.51349514184
    3/0190.4561.0142601.074801.564601.68460617514.5
    4/0190.5121.072601.13801.62601.7474619514.5
    250370.5581.1242601.184801.674601.79486921364.5
    350370.6611.2272601.287801.777601.897118725655
    500370.7891.3552601.415801.905602.025166031765.5
    750610.9681.5442601.6041102.154602.274244842956
    1000611.1171.6932601.7531102.303752.453323253146.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1106690.1280.1750.0610.0560.530+j0.4150.176+j0.0612943245244
    1/010.38440.1020.1390.0570.0540.494+j0.3990.140+j0.0593067278272
    2/010.610640.0820.1120.0530.0520.466+j0.3840.113+j0.0573201316303
    3/011.813420.0640.0870.0490.0520.438+j0.3660.088+j0.0573359356333
    4/012.216920.0510.070.0450.050.419+j0.3480.071+j0.0553532403367
    25012.620000.0430.0590.0420.0490.405+j0.3320.060+j0.0543699455411
    35013.328000.0310.0430.0380.0460.383+j0.3040.044+j0.0514019537459
    50014.240000.0210.030.0330.0430.362+j0.2730.032+j0.0494415616499
    75015.960000.0140.0210.0280.0410.338+j0.2350.023+j0.0465001716557
    100017.280000.0110.0180.0250.040.323+j0.2110.020+j0.0455462825608
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/kminch
    1198.1822.356.6023.882.0333.781.2736.3249917533.5
    1/0199.1923.376.6024.892.0334.801.2737.3460619184
    2/01910.2924.466.6025.982.0335.891.2738.4373721104
    3/01911.5825.766.6027.282.0339.731.5242.7790226064.5
    4/01913.0027.186.6028.702.0341.151.5244.20111029034.5
    2503714.1728.556.6030.072.0342.521.5245.57129331794.5
    3503716.7931.176.6032.692.0345.141.5248.18176638175
    5003720.0434.426.6035.942.0348.391.5251.43247047265.5
    7506124.5939.226.6040.742.7954.711.5257.76364363926
    10006128.3743.006.6044.532.7958.501.9162.31481079086.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1254.0029770.41990.570.01860.18370.530+j0.4150.176+j0.0612943245244
    1/0261.6237560.33460.460.01740.17720.494+j0.3990.140+j0.0593067278272
    2/0269.2447350.26900.370.01620.17060.466+j0.3840.113+j0.0573201316303
    3/0299.7259720.21000.290.01490.17060.438+j0.3660.088+j0.0573359356333
    4/0309.8875290.16730.230.01370.16400.419+j0.3480.071+j0.0553532403367
    250320.0489000.14110.190.01280.16080.405+j0.3320.060+j0.0543699455411
    350337.82124600.10170.140.01160.15090.383+j0.3040.044+j0.0514019537459
    500360.68178000.06890.100.01010.14110.362+j0.2730.032+j0.0494415616499
    750403.86267000.04590.070.00850.13450.338+j0.2350.023+j0.0465001716557
    1000436.88356000.03610.060.00760.13120.323+j0.2110.020+j0.0455462825608
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC