SPEC 26371
HVTECK AL 3/C 175TRXLPE TS PVC AIA PVC 15kV 100% CSA
3 Conductor, 175 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 175 TRXLPE AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 2 | 7 | 0.268 | 0.656 | 175 | 0.716 | 1x8 | 110 | 2.103 | 60 | 2.223 | 232 | 1634 | 3 |
| 1 | 19 | 0.299 | 0.687 | 175 | 0.747 | 1x6 | 110 | 2.17 | 60 | 2.29 | 270 | 1779 | 3 |
| 1/0 | 19 | 0.336 | 0.724 | 175 | 0.784 | 1x6 | 110 | 2.249 | 60 | 2.369 | 279 | 1920 | 3 |
| 2/0 | 19 | 0.376 | 0.764 | 175 | 0.824 | 1x6 | 110 | 2.336 | 75 | 2.486 | 289 | 2151 | 3 |
| 3/0 | 19 | 0.423 | 0.811 | 175 | 0.871 | 1x6 | 110 | 2.437 | 75 | 2.587 | 301 | 2356 | 3.5 |
| 4/0 | 19 | 0.475 | 0.863 | 175 | 0.923 | 1x6 | 110 | 2.55 | 75 | 2.7 | 314 | 2596 | 3.5 |
| 250 | 37 | 0.52 | 0.916 | 175 | 0.976 | 1x4 | 110 | 2.664 | 75 | 2.814 | 374 | 2882 | 3.5 |
| 350 | 37 | 0.616 | 1.012 | 175 | 1.072 | 1x4 | 110 | 2.872 | 75 | 3.022 | 398 | 3383 | 4 |
| 500 | 37 | 0.736 | 1.132 | 175 | 1.192 | 1x3 | 125 | 3.161 | 85 | 3.331 | 466 | 4189 | 4.5 |
| 750 | 61 | 0.908 | 1.314 | 175 | 1.374 | 1x2 | 125 | 3.554 | 85 | 3.724 | 549 | 5382 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 15.6 | 1194 | 0.266 | 0.365 | 0.052 | 0.029 | 0.731+j0.508 | 0.365+j0.045 | 2249 | 135 | 157 |
| 1 | 16 | 1506 | 0.211 | 0.289 | 0.048 | 0.027 | 0.657+j0.491 | 0.289+j0.042 | 2345 | 154 | 178 |
| 1/0 | 16.6 | 1900 | 0.167 | 0.229 | 0.045 | 0.026 | 0.599+j0.473 | 0.229+j0.040 | 2460 | 176 | 202 |
| 2/0 | 17.4 | 2395 | 0.133 | 0.182 | 0.042 | 0.024 | 0.553+j0.455 | 0.182+j0.039 | 2584 | 204 | 229 |
| 3/0 | 18.1 | 3020 | 0.105 | 0.144 | 0.038 | 0.023 | 0.515+j0.435 | 0.144+j0.037 | 2730 | 234 | 260 |
| 4/0 | 18.9 | 3808 | 0.084 | 0.115 | 0.035 | 0.021 | 0.485+j0.413 | 0.115+j0.036 | 2891 | 268 | 294 |
| 250 | 19.7 | 4500 | 0.07 | 0.096 | 0.033 | 0.02 | 0.465+j0.393 | 0.096+j0.035 | 3055 | 296 | 323 |
| 350 | 21.2 | 6300 | 0.051 | 0.07 | 0.029 | 0.019 | 0.435+j0.359 | 0.070+j0.033 | 3352 | 363 | 386 |
| 500 | 23.3 | 9000 | 0.036 | 0.05 | 0.025 | 0.017 | 0.408+j0.322 | 0.050+j0.032 | 3724 | 447 | 465 |
| 750 | 26.1 | 13500 | 0.023 | 0.033 | 0.021 | 0.015 | 0.377+j0.275 | 0.033+j0.030 | 4288 | 566 | 563 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch |
| 2 | 7 | 6.81 | 16.66 | 4.44 | 18.19 | 1x8 | 2.79 | 53.42 | 1.52 | 56.46 | 345 | 2432 | 3 |
| 1 | 19 | 7.59 | 17.45 | 4.44 | 18.97 | 1x6 | 2.79 | 55.12 | 1.52 | 58.17 | 402 | 2647 | 3 |
| 1/0 | 19 | 8.53 | 18.39 | 4.44 | 19.91 | 1x6 | 2.79 | 57.12 | 1.52 | 60.17 | 415 | 2857 | 3 |
| 2/0 | 19 | 9.55 | 19.41 | 4.44 | 20.93 | 1x6 | 2.79 | 59.33 | 1.91 | 63.14 | 430 | 3201 | 3 |
| 3/0 | 19 | 10.74 | 20.60 | 4.44 | 22.12 | 1x6 | 2.79 | 61.90 | 1.91 | 65.71 | 448 | 3506 | 3.5 |
| 4/0 | 19 | 12.07 | 21.92 | 4.44 | 23.44 | 1x6 | 2.79 | 64.77 | 1.91 | 68.58 | 467 | 3863 | 3.5 |
| 250 | 37 | 13.21 | 23.27 | 4.44 | 24.79 | 1x4 | 2.79 | 67.67 | 1.91 | 71.48 | 557 | 4289 | 3.5 |
| 350 | 37 | 15.65 | 25.70 | 4.44 | 27.23 | 1x4 | 2.79 | 72.95 | 1.91 | 76.76 | 592 | 5034 | 4 |
| 500 | 37 | 18.69 | 28.75 | 4.44 | 30.28 | 1x3 | 3.18 | 80.29 | 2.16 | 84.61 | 693 | 6234 | 4.5 |
| 750 | 61 | 23.06 | 33.38 | 4.44 | 34.90 | 1x2 | 3.18 | 90.27 | 2.16 | 94.59 | 817 | 8009 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 396.24 | 5313 | 0.8727 | 1.20 | 0.0158 | 0.0951 | 0.731+j0.508 | 0.365+j0.045 | 2249 | 135 | 157 |
| 1 | 406.40 | 6702 | 0.6923 | 0.95 | 0.0146 | 0.0886 | 0.657+j0.491 | 0.289+j0.042 | 2345 | 154 | 178 |
| 1/0 | 421.64 | 8455 | 0.5479 | 0.75 | 0.0137 | 0.0853 | 0.599+j0.473 | 0.229+j0.040 | 2460 | 176 | 202 |
| 2/0 | 441.96 | 10658 | 0.4364 | 0.60 | 0.0128 | 0.0787 | 0.553+j0.455 | 0.182+j0.039 | 2584 | 204 | 229 |
| 3/0 | 459.74 | 13439 | 0.3445 | 0.47 | 0.0116 | 0.0755 | 0.515+j0.435 | 0.144+j0.037 | 2730 | 234 | 260 |
| 4/0 | 480.06 | 16946 | 0.2756 | 0.38 | 0.0107 | 0.0689 | 0.485+j0.413 | 0.115+j0.036 | 2891 | 268 | 294 |
| 250 | 500.38 | 20025 | 0.2297 | 0.31 | 0.0101 | 0.0656 | 0.465+j0.393 | 0.096+j0.035 | 3055 | 296 | 323 |
| 350 | 538.48 | 28035 | 0.1673 | 0.23 | 0.0088 | 0.0623 | 0.435+j0.359 | 0.070+j0.033 | 3352 | 363 | 386 |
| 500 | 591.82 | 40050 | 0.1181 | 0.16 | 0.0076 | 0.0558 | 0.408+j0.322 | 0.050+j0.032 | 3724 | 447 | 465 |
| 750 | 662.94 | 60075 | 0.0755 | 0.11 | 0.0064 | 0.0492 | 0.377+j0.275 | 0.033+j0.030 | 4288 | 566 | 563 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC