SPEC 26401
HVTECK CU 1/C 260NLEPR TS PVC AIA PVC 25kV 100% CSA
Single Conductor, 260 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:260 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 260 NLEPR AIA 25kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 1 | 19 | 0.322 | 0.88 | 260 | 0.94 | 80 | 1.33 | 50 | 1.43 | 335 | 1178 | 3.5 |
| 1/0 | 19 | 0.362 | 0.92 | 260 | 0.98 | 80 | 1.37 | 50 | 1.47 | 407 | 1289 | 4 |
| 2/0 | 19 | 0.405 | 0.963 | 260 | 1.023 | 80 | 1.413 | 50 | 1.513 | 495 | 1418 | 4 |
| 3/0 | 19 | 0.456 | 1.014 | 260 | 1.074 | 80 | 1.564 | 60 | 1.684 | 606 | 1751 | 4.5 |
| 4/0 | 19 | 0.512 | 1.07 | 260 | 1.13 | 80 | 1.62 | 60 | 1.74 | 746 | 1951 | 4.5 |
| 250 | 37 | 0.558 | 1.124 | 260 | 1.184 | 80 | 1.674 | 60 | 1.794 | 869 | 2136 | 4.5 |
| 350 | 37 | 0.661 | 1.227 | 260 | 1.287 | 80 | 1.777 | 60 | 1.897 | 1187 | 2565 | 5 |
| 500 | 37 | 0.789 | 1.355 | 260 | 1.415 | 80 | 1.905 | 60 | 2.025 | 1660 | 3176 | 5.5 |
| 750 | 61 | 0.968 | 1.544 | 260 | 1.604 | 110 | 2.154 | 60 | 2.274 | 2448 | 4295 | 6 |
| 1000 | 61 | 1.117 | 1.693 | 260 | 1.753 | 110 | 2.303 | 75 | 2.453 | 3232 | 5314 | 6.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 10 | 669 | 0.128 | 0.175 | 0.047 | 0.056 | 0.530+j0.415 | 0.176+j0.061 | 2943 | 245 | 244 |
| 1/0 | 10.3 | 844 | 0.102 | 0.139 | 0.043 | 0.054 | 0.494+j0.399 | 0.140+j0.059 | 3067 | 278 | 272 |
| 2/0 | 10.6 | 1064 | 0.082 | 0.112 | 0.041 | 0.052 | 0.466+j0.384 | 0.113+j0.057 | 3201 | 316 | 303 |
| 3/0 | 11.8 | 1342 | 0.064 | 0.087 | 0.038 | 0.052 | 0.438+j0.366 | 0.088+j0.057 | 3359 | 356 | 333 |
| 4/0 | 12.2 | 1692 | 0.051 | 0.07 | 0.035 | 0.05 | 0.419+j0.348 | 0.071+j0.055 | 3532 | 403 | 367 |
| 250 | 12.6 | 2000 | 0.043 | 0.059 | 0.032 | 0.049 | 0.405+j0.332 | 0.060+j0.054 | 3699 | 455 | 411 |
| 350 | 13.3 | 2800 | 0.031 | 0.043 | 0.029 | 0.046 | 0.383+j0.304 | 0.044+j0.051 | 4019 | 537 | 459 |
| 500 | 14.2 | 4000 | 0.021 | 0.03 | 0.025 | 0.043 | 0.362+j0.273 | 0.032+j0.049 | 4415 | 616 | 499 |
| 750 | 15.9 | 6000 | 0.014 | 0.021 | 0.021 | 0.041 | 0.338+j0.235 | 0.023+j0.046 | 5001 | 716 | 557 |
| 1000 | 17.2 | 8000 | 0.011 | 0.018 | 0.019 | 0.04 | 0.323+j0.211 | 0.020+j0.045 | 5462 | 825 | 608 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | kg/km | inch |
| 1 | 19 | 8.18 | 22.35 | 6.60 | 23.88 | 2.03 | 33.78 | 1.27 | 36.32 | 499 | 1753 | 3.5 |
| 1/0 | 19 | 9.19 | 23.37 | 6.60 | 24.89 | 2.03 | 34.80 | 1.27 | 37.34 | 606 | 1918 | 4 |
| 2/0 | 19 | 10.29 | 24.46 | 6.60 | 25.98 | 2.03 | 35.89 | 1.27 | 38.43 | 737 | 2110 | 4 |
| 3/0 | 19 | 11.58 | 25.76 | 6.60 | 27.28 | 2.03 | 39.73 | 1.52 | 42.77 | 902 | 2606 | 4.5 |
| 4/0 | 19 | 13.00 | 27.18 | 6.60 | 28.70 | 2.03 | 41.15 | 1.52 | 44.20 | 1110 | 2903 | 4.5 |
| 250 | 37 | 14.17 | 28.55 | 6.60 | 30.07 | 2.03 | 42.52 | 1.52 | 45.57 | 1293 | 3179 | 4.5 |
| 350 | 37 | 16.79 | 31.17 | 6.60 | 32.69 | 2.03 | 45.14 | 1.52 | 48.18 | 1766 | 3817 | 5 |
| 500 | 37 | 20.04 | 34.42 | 6.60 | 35.94 | 2.03 | 48.39 | 1.52 | 51.43 | 2470 | 4726 | 5.5 |
| 750 | 61 | 24.59 | 39.22 | 6.60 | 40.74 | 2.79 | 54.71 | 1.52 | 57.76 | 3643 | 6392 | 6 |
| 1000 | 61 | 28.37 | 43.00 | 6.60 | 44.53 | 2.79 | 58.50 | 1.91 | 62.31 | 4810 | 7908 | 6.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 254.00 | 2977 | 0.4199 | 0.57 | 0.0143 | 0.1837 | 0.530+j0.415 | 0.176+j0.061 | 2943 | 245 | 244 |
| 1/0 | 261.62 | 3756 | 0.3346 | 0.46 | 0.0131 | 0.1772 | 0.494+j0.399 | 0.140+j0.059 | 3067 | 278 | 272 |
| 2/0 | 269.24 | 4735 | 0.2690 | 0.37 | 0.0125 | 0.1706 | 0.466+j0.384 | 0.113+j0.057 | 3201 | 316 | 303 |
| 3/0 | 299.72 | 5972 | 0.2100 | 0.29 | 0.0116 | 0.1706 | 0.438+j0.366 | 0.088+j0.057 | 3359 | 356 | 333 |
| 4/0 | 309.88 | 7529 | 0.1673 | 0.23 | 0.0107 | 0.1640 | 0.419+j0.348 | 0.071+j0.055 | 3532 | 403 | 367 |
| 250 | 320.04 | 8900 | 0.1411 | 0.19 | 0.0098 | 0.1608 | 0.405+j0.332 | 0.060+j0.054 | 3699 | 455 | 411 |
| 350 | 337.82 | 12460 | 0.1017 | 0.14 | 0.0088 | 0.1509 | 0.383+j0.304 | 0.044+j0.051 | 4019 | 537 | 459 |
| 500 | 360.68 | 17800 | 0.0689 | 0.10 | 0.0076 | 0.1411 | 0.362+j0.273 | 0.032+j0.049 | 4415 | 616 | 499 |
| 750 | 403.86 | 26700 | 0.0459 | 0.07 | 0.0064 | 0.1345 | 0.338+j0.235 | 0.023+j0.046 | 5001 | 716 | 557 |
| 1000 | 436.88 | 35600 | 0.0361 | 0.06 | 0.0058 | 0.1312 | 0.323+j0.211 | 0.020+j0.045 | 5462 | 825 | 608 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000