SPEC 26362
HVTECK AL 3/C 220NLEPR TS PVC AIA PVC 15kV 133% CSA
3 Conductor, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 220 NLEPR AIA 15kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch | |
| TBA | 2 | 7 | 0.268 | 0.746 | 220 | 0.806 | 1x8 | 110 | 2.297 | 75 | 2.447 | 255 | 1977 | 3 |
| TBA | 1 | 19 | 0.299 | 0.777 | 220 | 0.837 | 1x6 | 110 | 2.364 | 75 | 2.514 | 292 | 2131 | 3 |
| 665373 | 1 | 8 | 0.299 | 0.777 | 220 | 0.837 | 1x6 | 110 | 2.422 | 75 | 2.572 | 302 | 2755 | 3.5 |
| TBA | 1/0 | 19 | 0.336 | 0.814 | 220 | 0.874 | 1x6 | 110 | 2.444 | 75 | 2.594 | 302 | 2285 | 3.5 |
| TBA | 2/0 | 19 | 0.376 | 0.854 | 220 | 0.914 | 1x6 | 110 | 2.53 | 75 | 2.68 | 312 | 2464 | 3.5 |
| TBA | 3/0 | 19 | 0.423 | 0.901 | 220 | 0.961 | 1x6 | 110 | 2.632 | 75 | 2.782 | 323 | 2680 | 3.5 |
| TBA | 4/0 | 19 | 0.475 | 0.953 | 220 | 1.013 | 1x6 | 110 | 2.744 | 75 | 2.894 | 336 | 2934 | 3.5 |
| TBA | 250 | 37 | 0.52 | 1.006 | 220 | 1.066 | 1x4 | 110 | 2.859 | 75 | 3.009 | 396 | 3234 | 4 |
| TBA | 350 | 37 | 0.616 | 1.102 | 220 | 1.162 | 1x4 | 125 | 3.096 | 85 | 3.266 | 420 | 3827 | 4 |
| TBA | 500 | 37 | 0.736 | 1.222 | 220 | 1.282 | 1x3 | 125 | 3.355 | 85 | 3.525 | 488 | 4602 | 4.5 |
| 669887 | 750 | 58 | 0.908 | 1.416 | 220 | 1.476 | 1x1/0 | 125 | 3.861 | 85 | 4.031 | 703 | 7025 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 17.1 | 1194 | 0.266 | 0.365 | 0.046 | 0.031 | 0.735+j0.471 | 0.365+j0.047 | 2528 | 135 | 157 |
| 1 | 17.6 | 1506 | 0.211 | 0.289 | 0.044 | 0.03 | 0.660+j0.455 | 0.289+j0.044 | 2624 | 154 | 178 |
| 1 | 18 | 1506 | 0.211 | 0.289 | 0.044 | 0.03 | 0.660+j0.455 | 0.289+j0.044 | 2624 | 154 | 178 |
| 1/0 | 18.2 | 1900 | 0.167 | 0.229 | 0.041 | 0.028 | 0.600+j0.439 | 0.229+j0.043 | 2739 | 176 | 202 |
| 2/0 | 18.8 | 2395 | 0.133 | 0.182 | 0.038 | 0.026 | 0.553+j0.422 | 0.182+j0.041 | 2863 | 204 | 229 |
| 3/0 | 19.5 | 3020 | 0.105 | 0.144 | 0.035 | 0.025 | 0.514+j0.403 | 0.144+j0.040 | 3009 | 234 | 260 |
| 4/0 | 20.3 | 3808 | 0.084 | 0.115 | 0.032 | 0.023 | 0.483+j0.383 | 0.115+j0.038 | 3170 | 268 | 294 |
| 250 | 21.1 | 4500 | 0.07 | 0.096 | 0.03 | 0.022 | 0.462+j0.365 | 0.096+j0.037 | 3334 | 296 | 323 |
| 350 | 22.9 | 6300 | 0.051 | 0.07 | 0.027 | 0.021 | 0.430+j0.334 | 0.070+j0.035 | 3631 | 363 | 386 |
| 500 | 24.7 | 9000 | 0.036 | 0.05 | 0.023 | 0.019 | 0.402+j0.300 | 0.050+j0.033 | 4003 | 447 | 465 |
| 750 | 28.2 | 13500 | 0.023 | 0.033 | 0.02 | 0.017 | 0.369+j0.255 | 0.033+j0.032 | 4604 | 566 | 563 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch | |
| TBA | 2 | 7 | 6.81 | 18.95 | 5.59 | 20.47 | 1x8 | 2.79 | 58.34 | 1.91 | 62.15 | 379 | 2942 | 3 |
| TBA | 1 | 19 | 7.59 | 19.74 | 5.59 | 21.26 | 1x6 | 2.79 | 60.05 | 1.91 | 63.86 | 435 | 3171 | 3 |
| 665373 | 1 | 8 | 7.59 | 19.74 | 5.59 | 21.26 | 1x6 | 2.79 | 61.52 | 1.91 | 65.33 | 449 | 4100 | 3.5 |
| TBA | 1/0 | 19 | 8.53 | 20.68 | 5.59 | 22.20 | 1x6 | 2.79 | 62.08 | 1.91 | 65.89 | 449 | 3400 | 3.5 |
| TBA | 2/0 | 19 | 9.55 | 21.69 | 5.59 | 23.22 | 1x6 | 2.79 | 64.26 | 1.91 | 68.07 | 464 | 3667 | 3.5 |
| TBA | 3/0 | 19 | 10.74 | 22.89 | 5.59 | 24.41 | 1x6 | 2.79 | 66.85 | 1.91 | 70.66 | 481 | 3988 | 3.5 |
| TBA | 4/0 | 19 | 12.07 | 24.21 | 5.59 | 25.73 | 1x6 | 2.79 | 69.70 | 1.91 | 73.51 | 500 | 4366 | 3.5 |
| TBA | 250 | 37 | 13.21 | 25.55 | 5.59 | 27.08 | 1x4 | 2.79 | 72.62 | 1.91 | 76.43 | 589 | 4813 | 4 |
| TBA | 350 | 37 | 15.65 | 27.99 | 5.59 | 29.51 | 1x4 | 3.18 | 78.64 | 2.16 | 82.96 | 625 | 5695 | 4 |
| TBA | 500 | 37 | 18.69 | 31.04 | 5.59 | 32.56 | 1x3 | 3.18 | 85.22 | 2.16 | 89.54 | 726 | 6849 | 4.5 |
| 669887 | 750 | 58 | 23.06 | 35.97 | 5.59 | 37.49 | 1x1/0 | 3.18 | 98.07 | 2.16 | 102.39 | 1046 | 10454 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 434.34 | 5313 | 0.8727 | 1.20 | 0.0140 | 0.1017 | 0.735+j0.471 | 0.365+j0.047 | 2528 | 135 | 157 |
| 1 | 447.04 | 6702 | 0.6923 | 0.95 | 0.0134 | 0.0984 | 0.660+j0.455 | 0.289+j0.044 | 2624 | 154 | 178 |
| 1 | 457.20 | 6702 | 0.6923 | 0.95 | 0.0134 | 0.0984 | 0.660+j0.455 | 0.289+j0.044 | 2624 | 154 | 178 |
| 1/0 | 462.28 | 8455 | 0.5479 | 0.75 | 0.0125 | 0.0919 | 0.600+j0.439 | 0.229+j0.043 | 2739 | 176 | 202 |
| 2/0 | 477.52 | 10658 | 0.4364 | 0.60 | 0.0116 | 0.0853 | 0.553+j0.422 | 0.182+j0.041 | 2863 | 204 | 229 |
| 3/0 | 495.30 | 13439 | 0.3445 | 0.47 | 0.0107 | 0.0820 | 0.514+j0.403 | 0.144+j0.040 | 3009 | 234 | 260 |
| 4/0 | 515.62 | 16946 | 0.2756 | 0.38 | 0.0098 | 0.0755 | 0.483+j0.383 | 0.115+j0.038 | 3170 | 268 | 294 |
| 250 | 535.94 | 20025 | 0.2297 | 0.31 | 0.0091 | 0.0722 | 0.462+j0.365 | 0.096+j0.037 | 3334 | 296 | 323 |
| 350 | 581.66 | 28035 | 0.1673 | 0.23 | 0.0082 | 0.0689 | 0.430+j0.334 | 0.070+j0.035 | 3631 | 363 | 386 |
| 500 | 627.38 | 40050 | 0.1181 | 0.16 | 0.0070 | 0.0623 | 0.402+j0.300 | 0.050+j0.033 | 4003 | 447 | 465 |
| 750 | 716.28 | 60075 | 0.0755 | 0.11 | 0.0061 | 0.0558 | 0.369+j0.255 | 0.033+j0.032 | 4604 | 566 | 563 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E