SPEC 26362

HVTECK AL 3/C 220NLEPR TS PVC AIA PVC 15kV 133% CSA

3 Conductor, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 220 NLEPR AIA 15kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    TBA270.2680.7462200.8061x81102.297752.44725519773
    TBA1190.2990.7772200.8371x61102.364752.51429221313
    665373180.2990.7772200.8371x61102.422752.57230227553.5
    TBA1/0190.3360.8142200.8741x61102.444752.59430222853.5
    TBA2/0190.3760.8542200.9141x61102.53752.6831224643.5
    TBA3/0190.4230.9012200.9611x61102.632752.78232326803.5
    TBA4/0190.4750.9532201.0131x61102.744752.89433629343.5
    TBA250370.521.0062201.0661x41102.859753.00939632344
    TBA350370.6161.1022201.1621x41253.096853.26642038274
    TBA500370.7361.2222201.2821x31253.355853.52548846024.5
    669887750580.9081.4162201.4761x1/01253.861854.03170370255.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    217.111940.2660.3650.0460.0310.735+j0.4710.365+j0.0472528135157
    117.615060.2110.2890.0440.030.660+j0.4550.289+j0.0442624154178
    11815060.2110.2890.0440.030.660+j0.4550.289+j0.0442624154178
    1/018.219000.1670.2290.0410.0280.600+j0.4390.229+j0.0432739176202
    2/018.823950.1330.1820.0380.0260.553+j0.4220.182+j0.0412863204229
    3/019.530200.1050.1440.0350.0250.514+j0.4030.144+j0.0403009234260
    4/020.338080.0840.1150.0320.0230.483+j0.3830.115+j0.0383170268294
    25021.145000.070.0960.030.0220.462+j0.3650.096+j0.0373334296323
    35022.963000.0510.070.0270.0210.430+j0.3340.070+j0.0353631363386
    50024.790000.0360.050.0230.0190.402+j0.3000.050+j0.0334003447465
    75028.2135000.0230.0330.020.0170.369+j0.2550.033+j0.0324604566563
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    TBA276.8118.955.5920.471x82.7958.341.9162.1537929423
    TBA1197.5919.745.5921.261x62.7960.051.9163.8643531713
    665373187.5919.745.5921.261x62.7961.521.9165.3344941003.5
    TBA1/0198.5320.685.5922.201x62.7962.081.9165.8944934003.5
    TBA2/0199.5521.695.5923.221x62.7964.261.9168.0746436673.5
    TBA3/01910.7422.895.5924.411x62.7966.851.9170.6648139883.5
    TBA4/01912.0724.215.5925.731x62.7969.701.9173.5150043663.5
    TBA2503713.2125.555.5927.081x42.7972.621.9176.4358948134
    TBA3503715.6527.995.5929.511x43.1878.642.1682.9662556954
    TBA5003718.6931.045.5932.561x33.1885.222.1689.5472668494.5
    6698877505823.0635.975.5937.491x1/03.1898.072.16102.391046104545.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2434.3453130.87271.200.01400.10170.735+j0.4710.365+j0.0472528135157
    1447.0467020.69230.950.01340.09840.660+j0.4550.289+j0.0442624154178
    1457.2067020.69230.950.01340.09840.660+j0.4550.289+j0.0442624154178
    1/0462.2884550.54790.750.01250.09190.600+j0.4390.229+j0.0432739176202
    2/0477.52106580.43640.600.01160.08530.553+j0.4220.182+j0.0412863204229
    3/0495.30134390.34450.470.01070.08200.514+j0.4030.144+j0.0403009234260
    4/0515.62169460.27560.380.00980.07550.483+j0.3830.115+j0.0383170268294
    250535.94200250.22970.310.00910.07220.462+j0.3650.096+j0.0373334296323
    350581.66280350.16730.230.00820.06890.430+j0.3340.070+j0.0353631363386
    500627.38400500.11810.160.00700.06230.402+j0.3000.050+j0.0334003447465
    750716.28600750.07550.110.00610.05580.369+j0.2550.033+j0.0324604566563
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC