SPEC 26402

HVTECK CU 1/C 320NLEPR TS PVC AIA PVC 25kV 133% CSA

Single Conductor, 320 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:320 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 320 NLEPR AIA 25kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchinchmilinchlb/1000ftlb/1000ftinch
    TBA1190.32213201.06801.241.45501.5534513444
    TBA1/0190.3621.043201.1801.281.59601.7141716354.5
    TBA2/0190.4051.0833201.143801.3231.633601.75350517734.5
    TBA3/0190.4561.1343201.194801.3741.684601.80461619444.5
    TBA4/0190.5121.193201.25801.431.74601.8675621505
    668365!4/0190.5121.193201.25801.431.774601.89475920365
    TBA250370.5581.2443201.304801.4841.794601.91487923415
    TBA350370.6611.3473201.407801.5871.897602.017119727815.5
    TBA500370.7891.4753201.5351101.7752.085602.205167035216
    TBA750610.9681.6643201.7241101.9642.274752.424245846156.5
    TBA1000611.1171.8133201.8731102.1132.423752.573324255897
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ! Unilay stranded
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    110.96690.1280.1750.0530.0580.528+j0.3780.176+j0.0633315245244
    1/0128440.1020.1390.050.0570.489+j0.3640.140+j0.0633439278272
    2/012.310640.0820.1120.0470.0550.460+j0.3500.113+j0.0613572316303
    3/012.613420.0640.0870.0430.0530.433+j0.3340.088+j0.0593730356333
    4/01316920.0510.070.040.0510.412+j0.3180.071+j0.0573904403367
    4/013.316920.0510.070.040.0520.412+j0.3180.071+j0.0573904403367
    25013.420000.0430.0590.0380.050.398+j0.3040.060+j0.0554071455411
    35014.128000.0310.0430.0340.0470.375+j0.2790.045+j0.0534390537459
    50015.440000.0210.030.030.0450.352+j0.2520.032+j0.0514787616499
    7501760000.0140.0210.0250.0430.328+j0.2180.023+j0.0485373716557
    10001880000.0110.0180.0230.0410.314+j0.1960.020+j0.0465834825608
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmmmkg/kmkg/kminch
    TBA1198.1825.408.1326.922.0331.5036.831.2739.3751320004
    TBA1/0199.1926.428.1327.942.0332.5140.391.5243.4362124334.5
    TBA2/01910.2927.518.1329.032.0333.6041.481.5244.5375226394.5
    TBA3/01911.5828.808.1330.332.0334.9042.771.5245.8291728934.5
    TBA4/01913.0030.238.1331.752.0336.3244.201.5247.24112532005
    668365!4/01913.0030.238.1331.752.0336.3245.061.5248.11113030305
    TBA2503714.1731.608.1333.122.0337.6945.571.5248.62130834845
    TBA3503716.7934.218.1335.742.0340.3148.181.5251.23178141395.5
    TBA5003720.0437.478.1338.992.7945.0852.961.5256.01248552406
    TBA7506124.5942.278.1343.792.7949.8957.761.9161.57365868686.5
    TBA10006128.3746.058.1347.572.7953.6761.541.9165.35482583177
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ! Unilay stranded
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1276.8629770.41990.570.01620.19030.528+j0.3780.176+j0.0633315245244
    1/0304.8037560.33460.460.01520.18700.489+j0.3640.140+j0.0633439278272
    2/0312.4247350.26900.370.01430.18040.460+j0.3500.113+j0.0613572316303
    3/0320.0459720.21000.290.01310.17390.433+j0.3340.088+j0.0593730356333
    4/0330.2075290.16730.230.01220.16730.412+j0.3180.071+j0.0573904403367
    4/0337.8275290.16730.230.01220.17060.412+j0.3180.071+j0.0573904403367
    250340.3689000.14110.190.01160.16400.398+j0.3040.060+j0.0554071455411
    350358.14124600.10170.140.01040.15420.375+j0.2790.045+j0.0534390537459
    500391.16178000.06890.100.00910.14760.352+j0.2520.032+j0.0514787616499
    750431.80267000.04590.070.00760.14110.328+j0.2180.023+j0.0485373716557
    1000457.20356000.03610.060.00700.13450.314+j0.1960.020+j0.0465834825608
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC